Plan Review Details - Permit 17081012
Plan Review Stops For Permit 17081012
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-24 Cont ID  
Sent By aclange Date 2017-10-24 Time 15:26 Rev Time 0.00
Received By aclange Date 2017-10-23 Time 11:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-28 Cont ID  
Sent By shill Date 2017-08-28 Time 18:13 Rev Time 0.00
Received By shill Date 2017-08-28 Time 18:13 Sent To  
Notes
2017-08-28 18:13:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. AS THIS IS A THRESHOLD BUILDING (6 STORY), A
 THRESHOLD INSPECTION PLAN PREPARED BY SEOR IS REQUIRED.
 REVISE THE INDEX PAGE TO INCLUDE THE THRESHOLD
 INSPECTION PLAN (SHEET 1.1, SHOWN ON INDEX AS "NOTES").
  
 2. AS THIS IS A THRESHOLD BUILDING, THREE SETS OF PLANS
 REQUIRED (CITY, SI, JOB).
  
 3. STRUCTURAL CALCS PREPARED WITH ENERCALC REFER TO
 INCORRECT (OUTDATED) CODE AND STANDARD REFERENCES, FBC
 CHAPTER 35. REVISE AND CHECK ALL.
  
 4. S2.6 SPECS A 3'6" PARAPET; CALCULATIONS (ENERCALC)
 SPEC A 5' PARAPET, CLARIFY. S2.6 SHOULD BE REMOVED
 (ROOF PLAN; NOT NEEDED FOR THIS PERMIT, SEE COMMENT
 #5), BUT CALCULATIONS SHOULD BE CONSISTENT WITH
 BUILDING DESIGN.
  
 5. PLANS HAVE TOO MUCH INFORMATION. THIS APPEARS TO BE
 A FULL SET OF PLANS, WHICH IS IN CONFLICT WITH THE
 APPLICATION (FOUNDATION ONLY). FOR FOUNDATION PERMIT,
 ONLY THE FOLLOWING IS REQUIRED:
  
 PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION
 PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB)
 GEOTECHNICAL REPORT
 SURVEY DRAWING
 STORM WATER POLLUTION PREVENTION PLAN
 SITE PLAN
 1ST FLOOR ARCHITECTURAL PLAN
 ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING
 FOUNDATION PLAN
 FOUNDATION DETAILS AND CROSS SECTIONS
 STRUCTURAL ENGINEER'S GENERAL NOTES
 UNDERGROUND PLUMBING PLAN (IF APPLICABLE)
 ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT (IF
 APPLICABLE)
 ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR
 EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT).
 IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT,
 AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR
 PLAN SHOWING UNDERGROUND FIRE LINE
 THRESHOLD INSPECTION PLAN OR RESIDENT INSPECTION PLAN
 (AS APPLICABLE)
 INFORMATION SPECIFICALLY REQUESTED BY FIRE OR
 ENGINEERING
  
 SUBMISSION OF THE SHEETS NOT REQUIRED DELAYS FOUNDATION
 PERMIT ISSUANCE. A REVIEW HAS NOT BEEN DONE ON SHEETS
 OTHER THAN THOSE ABOVE. PLEASE REMOVE SHEETS NOT LISTED
 ABOVE.
  
 6. PLEASE ADVISE, WHO WILL PERFORM THE SOILS
 IMPROVEMENT MONITORING? THIS INFORMATION MAY BE
 PROVIDED IN A LETTER, ON LETTERHEAD, FBC 107. IF THE
 VIBROFLOTATION PERMIT HAS BEEN ISSUED BEFORE THE
 FOUNDATION PERMIT IS RESUBMITTED, YOU MAY DISREGARD
 THIS COMMENT. UPON ISSUANCE, ALL DOCUMENTS ASSOCIATED
 WITH A PERMIT BECOME AN OFFICIAL RECORD.
  
 7. I WAS UNABLE TO LOCATE THE THRESHOLD STATEMENT
 REQUIRED BY FS 553.79(7)(D) ON THE ARCHITECT'S AND
 ENGINEER'S PLAN. REVISE TO INCLUDE. IF THIS IS ALREADY
 ON THE PLANS, PLEASE ADVISE AS TO LOCATION AND IT IS
 POSSIBLE THAT THIS REVIEW CAN BE PASSED WITH PROVISO.
  
 8. PLEASE ADVISE, WILL THIS FOUNDATION PERMIT BE A
 PRIVATE PROVIDER PROJECT? IF YES, PLEASE PROVIDE
 PAPERWORK.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-02 Cont ID  
Sent By jpearson Date 2017-11-02 Time 14:24 Rev Time 0.00
Received By jpearson Date 2017-10-26 Time 14:24 Sent To I
Notes
2017-10-26 14:24:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 PREVIOUS COMMENTS CORRECTED HAVE BEEN REMOVED AND NOTED
 AS CORRECTED. REMAINING PREVIOUS COMMENTS HAVE THE
 ORIGINAL COMMENT THAT STILL NEEDS CORRECTION WITH
 FURTHER COMMENT IN (PARENTHESES).
  
 1. CORRECTED.
 2. CORRECTED.
 3. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23.
 IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF
 SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP
 SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM
 WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5,
 695.4(B)(3); FBC 107.2.1 (ENTIRE FIRE PUMP SYSTEM HAS
 BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN
 FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE
 FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC
 695.6).
 4. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS
 FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E)
 (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS.
 THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT
 BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE
 CODE REQUIREMENTS OF NEC 695.6).
 5.CORRECTED.
 6. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR
 FIRE PUMP. NEC 695.3(B) (ENTIRE FIRE PUMP SYSTEM HAS
 BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN
 FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE
 FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC
 695.6 AND 695.14. SHOW LOCATION ON PLAN OF FIRE PUMP
 ROOM AND THE ELECTRICAL FEED TO THAT ROOM FROM PRIMARY
 AND SECONDARY SOURCE.)
 7. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER
 AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING,
 AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6
 (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS.
 THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT
 BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE
 CODE REQUIREMENTS OF NEC 695.6).
 8. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE
 FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE
 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS
 SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE
 430.251(B); FBC 107.2.1 (ENTIRE FIRE PUMP SYSTEM HAS
 BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN
 FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE
 FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC
 695.6).
  
 NEW COMMENT:
 9. ADDRESS ON THE PLANS SHOWS 2181 N AUSTRALIAN, PERMIT
 SHOWS 2191 N AUSTRALIAN. PROVIDE CORRECT ADDRESS ON
 PLANS. FBC 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-06 Cont ID  
Sent By jpearson Date 2017-09-06 Time 14:24 Rev Time 0.00
Received By jpearson Date 2017-09-06 Time 14:24 Sent To  
Notes
2017-09-06 14:24:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-8 SHOWS 7 SETS OF 750 KCMIL CU FOR SERVICE
 FEEDERS, WHILE SHEET E-6 SHOWS 7 SETS OF 600 KCMIL CU.
 CORRECT DISCREPANCY. FBC 107.2.1
 2. LOAD CALCULATION FOR MDP SHOWS SEVERAL DIFFERENT
 CALCULATIONS (ONE STORY, TWO STORY, ETC.). PROVIDE LOAD
 CALCULATION RELATED TO THIS PERMIT ONLY FOR THE SIX
 STORY BUILDING. REMOVE ALL OTHER UNRELATED INFORMATION.
 ADDITIONALLY, THE LOAD VA SHOWN FOR THE 1 BEDROOM UNIT
 IS THE SAME AS FOR THE 2 BEDROOM UNIT. LOAD CALCULATION
 FOR PANEL H IS DIFFERENT THAN LISTED IN PANEL SCHEDULE.
 PROVIDE CORRECTIONS. NEC 220, 220.84, 215.2, 408.30;
 FBC 107.2.1
 3. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23.
 IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF
 SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP
 SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM
 WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5,
 695.4(B)(3); FBC 107.2.1
 4. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS
 FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E)
 5. PANEL H LOAD CALCULATION STATES THAT THE FIRST 10K
 VA ARE AT 100%. HOWEVER, THE LOAD SHOWN IS 4320 VA, NOT
 10,000. PANEL H1 LOAD CALCULATION IS SIMILARLY WRONG.
 PROVIDE CORRECTION. NEC 220.44
 6. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR
 FIRE PUMP. NEC 695.3(B)
 7. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER
 AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING,
 AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6
 8. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE
 FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE
 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS
 SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE
 430.251(B); FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-10-25 Cont ID  
Sent By squinone Date 2017-10-25 Time   Rev Time 0.00
Received By squinone Date 2017-10-25 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-25 Cont ID  
Sent By wjolin Date 2017-08-25 Time 13:07 Rev Time 0.00
Received By wjolin Date 2017-08-25 Time 13:07 Sent To  
Notes
2017-08-25 13:07:58FOUNDATION ONLY
  
 PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER
 MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE
 INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO VERTICAL
 CONSTRUCTION WORK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-02 Cont ID  
Sent By jpearson Date 2017-11-02 Time 11:07 Rev Time 0.00
Received By jpearson Date 2017-10-16 Time 12:41 Sent To  
Notes
2017-10-17 12:42:13C38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-04 Cont ID  
Sent By lmarchan Date 2017-10-04 Time 08:54 Rev Time 0.00
Received By lmarchan Date 2017-08-22 Time 13:40 Sent To  
Notes
2017-08-24 13:40:52C39

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 08:45 Rev Time 0.00
Received By shill Date 2017-08-29 Time 08:45 Sent To  
Notes
2017-08-29 08:47:39PER EMAIL DATED 8/29/17 FROM WILLIE SWOPE, PALM BEACH
 COUNTY IMPACT FEE OFFICE, IMPACT FEES MAY BE PAID
 BEFORE (VERTICAL) BUILDING PERMIT; OK TO ISSUE
 FOUNDATION PERMITS WITHOUT PALM BEACH COUNTY IMPACT FEE
 COLLECTION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By ccole Date 2017-10-25 Time 11:05 Rev Time 0.00
Received By ccole Date 2017-10-25 Time 11:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-09-19 Cont ID  
Sent By ccole Date 2017-09-19 Time 12:09 Rev Time 0.00
Received By ccole Date 2017-09-19 Time 11:47 Sent To  
Notes
2017-09-19 12:11:13MECHANICAL APPROVAL FOR UNDERGROUND CONDENSATE PIPING
 ONLY- CCOLE- 9/19/17

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-10-27 Cont ID  
Sent By tklarge Date 2017-10-27 Time 14:23 Rev Time 0.00
Received By tklarge Date 2017-10-27 Time 14:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-10-25 Cont ID  
Sent By tklarge Date 2017-10-25 Time 11:51 Rev Time 0.00
Received By tklarge Date 2017-10-19 Time 09:36 Sent To  
Notes
2017-10-25 11:51:421) A COMPLETE SET OF PLUMBING PLANS HAS BEEN SUBMITTED
 FOR REVIEW. THE PERMIT APPLICATION IS FOR A FOUNDATION
 ONLY PERMIT. SUBMIT PLUMBING PLANS THAT REFLECT THE
 SCOPE OF WORK TO BE INSTALLED FOR THE FOUNDATION PERMIT
 ONLY. THE PLANS ARE VAGUE AS TO WHAT IS BEING INSTALLED
 AT THIS TIME. WPB AMEND. TO FBC SEC. 107.2.1.
 2) PLACE A NOTE ON THE PLANS THAT THE PLUMBING RISERS
 FOR THE UNDERGROUND COLLECTION SYSTEMS ( SANITARY,
 STORM, WATER, COND., ETC.) WILL TERMINATE A MAXIMUM OF
 2 FEET ABOVE THE SLAB AND TERMINATE WITH AN APPROVED
 CAP OR PLUG.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-05 Cont ID  
Sent By gjohnson Date 2017-09-05 Time 14:05 Rev Time 0.00
Received By gjohnson Date 2017-09-05 Time 14:05 Sent To  
Notes
2017-09-05 14:17:471ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. TRAP PRIMER VALVES ARE REQUIRED ON ALL FLOOR DRAINS
 TRAP GUARDS ARE NOT APPROVED. PER FBC PL 1002.4 TRAP
 SEALS.
 EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS
 THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102
 MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO
 ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  
 2. THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. PER FBC PL
 708.3.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2017-10-23 Cont ID  
Sent By aclange Date 2017-10-23 Time 14:22 Rev Time 0.00
Received By aclange Date 2017-10-23 Time 14:22 Sent To  
Notes
2017-10-23 14:23:14RECEIVED SPECIAL INSPECTOR AGREEMENT.
 GFA PAUL H DANFOURTH PE, SI
 NOEL WOODALL INSPECTOR BN 2505
 CARL D. CROOK INSPECTOR BN 3909

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-08-28 Cont ID  
Sent By shill Date 2017-08-28 Time 15:27 Rev Time 0.00
Received By shill Date 2017-08-28 Time 15:27 Sent To  
Notes
2017-08-28 15:36:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A COMPLETE THRESHOLD PACKAGE (AGREEMENT SIGNED BY ALL
 PARTIES, RESUMES FOR INDIVIDUALS AS DESCRIBED BELOW)
 MAY BE SENT VIA EMAIL.
  
 A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 REVISE COVER PAGE/INDEX SHEET TO INCLUDE THE THRESHOLD
 INSPECTION PLAN, FBC 107.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 C) THRESHOLD BLDG., REQUIRED STATEMENT W.P.B. AMENDMENT
 110.3.7.4.4, FS553.79(7)(D): ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRESAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND CHAPTER
 633.
  
 I WAS UNABLE TO LOCATE, PLEASE ADVISE WHERE THIS CAN BE
 FOUND (A AND S SHEETS). IF LANGUAGE IS NOT IDENTICAL TO
 THE FLORIDA STATUTE, PLEASE EXPLAIN DISCREPANCY.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE
 RESUME'. AFTER THE RESUME' IS REVIEWED, AN INTERVIEW
 WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN
 INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING
 THE ABOVE CRITERIA.
  
 FOR THE JOB SITE INSPECTOR(S), PROVIDE RESUMES OF
 EXPERIENCE. IT IS RECOMMENDED THAT MORE THAN ONE
 INSPECTOR SIGN THE AGREEMENT IN THE EVENT THAT THE
 PRIMARY INSPECTOR IS NOT AVAILABLE. UNDER NO
 CIRCUMSTANCES WILL AN INSPECTOR NOT PREVIOUSLY APPROVED
 BE PERMITTED TO PERFORM INSPECTIONS. PLEASE NOTE THAT
 ADDITIONAL INSPECTORS MAY BE ADDED TO THE AGREEMENT
 AFTER PERMIT ISSUANCE.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 SHORING AND RESHORE MUST BE REVIEWED AND ISSUED PRIOR
 TO CONCRETE POUR. SHORING AND RESHORE ARE TO BE
 REVIEWED BY SEOR PRIOR TO SUBMITTAL TO THE CITY, SEE
 THRESHOLD INSPECTION PLAN.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) NA (REVISED 10/16/17)
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-11-01 Time   Rev Time 0.00
Received By pgreilic Date 2017-11-01 Time 12:14 Sent To  
Notes
2017-11-01 12:14:30PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-09-19 Time   Rev Time 0.00
Received By pgreilic Date 2017-09-19 Time 11:07 Sent To  
Notes
2017-09-19 11:08:02PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]