Plan Review Details - Permit 17081240
Plan Review Stops For Permit 17081240
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-09 Cont ID  
Sent By jleahy Date 2018-08-09 Time 08:02 Rev Time 0.00
Received By jleahy Date 2018-08-09 Time 15:17 Sent To  
Notes
2018-08-02 08:01:45FIRE PUMP PERMIT BY OYTHERS JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By jleahy Date 2017-09-13 Time 16:05 Rev Time 0.00
Received By jleahy Date 2017-09-13 Time 16:05 Sent To M
Notes
2017-09-13 16:06:31FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN FOR PROPOSED FIRE PUMP AND CONTROLER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-27 Cont ID  
Sent By pleduc Date 2018-07-27 Time   Rev Time 0.00
Received By pleduc Date 2018-07-27 Time 13:14 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By wjolin Date 2017-08-30 Time 10:44 Rev Time 0.00
Received By wjolin Date 2017-08-30 Time 10:17 Sent To E
Notes
2017-08-30 10:44:424396 EASLEY DRIVE - DEWATERING BUILDING
 FS PERMIT #17081240
 UGFIRELINE: #16020206
 BUILDING MASTER #15060563
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS DO NOT INDICATE AN ADDRESS FOR THE FACILITY.
  
 THE PERMIT VALUE OF $15,000 IS UNDERVALUED FOR THE
 SCOPE OF THE PROJECT. PERMIT VALUES SHALL INCLUDE BOTH
 LABOR AND MATERIALS. SUBMIT A COPY OF THE SIGNED
 CONTRACT INDICATING VALUE.
  
 THE UNDERGROUND FIRE MAIN (PERMIT #16020206) DOES NOT
 SHOW A SUPPLY TO A FIRE PUMP AND NO REVISION WAS EVER
 SUBMITTED SHOWING THIS CHANGE. THIS PERMIT HAS BEEN
 CLOSED. A SEPARATE UNDERGROUND PERMIT WILL BE NEEDED BY
 A FLORIDA STATE FIRE PROTECTION CONTRACTOR FOR THIS
 UNDERGROUND WORK.
  
 THE FIRE SPRINKLER SYSTEM DESIGN CANNOT BE VERIFIED
 WITHOUT THE FIRE PUMP AND PUMP HOUSE SUBMITTALS. WHAT
 CONTRACTOR IS BUYING AND INSTALLING THE PUMP AND HOUSE?
 IS THE ELECTRICAL SERVICE FOR THE FIRE PUMP, JOCKEY
 PUMP AND CONTROLLERS PERMITTED?
  
 STANDPIPE PROVIDED FOR EXTERIOR EGRESS STAIR.
  
 CLOSELY SPACED SPRINKLER DEMAND NOT FOUND IN ANY
 HYDRAULIC CALCULATIONS.
  
 SUBMIT THE SAFETY DATA SHEET JUSTIFYING SPRINKLER
 PROTECTION IS NOT REQUIRED IN THE ELEVATOR PIT
 UTILIZING NON-COMBUSTIBLE HYDRAULIC OIL.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-02 Cont ID  
Sent By jleahy Date 2018-08-02 Time 08:01 Rev Time 0.00
Received By jleahy Date 2018-07-25 Time 16:29 Sent To  
Notes
2018-07-26 16:29:17RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-18 Cont ID  
Sent By hmoser Date 2017-09-18 Time 10:18 Rev Time 0.00
Received By hmoser Date 2017-08-25 Time 10:53 Sent To  
Notes
2017-08-28 10:54:05ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-08-01 Cont ID  
Sent By hmoser Date 2018-08-01 Time 14:48 Rev Time 0.00
Received By hmoser Date 2018-08-01 Time 14:34 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-18 Cont ID  
Sent By hmoser Date 2017-09-18 Time 10:18 Rev Time 0.00
Received By hmoser Date 2017-09-18 Time 10:14 Sent To  
Notes
2017-09-18 10:18:04PLEASE REFER TO FIRE COMMENTS.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676