Plan Review Details - Permit 17081010
Plan Review Stops For Permit 17081010
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By rmcdouga Date 2017-08-25 Time 17:42 Rev Time 0.00
Received By rmcdouga Date 2017-08-25 Time 17:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-24 Cont ID  
Sent By rmcdouga Date 2017-08-24 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2017-08-24 Time 16:30 Sent To  
Notes
2017-08-24 16:30:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF A ROOF DIAGRAM THAT SHOWS THE
 LOCATIONS OF THE SKYLIGHTS THAT ARE BEING REPLACED.
 SPECIFY THE ROOF SLOPE AND THE ROOF HEIGHT ON THE
 DRAWINGS. THE DESIGN PRESSURES FROM THE PRODUCT
 APPROVALS IS +60 PSF AND - 60 PSF, WHICH IS NOT
 ADEQUATE FOR ROOF ZONE 3. FBC 107.2.1
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-24 Cont ID  
Sent By rmcdouga Date 2017-08-24 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2017-08-22 Time 12:45 Sent To  
Notes
2017-08-23 12:45:26REVISION ROUTED TO RMCDOUGAL