Plan Review Details - Permit 17081018
Plan Review Stops For Permit 17081018
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-03 Cont ID  
Sent By jwitmer Date 2017-10-03 Time 12:33 Rev Time 0.00
Received By jwitmer Date 2017-10-03 Time 11:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-24 Cont ID  
Sent By jwitmer Date 2017-08-24 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2017-08-02 Time 06:29 Sent To  
Notes
2017-08-24 06:59:492014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17081018
 ADD: 500 S AUSTRALIAN AVE. SUITE:200
 CONT: KARL CORP. CONSTRUCTION SERVICES
 TEL: 561-718-5569
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 24/ 2017
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES THIS NEW TENANT SPACE IS
 BEING SEPARATED OUT OF A LARGER TENANT SPACE. PLEASE
 PROVIDE THE REMAINING SQUARE FEET OF THE ORIGINAL
 TENANT SPACE. 2014 EXISTING BUILDING CODE LEVEL II
 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 CREATION OR EXTENSION OF NONCONFORMITY. ALL NEW WORK,
 RE-CONFIGURATION SHALL NOT CREATE OR EXTEND ANY
 NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 RE-CONFIGURATION OF SPACE IS BEING MADE WITH REGARD TO
 ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE SAFETY, MEANS
 OF EGRESS, OR THE CAPACITY OF MECHANICAL, PLUMBING, OR
 ELECTRICAL SYSTEMS.
 2) THE COVERSHEET INDICATES THE OCCUPANCY AS BUSINESS
 WITH 3115 SQ. FT. AND AN OCCUPANT LOAD OF ONLY 31.
 PLEASE NOTE WHEN IN REGARDS TO OCCUPANTS WHEN THERE IS
 A REMAINDER YOU ALWAYS ROUND UP OR 32 OCCUPANTS. 2014
 FBC-B TABLE 1004.1.2 & THE BUILDING OFFICIALS
 ASSOCIATION OF FLORIDA, INFORMAL INTERPRETATION REPORT
 # 5479 IN CONJUNCTION WITH FL. DEPT. OF COMMUNITY
 AFFAIRS.
  
 3) SHEET A-2.1 VERSES THE COVERSHEET/ LIFE SAFETY. THE
 COVERSHEET SHOWS THE NEW TENANT SEPARATION WALL AS A
 1-HOUR FIRE RATED WALL WHEREAS SHEET A-2.1 INDICATES
 WALL TYPE # 4 A NON-RATED PARTITION TO THE UNDERSIDE OF
 THE PARTITION. SHEET A-3.1 DETAIL 04 ALSO SHOWS THIS
 TYPE WALL AS NON-BEARING, NON-RATED. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED DISCREPANCY IN PLANS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-05 Cont ID  
Sent By jpearson Date 2017-10-05 Time 07:18 Rev Time 0.00
Received By jpearson Date 2017-10-05 Time 07:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-31 Cont ID  
Sent By jpearson Date 2017-08-31 Time 12:56 Rev Time 0.00
Received By jpearson Date 2017-08-31 Time 12:56 Sent To  
Notes
2017-08-31 12:56:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1
 2. PROVIDE A BLOCK NOTE WHERE APPLICABLE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR LOW VOLTAGE SYSTEMS, FIRE ALARM, CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, WALK-IN COOLERS,
 HOODS, ETC. FBC 105.1
 3. PROVIDE LOAD CALCULATION FOR EXISTING BUSS TO
 CONFIRM ADEQUATE SIZE FOR ADDITIONAL LOAD. NEC 220; FBC
 107.2.1
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS
 ADEQUATE. NEC 110.10
 6. PANEL SCHEDULE FOR PANEL H SHOWS CIRCUIT 13, 15, 17
 ON A 60 AMP BREAKER WITH # 6 WIRE TO TRANSFORMER. RISER
 DIAGRAM SHOWS # 8 WIRE TO TRANSFORMER. PROVIDE
 CORRECTION. NEC 215.2, 215.5, 310.15(B)(16); FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-05 Cont ID  
Sent By wjolin Date 2017-10-05 Time 09:32 Rev Time 0.00
Received By wjolin Date 2017-10-05 Time 09:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-25 Cont ID  
Sent By wjolin Date 2017-08-25 Time 12:49 Rev Time 0.00
Received By wjolin Date 2017-08-25 Time 12:39 Sent To  
Notes
2017-08-25 12:46:48SEPARATE PERMITS ARE NEEDED FOR THE FIRE SPRINKLER AND
 FIRE ALARM MODIFICATIONS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-11 Cont ID  
Sent By gjohnson Date 2017-10-11 Time 11:56 Rev Time 0.00
Received By gjohnson Date 2017-10-02 Time 14:21 Sent To  
Notes
2017-10-02 14:34:03B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-09-06 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-22 Time 15:37 Sent To  
Notes
2017-08-22 15:37:12B03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-08-24 Cont ID  
Sent By jwitmer Date 2017-08-24 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2017-08-24 Time 06:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-03 Cont ID  
Sent By ccole Date 2017-10-03 Time 15:08 Rev Time 0.00
Received By ccole Date 2017-10-03 Time 10:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-06 Cont ID  
Sent By ccole Date 2017-09-06 Time 17:01 Rev Time 0.00
Received By ccole Date 2017-09-06 Time 16:51 Sent To  
Notes
2017-09-06 17:15:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17081018
 9/6/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 HEAT PUMP SYSTEM- SECTION 312.1.
  
 2) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR
 THE O/A INTAKE DUCTS- SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 3) SHOW THE LOCATION OF THE NEW HEAT PUMP CONDENSER AND
 PROVIDE ENGINEERED INSTALLATION DETAILS- SECTION
 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2017-10-11 Cont ID  
Sent By gjohnson Date 2017-10-11 Time 11:56 Rev Time 0.00
Received By gjohnson Date 2017-10-11 Time 11:47 Sent To  
Notes
2017-10-11 11:56:14NO PLUMBING SHOWN ON PLAN
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-10-04 Cont ID  
Sent By gjohnson Date 2017-10-04 Time 17:54 Rev Time 0.00
Received By gjohnson Date 2017-10-04 Time 14:38 Sent To  
Notes
2017-10-04 17:55:54NO PLUMBING SHOWN ON PLAN
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  