Plan Review Details - Permit 17081026
Plan Review Stops For Permit 17081026
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-24 Cont ID  
Sent By ccole Date 2017-08-24 Time 16:30 Rev Time 0.00
Received By ccole Date 2017-08-24 Time 16:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By ccole Date 2017-08-22 Time 14:36 Rev Time 0.00
Received By ccole Date 2017-08-22 Time 14:36 Sent To  
Notes
2017-08-22 14:46:011ST REVIEW FBC-2014 BUILDING
 PERMIT #17081026
 8/22/17
  
 1) PROVIDE A SECOND SET OF NOA'S FOR THE PROPOSED
 ROOFING PROJECT- SECTION 107.1 WPB AMENDMENTS TO THE
 FBC. ONLY ONE SET WAS SUBMITTED.
  
 2) REFER TO LIMITATION #7 ON PAGE 31 OF NOA #14-1030.01
 INCREASED FASTENER DENSITIES AT PERIMETER AND CORNER
 AREAS REQUIRED. PROVIDE CALCULATIONS PREPARED AND
 SIGNED AND SEALED BY A FL. REGISTERED PROFESSIONAL
 ENGINEER, ARCHITECT, OR REGISTERED ROOF CONSULTANT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-24 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-23 Time 14:17 Sent To  
Notes
2017-08-24 14:17:15RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-22 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-22 Time 13:42 Sent To  
Notes
2017-08-22 13:42:13CCOLE