Plan Review Details - Permit 17081172
Plan Review Stops For Permit 17081172
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-13 Cont ID  
Sent By jwitmer Date 2017-11-13 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2017-10-06 Time 14:05 Sent To  
Notes
2017-11-09 11:11:562010 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17081172 WINDOW/ DOOR SUBMITTAL
 LEVELS 5-24
 W. P. B. PERMIT: 15111020 BUILDING PERMIT
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONSTRUCTION
 TEL: 561-827-3678
 E-MAIL: [email protected]
 : [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. NOV. 09/2017
 ACTION: BUILDING PROVISO/ PARTIAL APPROVAL
  
 THIS SUBMITTAL IS FOR THE EXTERIOR GLAZING FLOORS 5-24.
 WITHIN THE CONTINENTAL GLAZING SYSTEMS CALCULATION AND
 PRODUCT APPROVAL BOOK (3) GLAZING SYSTEMS ARE
 IDENTIFIED, CONTINENTAL 2850 SERIES LIFT & SLIDING
 GLASS DOOR S. M. I (DATE 07/18/2017), 3900 SERIES
 WINDOW WALL SYSTEM (DATE 07/18/2017) & SERIES 3060
 WINDOW WALL SYSTEMS (DATE 11/07/17).
  
 WITHIN THE SUBMITTED BOOKLET THE WINDOW SYSTEMS ARE
 IDENTIFIED STARTING WITH PAGE E01 & 01A (WINDOW WW-51 &
 51A) THROUGH SHEET E38. WITHIN THE SUBMITTED PLANS THE
 E DRAWINGS START WITH E01 & 01A BUT STOP WITH E31A. THE
 PROJECT MANAGER FOR CONTINENTAL GLASS SYSTEMS CARLOS
 VARGAS TOLD US THAT E32-E38 ARE NOT INCLUDED IN THIS
 SUBMITTAL BUT WILL BE SUBMITTED UNDER SEPARATE COVER
 AND REVIEW FOR THE UPPER 25TH FLOOR.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2017-10-07 07:31:072014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17081172/ CONTINENTAL GLAZING
 SYSTEMS
 W. P. B. PERMIT: 15101020
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONST.
 TEL: 561-827-3678
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: FRI-SAT. OCT. 5-6TH./ 2017
 ACTION: IN REVIEW/ SITE SPECIFIC PRODUCT APPROVAL TO BE
 REVIEWED BY THE BUILDING OFFICIAL ROBERT BROWN.
  
 1) MULLIONS. IN THE FLORIDA PRODUCT APPROVAL REPORT FL.
 18312.2 SERIES 3900 WINDOW WALL S. M. I. IN THE
 TECHNICAL SHEETS, SHEET 5 OF 11 INDICATES THE TYPE OF
 MULLIONS TESTED IN THIS REPORT. MULLION TYPES TESTED
 WERE M1, M1A, M2, M2A & J1 W/O REINFORCEMENT.
  
 IN REVIEWING MCY ENGINEERING SHEETS FOR SERIES 3900
 WINDOW WALL SYSTEM ON PAGE 27 THE REPORT LIST THE
 VARIOUS MULLION TYPES FOR THIS SERIES:
 M1, TYPICAL MULLION +/-126.0 PSF
 J1, FX-SGD MULLION +/-104.9 PSF
 J3, FX-SGD MULLION +/-104.9PSF
 M2, TYPICAL MULLION (W/ STL REINFORCEMENT) +/-141.0 PSF
 M4, FX-SGD MULLION (W/ STL REINFORCEMENT) +/-138.8 PSF
 J1, FX-SGD MULLION (W/ STL REINFORCEMENT) +/-140.0 PSF
  
 ON PAGES 5 & 6 THERE ARE TABLES 2 & 3 SINGLE SPAN
 MULLION LOAD CAPACITY- PSF. THE CONCERNS ARE IN THE J1
 COLUMN PORTION OF THE TABLES 2 & 3 THE J1 COLUMN. TO
 THE RIGHT OF THE SPAN TABLES ARE THE VARIOUS MULLION
 CONFIGURATIONS BOTH UNREINFORCED AND REINFORCED. THE
 VALUES OF PSF IN THE J1 COLUMN OF 141.0 WOULD SUGGEST
 THAT THE J1 MULLION SHOULD BE THE BOTTOM J1 LISTED
 ABOVE WITH STEEL REINFORCEMENT. THE TABLE 2 NOR 3
 PROVIDE A DETAIL OF A J1 MULLION W/ STL REINFORCEMENT.
  
 IS THIS OF CONCERN SINCE IN REVIEWING ALL OF THE WIDOW
 CONFIGURATIONS IN THE 3900 SERIES CHARTS THERE IS NO J1
 MULLIONS @ +/-104.9 NOR +/- 140.0? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED TO DETERMINE CODE COMPLIANCE
 WITH PRESSURES FOR COMPONENTS AND CLADDING. 2010 FBC-B
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By jwitmer Date 2017-09-15 Time   Rev Time 0.00
Received By jwitmer Date 2017-09-13 Time 11:14 Sent To  
Notes
2017-09-15 16:34:03BUILDING PLAN REVIEW
 W. P. B. REVISION: 17081172
 W. P. B.PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONSTRUCTION CO. TEL: 561-827-3678
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 1ST REVIEW
 DATE: THURS. SEPT.14/ 2017
 ACTION: DENIED
  
 1) CONTINENTAL GLASS SYSTEMS GLAZING CALCULATION I MCY
 ENGINEERING, INC. YIPING WANG HAS SIGNED BUT NOT DATED
 THE TITLE PAGE. PAGE 2 OF THIS REPORT, TABLE OF
 CONTENTS LIST THERE ARE 167 PAGES WITHIN THE REPORT.
 PLEASE NOTE THE TABLE OF CONTENTS IS NOT SIGNED AND
 SEALED NOR DATED.
 61G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH
 LISTED PAGES OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET.
  
 2) IN THE CONTINENTAL GLASS SYSTEMS GLAZING CALCULATION
 I MCY ENGINEERING, INC. REPORT THERE ARE (3) FLORIDA
 PRODUCT APPROVAL REPORT: FL # 17175 2850 SERIES SLIDE
 GLASS DOORS
 FLORIDA PRODUCT APPROVAL REPORT: FL # 18312.2 3900
 WINDOW WALL SYSTEM FLORIDA PRODUCT APPROVAL REPORT: FL
 # 22012 3060 WINDOW WALL SYSTEM
  
 2A) IN BOTH OF THE FLORIDA APPROVALS FL # 17175 & FL #
 18312.2 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2010 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER'S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 2B) THE FLORIDA PRODUCT APPROVAL REPORT: FL # 22012
 3060 WINDOW WALL SYSTEM IS NOT A LISTED SYSTEM UNDER
 CONTINENTAL GLASS SYSTEMS GLAZING. THERE IS A FLORIDA
 APPROVAL FL 22011 FOR CURTAIN WALLS THAT IS APPLIED
 FOR. WE NEED MORE INFORMATION ABOUT THIS SYSTEM, WAS
 THE APPROVAL # 22012 DENIED?
 PLEASE PROVIDE A RATIONAL ANALYSIS FOR THE SUBMITTED
 PAPERWORK. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY, COLLATE AND STAPLE INTO
 SETS OF PLANS. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION I DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-11-13 Time   Rev Time 0.00
Received By jwitmer Date 2017-10-06 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-15 Cont ID  
Sent By lmarchan Date 2017-09-15 Time 16:34 Rev Time 0.00
Received By lmarchan Date 2017-08-24 Time 15:03 Sent To  
Notes
2017-08-25 15:03:12SUBMITTAL ROUTED TO JWITMER