Plan Review Details - Permit 17081236
Plan Review Stops For Permit 17081236
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-06 Cont ID  
Sent By shill Date 2017-11-06 Time 14:16 Rev Time 0.00
Received By shill Date 2017-11-06 Time 14:16 Sent To  
Notes
2017-11-06 14:17:05PROVISO - REDLINED 18" MANEUVERING CLEARANCE REQUIRED
 AT DOOR 104
  
 ******
 INTERNAL USE:
  
 USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET -
  
 CONSTRUCTION TYPE:
 UNITS: 1
 FLOORS: 1
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE:
 SQ FT FOOTPRINT:
 SQ FT ROOF:
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 166
 PROP USE: FL BAR ASN
 SPRINKLER SYS?
 SPRK REQ'D?
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-09-27 Cont ID  
Sent By shill Date 2017-09-27 Time 16:31 Rev Time 0.00
Received By shill Date 2017-09-27 Time 16:31 Sent To  
Notes
2017-09-27 16:31:59PROVISO - REDLINED 18" MANEUVERING CLEARANCE REQUIRED
 AT DOOR 104
  
 ******
 INTERNAL USE:
  
 USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET -
  
 CONSTRUCTION TYPE:
 UNITS: 1
 FLOORS: 1
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE:
 SQ FT FOOTPRINT:
 SQ FT ROOF:
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 166
 PROP USE: FL BAR ASN
 SPRINKLER SYS?
 SPRK REQ'D?
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-06 Cont ID  
Sent By jpearson Date 2017-11-06 Time 14:41 Rev Time 0.00
Received By jpearson Date 2017-11-06 Time 14:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-27 Cont ID  
Sent By jpearson Date 2017-09-27 Time 06:32 Rev Time 0.00
Received By jpearson Date 2017-09-27 Time 06:32 Sent To  
Notes
2017-09-27 06:32:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS
 ADEQUATE. NEC 110.10
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 3. PANEL A, CIRCUIT 21, SHOWS A #12 WIRE ON A 30 AMP
 BREAKER. PROVIDE CORRECTION. NEC 310.15(B)(16)
 4. PANEL B, CIRCUIT 17,19, SHOWS A #12 WIRE ON A 30 AMP
 BREAKER. PROVIDE CORRECTION. NEC 310.15(B)(16)
 5. PANEL CU SHOWS A 40 AMP BREAKER FOR CU-2. SPECS ON
 THE MECHANICAL SHEET CALL FOR A 45 AMP BREAKER. PROVIDE
 CORRECTION. NEC 440.22(C)
 6. POWER PLAN SHOWS LANDSCAPE AND SIGN ON CIRCUIT B-24.
 THE SIGN CIRCUIT IS REQUIRED TO BE A DEDICATED CIRCUIT.
 PROVIDE CORRECTION. NEC 600.5(A)
 7. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1
 8. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 ETC. FBC 105.1, 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-18 Cont ID  
Sent By pleduc Date 2017-10-18 Time   Rev Time 0.00
Received By pleduc Date 2017-10-18 Time 13:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-31 Cont ID  
Sent By pleduc Date 2017-08-31 Time   Rev Time 0.00
Received By pleduc Date 2017-08-30 Time 13:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-11-16 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-13 Time 14:59 Sent To  
Notes
2017-11-13 14:59:44RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-07 Cont ID  
Sent By gjohnson Date 2017-11-07 Time 17:07 Rev Time 0.00
Received By gjohnson Date 2017-10-16 Time 15:30 Sent To  
Notes
2017-10-17 15:30:41C13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-03 Cont ID  
Sent By gjohnson Date 2017-10-03 Time 09:47 Rev Time 0.00
Received By gjohnson Date 2017-08-25 Time 11:07 Sent To  
Notes
2017-08-28 11:08:01C08

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-11-16 Cont ID  
Sent By ccole Date 2017-11-16 Time 11:56 Rev Time 0.00
Received By ccole Date 2017-11-16 Time 07:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-07 Cont ID  
Sent By ccole Date 2017-11-07 Time 12:37 Rev Time 0.00
Received By ccole Date 2017-11-07 Time 12:30 Sent To  
Notes
2017-11-07 12:42:352ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17081236
 11/7/17
  
 PLAN REVIEW RESULTS: DENIED
  
 1) 2ND REQUEST FOR THE REQUIRED INPUT DATA REPORT TO BE
 SUBMITTED WITH THE ENERGYGAUGE COMPLIANCE FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-22 Cont ID  
Sent By ccole Date 2017-09-22 Time 14:15 Rev Time 0.00
Received By ccole Date 2017-09-22 Time 14:15 Sent To  
Notes
2017-09-22 14:18:231ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17081236
 9/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE INPUT DATA REPORT AS REQUIRED BY THE
 CHECKLIST ON PAGE 1 OF THE ENERGYGAUGE ASHRAE 90.1
 COMPLIANCE SUBMITTAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-11-07 Cont ID  
Sent By gjohnson Date 2017-11-07 Time 17:06 Rev Time 0.00
Received By gjohnson Date 2017-11-07 Time 17:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-03 Cont ID  
Sent By gjohnson Date 2017-10-03 Time 09:16 Rev Time 0.00
Received By gjohnson Date 2017-10-03 Time 09:16 Sent To  
Notes
2017-10-03 09:47:331ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR
 WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 4. ON THE SANITARY ISOMETRIC DRAWING IT SHOWS THE
 BRANCH DRAIN FOR THE FLOOR DRAIN IN PANTRY AS 3"
 CONNECTING TO A 2" . PIPING CAN NOT BE REDUCED IN
 DIRECTION OF FLOW. PER FBC PL 704.2
  
 5. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
 6. PLEASE SIZE ENTIRE LENGTH OF THE BUILDING DRAIN, THE
 SANITARY SIZING CALCULATIONS ON SHT P1.1 SHOWS 4" THE
 ISOMETRIC DRAWING ONLY SHOWS 3" PLEASE CLARIFY. SHALL
 COMPLY WITH FBC PL TABLE 710.1(1)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-10-23 Time   Rev Time 0.00
Received By llouie Date 2017-10-20 Time 10:24 Sent To  
Notes
2017-10-23 16:09:10ZONING PROVISO:
  
 1.) A SEPARATE LANDSCAPE PERMIT, ADDRESSING ALL
 LANDSCAPE DEFICIENCIES SHALL BE SUBMITTED, APPROVED AND
 IMPLEMENTED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-31 Cont ID  
Sent By llouie Date 2017-08-31 Time   Rev Time  
Received By llouie Date 2017-08-31 Time   Sent To  
Notes
2017-08-31 15:54:15** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE HEIGHT DIMENSIONS ON SHEET A-3.1.1
 (BUILDING ELEVATIONS).
  
 2.) THE VALUE OF THE CONSTRUCTION ($430,000.00) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($678,392.00) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
  
 NOTES:
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  