Plan Review Details - Permit 17081338
Plan Review Stops For Permit 17081338
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-10-06 Cont ID  
Sent By jleahy Date 2017-10-06 Time 17:02 Rev Time 0.00
Received By jleahy Date 2017-10-06 Time 17:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-06 Cont ID  
Sent By jleahy Date 2017-10-06 Time 17:03 Rev Time 0.00
Received By jleahy Date 2017-09-28 Time 09:08 Sent To  
Notes
2017-09-29 09:08:54RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-13 Cont ID  
Sent By hmoser Date 2017-09-13 Time 13:30 Rev Time 0.00
Received By hmoser Date 2017-08-29 Time 11:03 Sent To  
Notes
2017-08-30 11:03:16MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-06 Cont ID  
Sent By hmoser Date 2017-10-06 Time 13:02 Rev Time 0.00
Received By hmoser Date 2017-10-06 Time 11:40 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By hmoser Date 2017-09-13 Time 13:30 Rev Time 0.00
Received By hmoser Date 2017-09-13 Time 13:15 Sent To  
Notes
2017-09-13 13:30:27PLAN DENIED
 1) PROVIDE A PLAN SHOWING LOCATION OF
 AIR HANDLER AND CONDENSER AND EQUIPMENT SCHEDULE.
 2) PROVIDE TWO COPIES OF PROPERTY SURVEY WITH
 THE PLAN. SECTION 107 FBC. 2014
 3) ELECTRICAL PERMIT REQUIRED FOR DISCONNECT AT
 AIR HANDLER AND CONDENSER
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676