Plan Review Details - Permit 17081347
| Plan Review Stops For Permit 17081347 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2017-09-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-09-19 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-09-19 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-09-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-09-19 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-09-07 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2017-09-07 10:30:44 | SHOW THE DISTANCE FROM DRIVEWAY. WHAT KIND OF | | | PROTECTION WILL BE USED, PLEASE PROVIDE DETAILS ON TYPE | | | OF METHOD. NFPA 58 SEC. 6.6.6.1.(B) | | | | | | THE LOCATION OF THE UNDERGROUND LP TANK SHALL COMPLY | | | WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE DISTANCE OF | | | THE LP TANK FROM THE EXTERIOR WALL OF THE STRUCTURE. | | | | | | THE TABLE SUBMITTED FOR 2 PSI INLET PRESSURE DOES NOT | | | INDICATE THE TYPE OF PIPE THE TABLE IS FOR. WHAT IS THE | | | TABLE NUMBER? PLEASE REFER TO THE EDITION IN EFFECT | | | WHICH IS 2011 EDITION FBC 2014 > NFPA 2011 | | | | | | REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, | | | INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE | | | AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM | | | THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR | | | EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. | | | | | | ENGINEERS SEAL AND SIGNATURE IS A COPY, PLEASE SUPPLY | | | TWO COPIES WITH AN INK SEAL AND ORIGINAL SIGNATURE OF | | | THE ENGINEER. F.A.C. RULE 61 G15-23.001, 23,002 | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEW | | | 561-805-6720 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-09-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-09-19 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-09-19 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-09-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-09-19 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-08-29 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2017-08-30 10:57:54 | PLUMB <5K |
|
|
|