Plan Review Details - Permit 17081077
Plan Review Stops For Permit 17081077
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-04 Cont ID  
Sent By rmcdouga Date 2018-01-04 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2018-01-03 Time 17:16 Sent To  
Notes
2018-01-04 13:21:34APPROVED WITH EXCEPTIONS (PROVISO)
  
 1) SUBMIT TWO SETS OF ENHANCED FASTENING CALCULATIONS
 FOR THE BALCONY WATERPROOFING. SEE LIMITATION #7 ON
 PAGE 2 OF 3 IN THE FLORIDA PRODUCT APPROVAL.
 FBC-R301.2.1
  
 2) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS FOR
 THE FABRIC COVERING THAT WILL BE INSTALLED ON THE
 PERGOLA. FBC 107.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-03 Cont ID  
Sent By rmcdouga Date 2017-10-03 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2017-10-03 Time 11:28 Sent To  
Notes
2017-10-03 11:42:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) I COULD NOT FIND ANY DOCUMENTS ON FILE THAT SHOW THE
 CONVERSION OF THE STORAGE AREA IN THE GARAGE INTO A
 GUEST ROOM AND BATHROOM. UNLESS YOU CAN PROVIDE THE
 DOCUMENTATION, THIS WILL BE REVIEWED AS A CHANGE OF USE
 WITHIN AN R-3 OCCUPANCY TYPE. AN IMPACT FEE REVIEW WILL
 BE REQUIRED. PROVIDE AN AREA TABULATION THAT SEPARATES
 THE NEW ADDITION TO THE MAIN HOUSE AND THE SQUARE
 FOOTAGE OF THE GUEST ROOM AND BATH FROM THE REST OF THE
 EXISTING LIVING SPACE ON THE PLANS. FBC 107.2.1
  
 2) SHOW HOW BED ROOM #2 ON SHEET A1.04 WILL COMPLY WITH
 FBC-R R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND
 RESCUE OPENING. FBC-R310.1.1 MINIMUM OPENING AREA. ALL
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE A
 MINIMUM NET CLEAR OPENING OF 5.7 SQUARE FEET
  
  
 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 4) FBC-R315.1 CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 5) ON SHEET S100 THERE IS AN ID TAG FOR SC1. THERE IS
 NOT AN SC1 LISTED IN THE LEGEND ON SHEET S100. PLEASE
 CLARIFY. FBC 107.2.1
  
 6) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE 7' WIDE SECTIONAL
 GARAGE DOORS, THE ROOFING (WATERPROOFING) MATERIAL THAT
 WILL BE USED ON THE BALCONY AND FOR LARGE MISSILE
 IMPACT RATED SINGLE HUNG AND FIXED WINDOWS (THE ONES
 SUBMITTED ARE FOR SMALL MISSILE).
  
 7) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CONCRETE ROOF TILE TO RESIST THE
 OVERTURN MOMENT. IF AN ADHESIVE WILL BE USED, SUBMIT
 THE PRODUCT APPROVALS FOR IT. FBC 107.3.4
  
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 FABRIC COVERING THAT WILL BE INSTALLED ON THE PERGOLA.
 FBC 107.2.1
  
 9) THE DOOR FROM THE GARAGE TO THE RESIDENCE SHALL
 COMPLY WITH FBC-R302.5.1 OPENING PROTECTION. OPENINGS
 FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR
 SLEEPING PURPOSES SHALL NOT BE PERMITTED. OTHER
 OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE
 EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 13/8
 INCHES (35 MM) IN THICKNESS, SOLID OR HONEY-COMB-CORE
 STEEL DOORS NOT LESS THAN 13/8 INCHES (35 MM) THICK, OR
 20-MINUTE FIRE-RATED DOORS, EQUIPPED WITH A
 SELF-CLOSING DEVICE.
  
 10) THE WALL BETWEEN THE GARAGE AND THE CONDITIONED
 SPACED IS REQUIRED TO BE THERMALLY INSULATED. FBC
 ENERGY CONSERVATION R402
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcdouga Date 2017-09-27 Time 07:40 Sent To  
Notes
2017-10-03 09:41:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-29 Cont ID  
Sent By jpearson Date 2017-12-29 Time 14:52 Rev Time 0.00
Received By jpearson Date 2017-12-29 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-18 Cont ID  
Sent By jpearson Date 2017-09-18 Time 16:14 Rev Time 0.00
Received By jpearson Date 2017-09-18 Time 16:14 Sent To  
Notes
2017-09-18 16:14:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION INCLUDES 1 WATT PER SQUARE FOOT FOR
 UNCONDITIONED SPACE. PROVIDE CODE SECTION THAT PERMITS
 THIS. FBC 107.2.1
 2. LOAD CALCULATION SHOWS 4850 WATTS FOR WATER HEATER
 WITH CIRCULATING PUMP. PLAN SHOWS 2 TANKLESS WATER
 HEATERS, 1 EXISTING AND 1 ADDED. WHAT IS THE CORRECT
 AMOUNT OF LOAD FOR WATER HEATERS? ARE THERE TANKLESS
 AND STANDARD WATER HEATERS? PROVIDE CLARIFICATION
 AND/OR CORRECTION. FBC 107.2.1, NEC 220
 3. LOAD CALCULATION SHOWS 2 SMALL APPLIANCE CIRCUITS.
 THE PANEL SCHEDULE SHOWS THAT THERE ARE 3. PER NEC
 220.83, EACH SMALL APPLIANCE CIRCUIT IS REQUIRED TO BE
 INCLUDED IN CALCULATION. NEC 220.83; FBC RE 3602.3
 4. LOAD CALCULATION DOES NOT INCLUDE WINE COOLER. ALL
 NAMEPLATE RATINGS OF EQUIPMENT MUST BE INCLUDED IN
 CALCULATION. PROVIDE CORRECTION. NEC 220.83; FBC RE
 3602.3
 5. LOAD CALCULATION SHOWS "ALLOWANCE" FOR SEVERAL
 ITEMS. AN ALLOWANCE IS NOT ACCEPTABLE FOR THIS TYPE OF
 LOAD CALCULATION. ALL NAMEPLATE RATINGS OF EQUIPMENT
 MUST BE INCLUDED IN CALCULATION. PROVIDE CORRECTION.
 NEC 220.83; FBC RE 3602.3
 6. LOAD CALCULATION SHOWS 15.75 KW FOR A/C LOAD. PER
 THE SPECS ON MECHANICAL PLAN, THE 3 CONDENSING UNITS
 WOULD EQUAL 16.8 KW. PROVIDE DETAIL OF A/C VS HEAT LOAD
 IN CALCULATION, USING THE LARGEST OF THE LOADS. PROVIDE
 CORRECTION. FYI, IT APPEARS THAT WHEN ALL OF THE
 COMMENTS RELATING TO LOAD CALCULATION ARE CORRECTED,
 THE EXISTING SERVICE OF 200 AMPS WILL BE TOO SMALL.
 PROVIDE CORRECTION IF NECESSARY. NEC 220.83, 230.42;
 FBC RE 3602.3
 7. PROVIDE MORE DETAIL IN PANEL SCHEDULES. PROVIDE
 CIRCUIT IDENTIFICATION ("EXISTING CIRCUIT" NOT
 ACCEPTABLE), PROVIDE WIRE SIZE OF CIRCUIT, AND PROVIDE
 THE LOAD FOR EACH CIRCUIT. IF LOAD IS INCLUDED IN
 GENERAL LIGHTING PORTION, SO NOTE. INDICATE AFCI OR
 GFCI PROTECTION WHERE REQUIRED TO COMPLY WITH CODE.
 ALSO SHOW WHAT THE ACTUAL LOAD ON EACH PANEL IS, THE
 GARAGE PANEL AND MAIN PANEL DO NOT LIST THE AMOUNT OF
 LOAD ON PANEL. THE GARAGE PANEL IS FED FROM A 50 AMP
 CIRCUIT, IS THIS ADEQUATE FOR THE LOAD ON PANE? NEC
 210.8, 210.12, 215.2, 215.5, 408.4, 408.30; FBC
 RE3706.2, RE3902; FBC 107.2.1
 8. MASTER CLOSET SHOWS STANDARD 4 INCH RECESS LIGHTS.
 PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION.
 NEC 410.16; FBC RE4003.12
 9. MASTER BATH SHOWS A RECEPTACLE ADJACENT TO THE
 TOILET THAT DOES NOT HAVE GFCI PROTECTION. ALL
 RECEPTACLES IN THE BATHROOM REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.1
 10. PROVIDE RECEPTACLE AND LIGHT CONTROLLED BY A SWITCH
 AT EACH AHU IN ATTIC SPACE. FBC RE M1305.1.3.1
 11. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1
 12. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
 13. LIGHTING ADJACENT TO POOL NOT CODE COMPLIANT.
 PROVIDE CORRECTION. NEC 680.22(B); FBC RE 4203.4
 14. RECEPTACLES FOR GDO REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE3902.2
 15. GUEST ROOM CLOSET LIGHT IS SHOWN AS A 4 INCH RECESS
 LIGHT. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE
 CORRECTION. NEC 410.16; FBC RE4003.12
 16. ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION. PROVIDE CORRECTION. A NOTE WILL SUFFICE.
 NEC 210.12; FBC RE3902.12
 17. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 18. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-12-19 Cont ID  
Sent By FM Date 2017-12-19 Time 10:42 Rev Time 0.00
Received By fmittner Date 2017-12-15 Time 15:01 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-09-07 Cont ID  
Sent By fmittner Date 2017-09-07 Time 11:34 Rev Time 0.00
Received By fmittner Date 2017-09-07 Time 11:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-08 Cont ID  
Sent By rmcdouga Date 2018-02-08 Time 18:59 Rev Time 0.00
Received By rmcdouga Date 2018-02-07 Time 14:36 Sent To  
Notes
2018-02-08 14:36:16IMPACT FEES ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-04 Cont ID  
Sent By rmcdouga Date 2018-01-04 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2017-12-08 Time 16:22 Sent To I
Notes
2017-12-11 16:22:11R28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-04 Cont ID  
Sent By rmcdouga Date 2017-10-04 Time 16:00 Rev Time 0.00
Received By rmcdouga Date 2017-08-23 Time 14:03 Sent To  
Notes
2017-08-24 14:03:52R30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-02-08 Cont ID  
Sent By rmcdouga Date 2018-02-08 Time 18:59 Rev Time 0.00
Received By rmcdouga Date 2018-02-08 Time 18:53 Sent To I
Notes
2018-02-08 19:00:49MU 2018-3439 PAID $22.46

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-09-27 Cont ID  
Sent By rmcdouga Date 2017-09-27 Time 17:47 Rev Time 0.00
Received By rmcdouga Date 2017-09-27 Time 17:47 Sent To  
Notes
2017-09-27 17:48:02BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-01-03 Cont ID  
Sent By rmcdouga Date 2018-01-03 Time 18:39 Rev Time 0.00
Received By rmcdouga Date 2018-01-03 Time 17:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-04 Cont ID  
Sent By rmcdouga Date 2017-10-04 Time 16:00 Rev Time 0.00
Received By rmcdouga Date 2017-10-04 Time 16:00 Sent To  
Notes
2017-10-04 15:58:16PLAN
 REVIEW COMMENTS
 (CONTRIBUTING HISTORIC STRUCTURES)
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 2) THE MECHANICAL PLANS ARE ARE NOT ACCEPTABLE. THE
 DUCTWORK AND EQUIPMENT CAN NOT BE SEEN CLEARLY DUE TO
 THE LAYERS WITH THE FURNITURE AND FIXTURES THAT ARE ON
 THE DRAWINGS. PLEASE SUBMIT MECHANICAL PLANS THAT
 CLEARLY SHOW THE MECHANICAL EQUIPMENT AND DUCT WORK. IN
 ADDITION TO THE REQUIRED MECHANICAL ITEMS, ONLY THE
 WALLS AND ROOM LABELS SHOULD BE SHOWN ON THE DRAWINGS.
 FBC 107.2.1
  
 3) THE SIZES OF ALL OF THE DUCTS ARE REQUIRED TO BE
 SHOWN ON THE DRAWINGS. FBC 107.3.5.1.4

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-12-29 Cont ID  
Sent By tklarge Date 2017-12-29 Time 12:02 Rev Time 0.00
Received By tklarge Date 2017-12-29 Time 11:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-03 Cont ID  
Sent By rmcdouga Date 2017-10-03 Time 17:57 Rev Time 0.00
Received By rmcdouga Date 2017-10-03 Time 17:57 Sent To  
Notes
2017-10-03 18:01:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY PLUMBING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A PLUMBING RISER DIAGRAM FOR THE GUEST ROOM
 BATH. FBC 107.3.5.3
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-03-27 Cont ID  
Sent By rmcdouga Date 2019-03-27 Time 11:41 Rev Time 0.00
Received By rmcdouga Date 2019-03-27 Time 11:41 Sent To  
Notes
2019-03-27 11:44:29ROOFING
 POLYGLASS UNDERLAYMENT NOA NO 15-0410.04
 TILE BOND ROOF TILE ADHESIVE NOA NO 16-0222.01
 ENTEGRA ROOF TILE NOA NO 14-0416.12

Review Stop Z ZONING
Rev No 2 Status P Date 2017-12-19 Cont ID  
Sent By fmittner Date 2017-12-19 Time 10:50 Rev Time 0.00
Received By fmittner Date 2017-12-19 Time 10:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-09-07 Cont ID  
Sent By fmittner Date 2017-09-07 Time 11:34 Rev Time 0.00
Received By fmittner Date 2017-09-07 Time 11:34 Sent To  
Notes
***NONE***