Plan Review Details - Permit 17081222
Plan Review Stops For Permit 17081222
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By cthroop Date 2017-10-17 Time 08:44 Rev Time 0.00
Received By cthroop Date 2017-10-17 Time 08:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By aclange Date 2017-09-15 Time 14:03 Rev Time 0.00
Received By aclange Date 2017-09-15 Time 13:36 Sent To  
Notes
2017-09-15 14:07:50****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 1. FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2. NOTE: IF ANY NEW FRAMING OR DRYWALL IS INCLUDED
 PLEASE SHOW THIS ON THE PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-16 Cont ID  
Sent By jpearson Date 2017-10-16 Time 07:08 Rev Time 0.00
Received By jpearson Date 2017-10-16 Time 07:08 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-19 Cont ID  
Sent By jpearson Date 2017-09-19 Time 16:09 Rev Time 0.00
Received By jpearson Date 2017-09-19 Time 16:09 Sent To  
Notes
2017-09-19 16:09:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 2. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE PER CODE.
 NEC 210.11(C)(3) , FBC RE3703.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-17 Cont ID  
Sent By cthroop Date 2017-10-17 Time 08:44 Rev Time 0.00
Received By cthroop Date 2017-10-12 Time 15:00 Sent To  
Notes
2017-10-13 15:00:40RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-27 Cont ID  
Sent By gjohnson Date 2017-09-27 Time 15:06 Rev Time 0.00
Received By gjohnson Date 2017-08-25 Time 15:19 Sent To  
Notes
2017-08-31 15:19:50R35

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By gjohnson Date 2017-10-17 Time 07:58 Rev Time 0.00
Received By gjohnson Date 2017-10-17 Time 07:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-09-27 Cont ID  
Sent By gjohnson Date 2017-09-27 Time 15:06 Rev Time 0.00
Received By gjohnson Date 2017-09-27 Time 15:06 Sent To  
Notes
***NONE***