| Plan Review Stops For Permit 17081236 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-11-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-06 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-11-06 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2017-11-06 14:17:05 | PROVISO - REDLINED 18" MANEUVERING CLEARANCE REQUIRED | | | AT DOOR 104 | | | | | | ****** | | | INTERNAL USE: | | | | | | USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG | | | SQUARE FEET - | | | | | | CONSTRUCTION TYPE: | | | UNITS: 1 | | | FLOORS: 1 | | | BEDROOMS: | | | ROOMS: | | | SQ FT LIVABLE: | | | SQ FT FOOTPRINT: | | | SQ FT ROOF: | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 166 | | | PROP USE: FL BAR ASN | | | SPRINKLER SYS? | | | SPRK REQ'D? | | | BATHRMS: | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED B | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2017-09-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-27 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-27 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2017-09-27 16:31:59 | PROVISO - REDLINED 18" MANEUVERING CLEARANCE REQUIRED | | | AT DOOR 104 | | | | | | ****** | | | INTERNAL USE: | | | | | | USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG | | | SQUARE FEET - | | | | | | CONSTRUCTION TYPE: | | | UNITS: 1 | | | FLOORS: 1 | | | BEDROOMS: | | | ROOMS: | | | SQ FT LIVABLE: | | | SQ FT FOOTPRINT: | | | SQ FT ROOF: | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 166 | | | PROP USE: FL BAR ASN | | | SPRINKLER SYS? | | | SPRK REQ'D? | | | BATHRMS: | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED B | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-11-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-06 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-06 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-09-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-09-27 |
Time |
06:32 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-09-27 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2017-09-27 06:32:06 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT | | | CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS | | | ADEQUATE. NEC 110.10 | | | 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. NEC 250.94 | | | 3. PANEL A, CIRCUIT 21, SHOWS A #12 WIRE ON A 30 AMP | | | BREAKER. PROVIDE CORRECTION. NEC 310.15(B)(16) | | | 4. PANEL B, CIRCUIT 17,19, SHOWS A #12 WIRE ON A 30 AMP | | | BREAKER. PROVIDE CORRECTION. NEC 310.15(B)(16) | | | 5. PANEL CU SHOWS A 40 AMP BREAKER FOR CU-2. SPECS ON | | | THE MECHANICAL SHEET CALL FOR A 45 AMP BREAKER. PROVIDE | | | CORRECTION. NEC 440.22(C) | | | 6. POWER PLAN SHOWS LANDSCAPE AND SIGN ON CIRCUIT B-24. | | | THE SIGN CIRCUIT IS REQUIRED TO BE A DEDICATED CIRCUIT. | | | PROVIDE CORRECTION. NEC 600.5(A) | | | 7. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. FBC CE 405.7.1 | | | 8. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED | | | SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, | | | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, | | | ETC. FBC 105.1, 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-10-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-10-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-10-18 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-08-31 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-08-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-08-30 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-11-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-11-13 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2017-11-13 14:59:44 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-07 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-16 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-10-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-03 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-08-25 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-16 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-16 |
Time |
07:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-11-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-07 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-07 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2017-11-07 12:42:35 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17081236 | | | 11/7/17 | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | 1) 2ND REQUEST FOR THE REQUIRED INPUT DATA REPORT TO BE | | | SUBMITTED WITH THE ENERGYGAUGE COMPLIANCE FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-09-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-09-22 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-09-22 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2017-09-22 14:18:23 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17081236 | | | 9/22/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE INPUT DATA REPORT AS REQUIRED BY THE | | | CHECKLIST ON PAGE 1 OF THE ENERGYGAUGE ASHRAE 90.1 | | | COMPLIANCE SUBMITTAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-11-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-07 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-07 |
Time |
17:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-10-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-03 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-03 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2017-10-03 09:47:33 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 | | | DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | | DISPENSER. | | | | | | 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR | | | WALL. | | | THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM | | | AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 | | | INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE | | | OTHER SIDE. | | | | | | 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE | | | WALL. | | | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, | | | LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND | | | EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. | | | | | | 4. ON THE SANITARY ISOMETRIC DRAWING IT SHOWS THE | | | BRANCH DRAIN FOR THE FLOOR DRAIN IN PANTRY AS 3" | | | CONNECTING TO A 2" . PIPING CAN NOT BE REDUCED IN | | | DIRECTION OF FLOW. PER FBC PL 704.2 | | | | | | 5. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1 | | | | | | 6. PLEASE SIZE ENTIRE LENGTH OF THE BUILDING DRAIN, THE | | | SANITARY SIZING CALCULATIONS ON SHT P1.1 SHOWS 4" THE | | | ISOMETRIC DRAWING ONLY SHOWS 3" PLEASE CLARIFY. SHALL | | | COMPLY WITH FBC PL TABLE 710.1(1) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-10-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2017-10-20 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2017-10-23 16:09:10 | ZONING PROVISO: | | | | | | 1.) A SEPARATE LANDSCAPE PERMIT, ADDRESSING ALL | | | LANDSCAPE DEFICIENCIES SHALL BE SUBMITTED, APPROVED AND | | | IMPLEMENTED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2017-08-31 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-08-31 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2017-08-31 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-08-31 15:54:15 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PROVIDE HEIGHT DIMENSIONS ON SHEET A-3.1.1 | | | (BUILDING ELEVATIONS). | | | | | | 2.) THE VALUE OF THE CONSTRUCTION ($430,000.00) EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE ($678,392.00) ACCORDING TO | | | THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, | | | PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDRS), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. | | | | | | | | | NOTES: | | | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|