Plan Review Details - Permit 17081411
Plan Review Stops For Permit 17081411
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-12-05 Cont ID  
Sent By jleahy Date 2017-12-05 Time 14:22 Rev Time 0.00
Received By jleahy Date 2017-12-05 Time 14:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-11-07 Cont ID  
Sent By jpearson Date 2017-11-07 Time 13:36 Rev Time 0.00
Received By jpearson Date 2017-11-07 Time 13:36 Sent To I
Notes
2017-11-07 13:36:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. COPY OF CONTRACT SUPPLIED DOES NOT INCLUDE COST OF
 CONTRACT. PROVIDE CORRECTION, SHOWING VALUE OF CUSTOMER
 SUPPLIED EQUIPMENT IN ADDITION TO THE ACTUAL CONTRACT
 COST. FBC 109.3 PLEASE BE ADVISED THAT THIS COMMENT HAS
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: ?WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
 2. ELECTRICAL PLAN MUST BE SIGNED AND SEALED BY A
 LICENSED DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FBC 107.2.1;
 FS 471, 481
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By jleahy Date 2017-09-13 Time 16:12 Rev Time 0.00
Received By jleahy Date 2017-09-13 Time 16:11 Sent To  
Notes
2017-09-13 16:13:27FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR WORK TO LOW SUBMIT A SIGNED CONTRACT FOR WORK
 PERFORMED.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL
  
 NEED CUT SHEETS ON GATE AND CONTROLER.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-12-05 Cont ID  
Sent By pleduc Date 2017-12-05 Time   Rev Time 0.00
Received By pleduc Date 2017-12-04 Time 16:53 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-03 Cont ID  
Sent By pleduc Date 2017-11-03 Time   Rev Time 0.00
Received By pleduc Date 2017-11-03 Time 13:21 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By pleduc Date 2017-09-13 Time   Rev Time 0.00
Received By pleduc Date 2017-09-13 Time 13:24 Sent To E
Notes
2017-09-13 15:11:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THERE IS LIMITED DETAIL PROVIDED INDICATING WHERE
 THIS GATE IS LOCATED AND WHETHER IT IS ENTRY OR EGRESS
 OR BOTH.
  
 PLEASE PROVIDE A DETAILED SITE PALN AND VEHICLE PATH OF
 TRAVEL DIRECTION.
  
  
  
 2) THERE IS INSUFFICIENT INFORMATION PROVIDED TO REVIEW
 REGARDING HOW THE GATE(S) WILL FUNCTION FOR AN
 EMERGENCY VEHICLE.
  
 PLEASE PROVIDE AN EXPLANATION. A KNOX KEY SWITCH MAY BE
 REQUIRED IF ACCESS/EGRESS IS CONTROLLED.
  
  
  
 3) NEW DELINIATORS ARE INDICATED, THOUGH IT IS NOTED AS
 CUSTOMER PROVIDED, INFORMATION ON THESE NEEDS TO BE
 PROVIDED; WHAT TYPE, SIZE, ETC.
  
 PLEASE PROVIDE SPEC SHEETS.
  
  
  
  
 4) THERE ARE NO INDICATIONS OF THE DIMENSION/WIDTH OF
 THE TRAVEL LANE BETWEEN THE MEDIUM AND THE NEW
 DELINIATORS.
  
 FOR EMERGECNY VEHILES ACCESS IT MUST BE 20' MINIMUM.
  
 PLEASE PROVIDE DIMENSION ON THE SITE PLAN
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-05 Cont ID  
Sent By jleahy Date 2017-12-05 Time 14:23 Rev Time 0.00
Received By jleahy Date 2017-12-01 Time 12:55 Sent To  
Notes
2017-12-04 12:55:47RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-07 Cont ID  
Sent By jpearson Date 2017-11-07 Time 13:36 Rev Time 0.00
Received By jpearson Date 2017-11-01 Time 11:46 Sent To  
Notes
2017-11-02 11:47:03RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-13 Cont ID  
Sent By jleahy Date 2017-09-13 Time 16:13 Rev Time 0.00
Received By jleahy Date 2017-08-30 Time 12:43 Sent To  
Notes
2017-09-13 09:16:35ADDED F/D GATE ACCESS JLEAHY SENT TO F/D 9/13/17
2017-08-31 12:43:44ELEC <5K