Plan Review Details - Permit 17081014
Plan Review Stops For Permit 17081014
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-23 Cont ID  
Sent By aclange Date 2017-10-23 Time 12:10 Rev Time 0.00
Received By aclange Date 2017-10-23 Time 11:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 18:17 Rev Time 0.00
Received By shill Date 2017-08-29 Time 18:17 Sent To  
Notes
2017-08-29 18:17:40SEE COMMENTS FOR 17081012
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-02 Cont ID  
Sent By jpearson Date 2017-11-02 Time 08:29 Rev Time 0.00
Received By jpearson Date 2017-10-25 Time 08:29 Sent To I
Notes
2017-10-25 08:29:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 PREVIOUS COMMENTS CORRECTED HAVE BEEN REMOVED AND NOTED
 AS CORRECTED. REMAINING PREVIOUS COMMENTS HAVE THE
 ORIGINAL COMMENT THAT STILL NEEDS CORRECTION WITH
 FURTHER COMMENT IN (PARENTHESES).
  
 1. CORRECTED.
 2. CORRECTED.
 3. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23.
 IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF
 SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP
 SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM
 WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5,
 695.4(B)(3); FBC 107.2.1 (JOCKEY PUMP AND ENTIRE FIRE
 PUMP SYSTEM HAS BEEN REMOVED FROM PLANS. THIS WILL NEED
 TO BE ON PLAN FOR THE FOUNDATION PERMIT BECAUSE THE
 WIRING TO THE FIRE PUMP NEEDS TO MEET THE CODE
 REQUIREMENTS OF NEC 695.6).
 4. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS
 FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E)
 (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS.
 THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT
 BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE
 CODE REQUIREMENTS OF NEC 695.6).
 5. CORRECTED.
 6. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR
 FIRE PUMP. NEC 695.3(B) (ENTIRE FIRE PUMP SYSTEM HAS
 BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN
 FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE
 FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC
 695.6 AND 695.14. SHOW LOCATION ON PLAN OF FIRE PUMP
 ROOM AND THE ELECTRICAL FEED TO THAT ROOM FROM PRIMARY
 AND SECONDARY SOURCE.)
 7. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER
 AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING,
 AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6
 (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS.
 THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT
 BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE
 CODE REQUIREMENTS OF NEC 695.6).
 8. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE
 FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE
 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS
 SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE
 430.251(B); FBC 107.2.1 (ENTIRE FIRE PUMP SYSTEM HAS
 BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN
 FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE
 FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC
 695.6).
  
 NEW COMMENT:
 9. ADDRESS ON THE PLANS SHOWS 2191 N AUSTRALIAN, PERMIT
 SHOWS 2181 N AUSTRALIAN. PROVIDE CORRECT ADDRESS ON
 PLANS. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-06 Cont ID  
Sent By jpearson Date 2017-09-06 Time 13:30 Rev Time 0.00
Received By jpearson Date 2017-09-06 Time 13:30 Sent To  
Notes
2017-09-06 13:29:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-8 SHOWS 7 SETS OF 750 KCMIL CU FOR SERVICE
 FEEDERS, WHILE SHEET E-6 SHOWS 7 SETS OF 600 KCMIL CU.
 CORRECT DISCREPANCY. FBC 107.2.1
 2. LOAD CALCULATION FOR MDP SHOWS SEVERAL DIFFERENT
 CALCULATIONS (ONE STORY, TWO STORY, ETC.). PROVIDE LOAD
 CALCULATION RELATED TO THIS PERMIT ONLY FOR THE SIX
 STORY BUILDING. REMOVE ALL OTHER UNRELATED INFORMATION.
 ADDITIONALLY, THE LOAD VA SHOWN FOR THE 1 BEDROOM UNIT
 IS THE SAME AS FOR THE 2 BEDROOM UNIT. LOAD CALCULATION
 FOR PANEL H IS DIFFERENT THAN LISTED IN PANEL SCHEDULE.
 PROVIDE CORRECTIONS. NEC 220, 220.84, 215.2, 408.30;
 FBC 107.2.1
 3. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23.
 IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF
 SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP
 SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM
 WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5,
 695.4(B)(3); FBC 107.2.1
 4. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS
 FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E)
 5. PANEL H LOAD CALCULATION STATES THAT THE FIRST 10K
 VA ARE AT 100%. HOWEVER, THE LOAD SHOWN IS 4320 VA, NOT
 10,000. PANEL H1 LOAD CALCULATION IS SIMILARLY WRONG.
 PROVIDE CORRECTION. NEC 220.44
 6. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR
 FIRE PUMP. NEC 695.3(B)
 7. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER
 AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING,
 AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6
 8. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE
 FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE
 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS
 SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE
 430.251(B); FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-10-25 Cont ID  
Sent By squinone Date 2017-10-25 Time   Rev Time  
Received By squinone Date 2017-10-25 Time   Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-02 Cont ID  
Sent By wjolin Date 2017-11-02 Time 09:07 Rev Time 0.00
Received By wjolin Date 2017-11-02 Time 09:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-25 Cont ID  
Sent By wjolin Date 2017-08-25 Time 12:54 Rev Time 0.00
Received By wjolin Date 2017-08-25 Time 12:54 Sent To  
Notes
2017-08-25 12:55:35FOUNDATION ONLY
  
 PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER
 MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE
 INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO
 CONSTRUCTION WORK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-31 Cont ID  
Sent By cpuell Date 2017-10-31 Time 12:52 Rev Time 0.00
Received By cpuell Date 2017-10-16 Time 12:48 Sent To  
Notes
2017-10-31 11:27:0110/31 TO PROCESSING
  
  
2017-10-31 11:05:5510/31 TO PAUL GRELLIC DESK
  
2017-10-17 12:49:00C01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-04 Cont ID  
Sent By lmarchan Date 2017-10-04 Time 08:55 Rev Time 0.00
Received By lmarchan Date 2017-08-22 Time 13:39 Sent To  
Notes
2017-08-24 13:39:51C01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 08:48 Rev Time 0.00
Received By shill Date 2017-08-29 Time 08:48 Sent To  
Notes
2017-08-29 08:48:27PER EMAIL DATED 8/29/17 FROM WILLIE SWOPE, PALM BEACH
 COUNTY IMPACT FEE OFFICE, IMPACT FEES MAY BE PAID
 BEFORE (VERTICAL) BUILDING PERMIT; OK TO ISSUE
 FOUNDATION PERMITS WITHOUT PALM BEACH COUNTY IMPACT FEE
 COLLECTION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-10-23 Cont ID  
Sent By ccole Date 2017-10-23 Time 14:59 Rev Time 0.00
Received By ccole Date 2017-10-23 Time 14:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-20 Cont ID  
Sent By gjohnson Date 2017-10-20 Time 07:16 Rev Time 0.00
Received By gjohnson Date 2017-10-20 Time 07:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-09-01 Cont ID  
Sent By thunt Date 2017-09-01 Time 15:36 Rev Time 0.00
Received By thunt Date 2017-09-01 Time 15:36 Sent To  
Notes
2017-09-01 15:37:13PASS FOR FOUNDATION ONLY 1ST ROUGH STORM AND SEWER ONLY

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2017-10-23 Cont ID  
Sent By aclange Date 2017-10-23 Time 14:11 Rev Time 0.00
Received By aclange Date 2017-10-23 Time 14:11 Sent To  
Notes
2017-10-23 14:14:52RECEIVED SPECIAL INSPECTOR AGREEMENT.
 GFA PAUL H DANFOURTH PE, SI
 NOEL WOODALL INSPECTOR BN 2505
 CARL D. CROOK INSPECTOR BN 3909
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 18:17 Rev Time 0.00
Received By shill Date 2017-08-29 Time 18:17 Sent To  
Notes
2017-08-29 18:18:00SEE COMMENTS FOR 17081012
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-10-31 Time   Rev Time 0.00
Received By pgreilic Date 2017-10-31 Time 11:19 Sent To  
Notes
2017-10-31 11:19:31PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-09-14 Time   Rev Time 0.00
Received By pgreilic Date 2017-09-13 Time 15:59 Sent To  
Notes
2017-09-14 14:41:17PAUL GREILICH, SENIOR PLANNER