Plan Review Details - Permit 17081061
Plan Review Stops For Permit 17081061
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-09-15 Cont ID  
Sent By aclange Date 2017-09-15 Time 12:55 Rev Time 0.00
Received By aclange Date 2017-09-15 Time 11:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-03 Cont ID  
Sent By jleahy Date 2017-11-03 Time 11:56 Rev Time 0.00
Received By jleahy Date 2017-11-03 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-18 Cont ID  
Sent By jpearson Date 2017-09-18 Time 09:50 Rev Time 0.00
Received By jpearson Date 2017-09-18 Time 09:50 Sent To  
Notes
2017-09-18 09:50:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MORE DETAIL REQUIRED FOR RELOCATION OF STEAM
 GENERATOR. IS THIS UNIT RATED TO BE INSTALLED IN A DAMP
 LOCATION? HOW IS THE POWER SUPPLIED TO THE UNIT, WITH
 CORD AND PLUG OR DIRECT CONNECTED (NO RECEPTACLE
 PERMITTED IN SHOWER)? IS THE BENCH THIS IS LOCATED
 UNDER COMPLETELY ENCLOSED SO THE STEAM UNIT WOULD NOT
 ACTUALLY BE IN THE SHOWER? WHERE IS THE REQUIRED
 DISCONNECT FOR THIS UNIT? PROVIDE RESPONSES AND SPEC
 SHEET FOR UNIT. NEC 110.3, 406.9(C), 424.12(B), 424.19
 2. PROVIDE FLOOR PLAN SHOWING SMOKE/CO ALARMS IN EACH
 LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-11-03 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-17 Time 14:52 Sent To  
Notes
2017-10-18 14:52:07R27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-10-17 Time 14:04 Rev Time 0.00
Received By lcrespo Date 2017-09-18 Time 14:04 Sent To  
Notes
2017-08-23 15:55:36R27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-11-03 Cont ID  
Sent By ccole Date 2017-11-03 Time 12:33 Rev Time 0.00
Received By ccole Date 2017-11-03 Time 12:33 Sent To  
Notes
2017-11-03 12:34:23SEPARATE PERMIT REQUIRED FPOR MECHANICAL ALTERATIONS.
 CCOLE- 11/3/17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-17 Cont ID  
Sent By ccole Date 2017-10-17 Time 14:20 Rev Time 0.00
Received By ccole Date 2017-10-17 Time 14:19 Sent To  
Notes
2017-10-17 14:23:431ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17081061
 10/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL WITH
 CORRESPONDING DETAILS ON THE PLAN. CLARIFY IF ANY
 ALTERATIONS TO THE EXISTING HVAC SYSTEMS ARE PROPOSED
 FOR THE NEW BATHROOM SUCH AS NEW EXHAUST FAN AND VENT,
 NEW AC DUCTS, DIFFUSER, OR GRILLS ETC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-26 Cont ID  
Sent By lcrespo Date 2017-10-26 Time 16:54 Rev Time 0.00
Received By lcrespo Date 2017-10-26 Time 16:54 Sent To  
Notes
2017-10-26 16:56:0510/26/17 APPROVED BY PLUMBING, PUT BACK IN "27", LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-18 Cont ID  
Sent By lcrespo Date 2017-09-18 Time 14:04 Rev Time 0.00
Received By lcrespo Date 2017-09-18 Time 14:04 Sent To  
Notes
2017-09-18 14:07:44FAUCET IN MASTER VALVE SHALL HAVE A TEMPERED MIXING
 VALVE. IF INTEGRAL PROVIDE SPECIFICATION OR LOCATION
 WHERE IT WILL BE PLACED FBC P2724.1
  
 SHOWER SHOWS A WEDI SYSTEM PLEASE PROVIDE MANUFACTURE
 SPECIFICATIONS. PLEASE PROVIDE WHAT STANDARD OF TESTING
 METHODS WAS USED FOR PRODUCT APPROVAL. FBC P2609.4
  
 SHOWER SHOWS A STEAM GENERATOR PLEASE PROVIDE
 MANUFACTURE SPECIFICATION. THE STEAM UNIT IS UNDER A
 THE SHOWER SEAT. HOW IS THE STEAM ENTERING THE SHOWER?
 PLEASE CLARIFY WHAT TYPE OF PROTECTION IS BEING USED
 AND SHOW WHERE IT GOING IN THE SHOWER. FBC AMENDMENTS
 107.2.1
  
 HAND HELD SHOWER MUST HAVE INTEGRAL VACUUM BREAKER FBC
 P2902.4.2
  
 LAVS SHOW WALL MOUNTED FAUCET TO FIXTURE AND REQUIRE
 VALVES SERVING IT. PLEASE SHOW AND CLARIFY IF BEING
 INSTALLED UNDER SINK. FBC P2903.9.3
  
 LAY OUT ON PLAN NOT TO CODE, PLEASE PROVIDE AN
 ISOMETRIC DIAGRAM. SHOWER EXCEEDS LENGTH ON TRAP AND
 VENTING. DRAIN, WASTE AND VENT PIPE SIZING AND RISER
 DIAGRAM FBC P3004, P3005
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 561-805-6720
 [email protected]
  