Plan Review Details - Permit 17081015
Plan Review Stops For Permit 17081015
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-23 Cont ID  
Sent By aclange Date 2017-10-23 Time 13:57 Rev Time 0.00
Received By aclange Date 2017-10-23 Time 13:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 17:55 Rev Time 0.00
Received By shill Date 2017-08-29 Time 17:55 Sent To  
Notes
2017-08-29 18:03:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. CALCULATIONS AND PLANS ARE FOR THE SIX STORY
 BUILDING. THE ADDRESS ON THE APPLICATION, 2221, DOES
 NOT CORRELATE WITH ANY OF THE BUILDING PERMIT
 APPLICATIONS (2201, 2171, 2191 N AUSTRALIAN AVE). THE
 SITE PLAN SHOWS A SIX STORY PROPOSED BUILDING AS 2221 N
 AUSTRALIAN AVE. ON THE SITE PLAN, WHERE IS 2191 N
 AUSTRALIAN AVE? IS ANOTHER SIX STORY PROPOSED? FBC 107,
 SCOPE NOT CLEAR.
  
 SITE PLAN SHOWS "EXISTING" SIX STORY BUILDINGS WHICH DO
 NOT APPEAR ON AERIALS, AND NO EVIDENCE OF PERMITS FOR
 RECENT CONSTRUCTION OF SIX STORY BUILDINGS ON THIS
 PARCEL. REVISE SITE PLAN (ON ALL AFFECTED PERMITS) OR
 CLARIFY.
  
 2. A COMPLETE SET OF PLANS WAS SUBMITTED. REMOVE
 UNNECESSARY SHEETS, FBC 107. SEE REVIEW UNDER 17081012
 FOR DOCUMENTS TYPICALLY REQUIRED FOR FOUNDATION PERMIT.
  
 3. CALCULATIONS INCLUDE OUTDATED CODE REFERENCES,
 REVISE, FBC CH 35 (ASCE7-05, IBC 2009, ACI 2008, ETC.).
  
 4. IF THIS IS A PROPOSED SIX STORY, THIS IS A THRESHOLD
 BUILDING AND THE COMMENTS FOR 17081012 ARE APPLICABLE.
  
 SCOPE NOT CLEAR; COMPLETE REVIEW CANNOT BE DONE AT THIS
 TIME.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-02 Cont ID  
Sent By jpearson Date 2017-11-02 Time 14:13 Rev Time 0.00
Received By jpearson Date 2017-10-26 Time 14:13 Sent To  
Notes
2017-11-02 15:12:09FIRE REVIEW PASSED WITHOUTH FIRE PUMP, CHANGES
 ELECTRICAL STATUS TO PASS. 11-2-17
2017-10-26 14:12:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 PREVIOUS COMMENTS CORRECTED HAVE BEEN REMOVED AND NOTED
 AS CORRECTED. REMAINING PREVIOUS COMMENTS HAVE THE
 ORIGINAL COMMENT THAT STILL NEEDS CORRECTION WITH
 FURTHER COMMENT IN (PARENTHESES).
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23.
 IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF
 SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP
 SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM
 WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5,
 695.4(B)(3); FBC 107.2.1 (JOCKEY PUMP AND ENTIRE FIRE
 PUMP SYSTEM HAS BEEN REMOVED FROM PLANS. THIS WILL NEED
 TO BE ON PLAN FOR THE FOUNDATION PERMIT BECAUSE THE
 WIRING TO THE FIRE PUMP NEEDS TO MEET THE CODE
 REQUIREMENTS OF NEC 695.6).
 5. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS
 FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E)
 (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS.
 THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT
 BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE
 CODE REQUIREMENTS OF NEC 695.6).
 6. CORRECTED.
 7. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR
 FIRE PUMP. NEC 695.3(B) (ENTIRE FIRE PUMP SYSTEM HAS
 BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN
 FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE
 FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC
 695.6 AND 695.14. SHOW LOCATION ON PLAN OF FIRE PUMP
 ROOM AND THE ELECTRICAL FEED TO THAT ROOM FROM PRIMARY
 AND SECONDARY SOURCE.)
 8. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER
 AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING,
 AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6
 (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS.
 THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT
 BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE
 CODE REQUIREMENTS OF NEC 695.6).
 9. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE
 FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE
 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS
 SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE
 430.251(B); FBC 107.2.1 (ENTIRE FIRE PUMP SYSTEM HAS
 BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN
 FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE
 FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC
 695.6).
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-05 Cont ID  
Sent By jpearson Date 2017-09-05 Time 16:04 Rev Time 0.00
Received By jpearson Date 2017-09-05 Time 16:04 Sent To  
Notes
2017-09-05 15:53:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SEE BUILDING PLAN REVIEW COMMENTS IN REFERENCE TO
 ADDRESS ON PLANS. PROVIDE CORRECTION AS NEEDED ON
 PLANS. FBC 107.2.1
 2. SHEET E-8 SHOWS 7 SETS OF 750 KCMIL CU FOR SERVICE
 FEEDERS, WHILE SHEET E-6 SHOWS 7 SETS OF 600 KCMIL CU.
 CORRECT DISCREPANCY. FBC 107.2.1
 3. LOAD CALCULATION FOR MDP SHOWS SEVERAL DIFFERENT
 CALCULATIONS (ONE STORY, TWO STORY, ETC.). PROVIDE LOAD
 CALCULATION RELATED TO THIS PERMIT ONLY FOR THE SIX
 STORY BUILDING. REMOVE ALL OTHER UNRELATED INFORMATION.
 ADDITIONALLY, THE LOAD VA SHOWN FOR THE 1 BEDROOM UNIT
 IS THE SAME AS FOR THE 2 BEDROOM UNIT. LOAD CALCULATION
 FOR PANEL H IS DIFFERENT THAN LISTED IN PANEL SCHEDULE.
 PROVIDE CORRECTIONS. NEC 220, 220.84, 215.2, 408.30;
 FBC 107.2.1
 4. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23.
 IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF
 SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP
 SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM
 WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5,
 695.4(B)(3); FBC 107.2.1
 5. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS
 FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E)
 6. PANEL H LOAD CALCULATION STATES THAT THE FIRST 10K
 VA ARE AT 100%. HOWEVER, THE LOAD SHOWN IS 4320 VA, NOT
 10,000. PANEL H1 LOAD CALCULATION IS SIMILARLY WRONG.
 PROVIDE CORRECTION. NEC 220.44
 7. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR
 FIRE PUMP. NEC 695.3(B)
 8. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER
 AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING,
 AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6
 9. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE
 FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE
 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS
 SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE
 430.251(B); FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-10-25 Cont ID  
Sent By squinone Date 2017-10-25 Time   Rev Time 0.00
Received By squinone Date 2017-10-25 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-02 Cont ID  
Sent By wjolin Date 2017-11-02 Time 09:06 Rev Time 0.00
Received By wjolin Date 2017-11-02 Time 09:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-25 Cont ID  
Sent By wjolin Date 2017-08-25 Time 13:07 Rev Time 0.00
Received By wjolin Date 2017-08-25 Time 13:07 Sent To  
Notes
2017-08-25 13:07:29FOUNDATION ONLY
  
 PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER
 MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE
 INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO VERTICAL
 CONSTRUCTION WORK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-03 Cont ID  
Sent By tklarge Date 2017-11-03 Time 14:56 Rev Time 0.00
Received By tklarge Date 2017-11-01 Time 15:25 Sent To  
Notes
2017-11-02 15:26:09RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-02 Cont ID  
Sent By lmarchan Date 2017-11-02 Time 11:15 Rev Time 0.00
Received By jpearson Date 2017-10-16 Time 12:51 Sent To  
Notes
2017-10-17 12:51:28C34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-04 Cont ID  
Sent By lmarchan Date 2017-10-04 Time 08:55 Rev Time 0.00
Received By lmarchan Date 2017-08-22 Time 14:01 Sent To  
Notes
2017-08-24 14:01:23C34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 08:48 Rev Time 0.00
Received By shill Date 2017-08-29 Time 08:48 Sent To  
Notes
2017-08-29 08:48:55PER EMAIL DATED 8/29/17 FROM WILLIE SWOPE, PALM BEACH
 COUNTY IMPACT FEE OFFICE, IMPACT FEES MAY BE PAID
 BEFORE (VERTICAL) BUILDING PERMIT; OK TO ISSUE
 FOUNDATION PERMITS WITHOUT PALM BEACH COUNTY IMPACT FEE
 COLLECTION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-10-23 Cont ID  
Sent By ccole Date 2017-10-23 Time 15:15 Rev Time 0.00
Received By ccole Date 2017-10-23 Time 15:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-11-03 Cont ID  
Sent By tklarge Date 2017-11-03 Time 14:56 Rev Time 0.00
Received By tklarge Date 2017-11-03 Time 09:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-10-30 Cont ID  
Sent By tklarge Date 2017-10-30 Time 09:18 Rev Time 0.00
Received By tklarge Date 2017-10-30 Time 08:58 Sent To  
Notes
2017-10-30 09:00:271) ONE SET OF THE SUBMITTED PLANS HAS PLUMBING SHEETS
 THAT DO NOT BEAR THE SEAL OF THE DESIGN ENGINEER OF
 RECORD. COMPLY WITH F.A.C. RULE 61G15-23.001. REFER TO
 SHEETS P-1, P-3, P-5, P-6 & P-10.
 2) ONE SET OF THE SUBMITTED PLANS DOES NOT CONTAIN ANY
 PLUMBING DRAWINGS. SUBMIT THE PLUMBING DRAWINGS FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-06 Cont ID  
Sent By gjohnson Date 2017-09-06 Time 17:01 Rev Time 0.00
Received By gjohnson Date 2017-09-06 Time 16:50 Sent To  
Notes
2017-09-06 17:02:151ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. TRAP PRIMER VALVES ARE REQUIRED ON ALL FLOOR DRAINS
 TRAP GUARDS ARE NOT APPROVED. PER FBC PL 1002.4 TRAP
 SEALS.
 EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS
 THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102
 MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO
 ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  
 2. THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. PER FBC PL
 708.3.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2017-10-23 Cont ID  
Sent By aclange Date 2017-10-23 Time 14:15 Rev Time 0.00
Received By aclange Date 2017-10-23 Time 14:15 Sent To  
Notes
2017-10-23 14:16:16RECEIVED SPECIAL INSPECTOR AGREEMENT.
 GFA PAUL H DANFOURTH PE, SI
 NOEL WOODALL INSPECTOR BN 2505
 CARL D. CROOK INSPECTOR BN 3909

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 18:16 Rev Time 0.00
Received By shill Date 2017-08-29 Time 18:16 Sent To  
Notes
2017-08-29 18:16:42SEE 17081012
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-11-01 Time   Rev Time 0.00
Received By pgreilic Date 2017-11-01 Time 12:13 Sent To  
Notes
2017-11-01 12:13:36PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-09-19 Time   Rev Time 0.00
Received By pgreilic Date 2017-09-19 Time 11:38 Sent To  
Notes
2017-09-19 11:38:43PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]