Plan Review Details - Permit 17081012
| Plan Review Stops For Permit 17081012 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-10-24 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-10-24 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-10-23 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-08-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-28 |
Time |
18:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-28 |
Time |
18:13 |
Sent To |
|
|
| Notes |
| 2017-08-28 18:13:52 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. AS THIS IS A THRESHOLD BUILDING (6 STORY), A | | | THRESHOLD INSPECTION PLAN PREPARED BY SEOR IS REQUIRED. | | | REVISE THE INDEX PAGE TO INCLUDE THE THRESHOLD | | | INSPECTION PLAN (SHEET 1.1, SHOWN ON INDEX AS "NOTES"). | | | | | | 2. AS THIS IS A THRESHOLD BUILDING, THREE SETS OF PLANS | | | REQUIRED (CITY, SI, JOB). | | | | | | 3. STRUCTURAL CALCS PREPARED WITH ENERCALC REFER TO | | | INCORRECT (OUTDATED) CODE AND STANDARD REFERENCES, FBC | | | CHAPTER 35. REVISE AND CHECK ALL. | | | | | | 4. S2.6 SPECS A 3'6" PARAPET; CALCULATIONS (ENERCALC) | | | SPEC A 5' PARAPET, CLARIFY. S2.6 SHOULD BE REMOVED | | | (ROOF PLAN; NOT NEEDED FOR THIS PERMIT, SEE COMMENT | | | #5), BUT CALCULATIONS SHOULD BE CONSISTENT WITH | | | BUILDING DESIGN. | | | | | | 5. PLANS HAVE TOO MUCH INFORMATION. THIS APPEARS TO BE | | | A FULL SET OF PLANS, WHICH IS IN CONFLICT WITH THE | | | APPLICATION (FOUNDATION ONLY). FOR FOUNDATION PERMIT, | | | ONLY THE FOLLOWING IS REQUIRED: | | | | | | PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION | | | PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB) | | | GEOTECHNICAL REPORT | | | SURVEY DRAWING | | | STORM WATER POLLUTION PREVENTION PLAN | | | SITE PLAN | | | 1ST FLOOR ARCHITECTURAL PLAN | | | ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING | | | FOUNDATION PLAN | | | FOUNDATION DETAILS AND CROSS SECTIONS | | | STRUCTURAL ENGINEER'S GENERAL NOTES | | | UNDERGROUND PLUMBING PLAN (IF APPLICABLE) | | | ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT (IF | | | APPLICABLE) | | | ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR | | | EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT). | | | IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT, | | | AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR | | | PLAN SHOWING UNDERGROUND FIRE LINE | | | THRESHOLD INSPECTION PLAN OR RESIDENT INSPECTION PLAN | | | (AS APPLICABLE) | | | INFORMATION SPECIFICALLY REQUESTED BY FIRE OR | | | ENGINEERING | | | | | | SUBMISSION OF THE SHEETS NOT REQUIRED DELAYS FOUNDATION | | | PERMIT ISSUANCE. A REVIEW HAS NOT BEEN DONE ON SHEETS | | | OTHER THAN THOSE ABOVE. PLEASE REMOVE SHEETS NOT LISTED | | | ABOVE. | | | | | | 6. PLEASE ADVISE, WHO WILL PERFORM THE SOILS | | | IMPROVEMENT MONITORING? THIS INFORMATION MAY BE | | | PROVIDED IN A LETTER, ON LETTERHEAD, FBC 107. IF THE | | | VIBROFLOTATION PERMIT HAS BEEN ISSUED BEFORE THE | | | FOUNDATION PERMIT IS RESUBMITTED, YOU MAY DISREGARD | | | THIS COMMENT. UPON ISSUANCE, ALL DOCUMENTS ASSOCIATED | | | WITH A PERMIT BECOME AN OFFICIAL RECORD. | | | | | | 7. I WAS UNABLE TO LOCATE THE THRESHOLD STATEMENT | | | REQUIRED BY FS 553.79(7)(D) ON THE ARCHITECT'S AND | | | ENGINEER'S PLAN. REVISE TO INCLUDE. IF THIS IS ALREADY | | | ON THE PLANS, PLEASE ADVISE AS TO LOCATION AND IT IS | | | POSSIBLE THAT THIS REVIEW CAN BE PASSED WITH PROVISO. | | | | | | 8. PLEASE ADVISE, WILL THIS FOUNDATION PERMIT BE A | | | PRIVATE PROVIDER PROJECT? IF YES, PLEASE PROVIDE | | | PAPERWORK. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-11-02 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-02 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-26 |
Time |
14:24 |
Sent To |
I |
|
| Notes |
| 2017-10-26 14:24:32 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | PREVIOUS COMMENTS CORRECTED HAVE BEEN REMOVED AND NOTED | | | AS CORRECTED. REMAINING PREVIOUS COMMENTS HAVE THE | | | ORIGINAL COMMENT THAT STILL NEEDS CORRECTION WITH | | | FURTHER COMMENT IN (PARENTHESES). | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23. | | | IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF | | | SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP | | | SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM | | | WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5, | | | 695.4(B)(3); FBC 107.2.1 (ENTIRE FIRE PUMP SYSTEM HAS | | | BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN | | | FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE | | | FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC | | | 695.6). | | | 4. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS | | | FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E) | | | (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS. | | | THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT | | | BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE | | | CODE REQUIREMENTS OF NEC 695.6). | | | 5.CORRECTED. | | | 6. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR | | | FIRE PUMP. NEC 695.3(B) (ENTIRE FIRE PUMP SYSTEM HAS | | | BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN | | | FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE | | | FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC | | | 695.6 AND 695.14. SHOW LOCATION ON PLAN OF FIRE PUMP | | | ROOM AND THE ELECTRICAL FEED TO THAT ROOM FROM PRIMARY | | | AND SECONDARY SOURCE.) | | | 7. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER | | | AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING, | | | AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6 | | | (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS. | | | THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT | | | BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE | | | CODE REQUIREMENTS OF NEC 695.6). | | | 8. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE | | | FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE | | | 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS | | | SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE | | | 430.251(B); FBC 107.2.1 (ENTIRE FIRE PUMP SYSTEM HAS | | | BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN | | | FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE | | | FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC | | | 695.6). | | | | | | NEW COMMENT: | | | 9. ADDRESS ON THE PLANS SHOWS 2181 N AUSTRALIAN, PERMIT | | | SHOWS 2191 N AUSTRALIAN. PROVIDE CORRECT ADDRESS ON | | | PLANS. FBC 107.2.1 | | | | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-09-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-09-06 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-09-06 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2017-09-06 14:24:43 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SHEET E-8 SHOWS 7 SETS OF 750 KCMIL CU FOR SERVICE | | | FEEDERS, WHILE SHEET E-6 SHOWS 7 SETS OF 600 KCMIL CU. | | | CORRECT DISCREPANCY. FBC 107.2.1 | | | 2. LOAD CALCULATION FOR MDP SHOWS SEVERAL DIFFERENT | | | CALCULATIONS (ONE STORY, TWO STORY, ETC.). PROVIDE LOAD | | | CALCULATION RELATED TO THIS PERMIT ONLY FOR THE SIX | | | STORY BUILDING. REMOVE ALL OTHER UNRELATED INFORMATION. | | | ADDITIONALLY, THE LOAD VA SHOWN FOR THE 1 BEDROOM UNIT | | | IS THE SAME AS FOR THE 2 BEDROOM UNIT. LOAD CALCULATION | | | FOR PANEL H IS DIFFERENT THAN LISTED IN PANEL SCHEDULE. | | | PROVIDE CORRECTIONS. NEC 220, 220.84, 215.2, 408.30; | | | FBC 107.2.1 | | | 3. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23. | | | IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF | | | SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP | | | SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM | | | WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5, | | | 695.4(B)(3); FBC 107.2.1 | | | 4. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS | | | FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E) | | | 5. PANEL H LOAD CALCULATION STATES THAT THE FIRST 10K | | | VA ARE AT 100%. HOWEVER, THE LOAD SHOWN IS 4320 VA, NOT | | | 10,000. PANEL H1 LOAD CALCULATION IS SIMILARLY WRONG. | | | PROVIDE CORRECTION. NEC 220.44 | | | 6. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR | | | FIRE PUMP. NEC 695.3(B) | | | 7. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER | | | AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING, | | | AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6 | | | 8. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE | | | FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE | | | 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS | | | SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE | | | 430.251(B); FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2017-10-25 |
|
|
Cont ID |
|
| Sent By |
squinone |
Date |
2017-10-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
squinone |
Date |
2017-10-25 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-08-25 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-08-25 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-08-25 |
Time |
13:07 |
Sent To |
|
|
| Notes |
| 2017-08-25 13:07:58 | FOUNDATION ONLY | | | | | | PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER | | | MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE | | | INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO VERTICAL | | | CONSTRUCTION WORK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-02 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-02 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-16 |
Time |
12:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-10-04 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-10-04 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-08-22 |
Time |
13:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2017-08-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-29 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-29 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2017-08-29 08:47:39 | PER EMAIL DATED 8/29/17 FROM WILLIE SWOPE, PALM BEACH | | | COUNTY IMPACT FEE OFFICE, IMPACT FEES MAY BE PAID | | | BEFORE (VERTICAL) BUILDING PERMIT; OK TO ISSUE | | | FOUNDATION PERMITS WITHOUT PALM BEACH COUNTY IMPACT FEE | | | COLLECTION. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-10-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-25 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-25 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2017-09-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-09-19 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-09-19 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2017-09-19 12:11:13 | MECHANICAL APPROVAL FOR UNDERGROUND CONDENSATE PIPING | | | ONLY- CCOLE- 9/19/17 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-10-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-10-27 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-10-27 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-10-25 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-10-25 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-10-19 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2017-10-25 11:51:42 | 1) A COMPLETE SET OF PLUMBING PLANS HAS BEEN SUBMITTED | | | FOR REVIEW. THE PERMIT APPLICATION IS FOR A FOUNDATION | | | ONLY PERMIT. SUBMIT PLUMBING PLANS THAT REFLECT THE | | | SCOPE OF WORK TO BE INSTALLED FOR THE FOUNDATION PERMIT | | | ONLY. THE PLANS ARE VAGUE AS TO WHAT IS BEING INSTALLED | | | AT THIS TIME. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) PLACE A NOTE ON THE PLANS THAT THE PLUMBING RISERS | | | FOR THE UNDERGROUND COLLECTION SYSTEMS ( SANITARY, | | | STORM, WATER, COND., ETC.) WILL TERMINATE A MAXIMUM OF | | | 2 FEET ABOVE THE SLAB AND TERMINATE WITH AN APPROVED | | | CAP OR PLUG. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-09-05 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-09-05 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-05 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2017-09-05 14:17:47 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. TRAP PRIMER VALVES ARE REQUIRED ON ALL FLOOR DRAINS | | | TRAP GUARDS ARE NOT APPROVED. PER FBC PL 1002.4 TRAP | | | SEALS. | | | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS | | | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 | | | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO | | | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO | | | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE | | | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A | | | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR | | | ASSE 1044. | | | | | | 2. THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE | | | BUILDING DRAIN AND THE BUILDING SEWER. PER FBC PL | | | 708.3.5 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
P |
Date |
2017-10-23 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-10-23 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-10-23 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2017-10-23 14:23:14 | RECEIVED SPECIAL INSPECTOR AGREEMENT. | | | GFA PAUL H DANFOURTH PE, SI | | | NOEL WOODALL INSPECTOR BN 2505 | | | CARL D. CROOK INSPECTOR BN 3909 |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2017-08-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-28 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-28 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2017-08-28 15:36:17 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | A COMPLETE THRESHOLD PACKAGE (AGREEMENT SIGNED BY ALL | | | PARTIES, RESUMES FOR INDIVIDUALS AS DESCRIBED BELOW) | | | MAY BE SENT VIA EMAIL. | | | | | | A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | REVISE COVER PAGE/INDEX SHEET TO INCLUDE THE THRESHOLD | | | INSPECTION PLAN, FBC 107. | | | | | | B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. | | | | | | C) THRESHOLD BLDG., REQUIRED STATEMENT W.P.B. AMENDMENT | | | 110.3.7.4.4, FS553.79(7)(D): ALL PLANS FOR THE BUILDING | | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE | | | FIRESAFETY STANDARDS AS DETERMINED BY THE LOCAL | | | AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND CHAPTER | | | 633. | | | | | | I WAS UNABLE TO LOCATE, PLEASE ADVISE WHERE THIS CAN BE | | | FOUND (A AND S SHEETS). IF LANGUAGE IS NOT IDENTICAL TO | | | THE FLORIDA STATUTE, PLEASE EXPLAIN DISCREPANCY. | | | | | | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE | | | RESUME'. AFTER THE RESUME' IS REVIEWED, AN INTERVIEW | | | WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN | | | INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING | | | THE ABOVE CRITERIA. | | | | | | FOR THE JOB SITE INSPECTOR(S), PROVIDE RESUMES OF | | | EXPERIENCE. IT IS RECOMMENDED THAT MORE THAN ONE | | | INSPECTOR SIGN THE AGREEMENT IN THE EVENT THAT THE | | | PRIMARY INSPECTOR IS NOT AVAILABLE. UNDER NO | | | CIRCUMSTANCES WILL AN INSPECTOR NOT PREVIOUSLY APPROVED | | | BE PERMITTED TO PERFORM INSPECTIONS. PLEASE NOTE THAT | | | ADDITIONAL INSPECTORS MAY BE ADDED TO THE AGREEMENT | | | AFTER PERMIT ISSUANCE. | | | | | | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. | | | | | | F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED. | | | | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, | | | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT | | | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING | | | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND | | | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | SHORING AND RESHORE MUST BE REVIEWED AND ISSUED PRIOR | | | TO CONCRETE POUR. SHORING AND RESHORE ARE TO BE | | | REVIEWED BY SEOR PRIOR TO SUBMITTAL TO THE CITY, SEE | | | THRESHOLD INSPECTION PLAN. | | | | | | H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | I) NA (REVISED 10/16/17) | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-11-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2017-11-01 |
Time |
12:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-09-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2017-09-19 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
|