| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-10-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-10-06 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-10-06 |
Time |
07:14 |
Sent To |
|
|
| Notes |
| 2017-10-06 07:48:05 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD CALCULATIONS ARE REQUIRED TO HAVE | | | THE FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN | | | SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT | | | ACCEPTABLE. FAC 61G15 - 23.002 | | | | | | 2) THE ENGINEER, RONALD H. WILSON, THAT IS ON THE | | | AMERICAST PAD ANCHORING PLAN HAS HAD HIS FLORIDA PE | | | LICENSE REVOKED. THE SIGNATURE ON THE PLAN IS NOT AN | | | ORIGINAL HANDWRITTEN ONE AS REQUIRED BY FAC | | | 61G15-23.002. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-08-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-08-28 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-28 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2017-08-28 10:57:46 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD CALCULATIONS ARE REQUIRED TO HAVE | | | THE FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN | | | SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT | | | ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE | | | ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS | | | AND DOCUMENTS. | | | | | | 2) THIS PROJECT IS LOCATED IN EXPOSURE CATEGORY D WITH | | | A 170 MPH WIND SPEED. PROVIDE THE REQUIRED DESIGN | | | PRESSURES FOR THE GENERATOR ANCHORING. THE PRESSURES | | | INDICATED ON THE GENERATOR PAD DOCUMENTS ARE NOT | | | ADEQUATE. FBC-R301.2.1 | | | | | | 3) THE PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA. THE GENERATOR EQUIPMENT IS REQUIRED TO BE LOCATED | | | ONE FOOT ABOVE THE BFE, WHICH WILL BE 8 FEET NGVD. | | | FBC-R322.1.6 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-08-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-08-29 |
Time |
18:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-08-29 |
Time |
18:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2017-11-02 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2017-11-02 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2017-11-02 |
Time |
15:49 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2017-10-05 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2017-10-05 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2017-10-05 |
Time |
14:31 |
Sent To |
B1 |
|
| Notes |
| 2017-10-05 14:42:58 | 10/5/17 2ND GAS REVIEW**DENIED** | | | | | | 1) THE P.E RONALD WILSON LIC #9710 LICENSE HAS BEEN | | | REVOKED SINCE 02/28/2017. ALSO ALL SIGNATURES ARE | | | REQUIRED TO BE WET (NO COPIES) PER FL ADMIN CODE | | | 61G15-23.001. PLEASE RESUBMIT | | | | | | 2) YOU ARE STILL MISSING THE SIZING TABLE FOR THE | | | SCHEDULE 40 METALLIC PIPE AS A .5LB PLEASE SUBMIT THE | | | PROPER TABLE FBC-G 402.3 | | | | | | 3) PROVIDE MANUFACTOR SPECS FOR EXISTING GAS REGULATOR | | | AS THIS IS NOT A LIKE FOR LIKE SYSTEM. CITY RECORDS | | | SHOW A SMALLER EXISTING GENERATOR INSTALLED IN 2006 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-08-28 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2017-08-28 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2017-08-28 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2017-08-28 15:01:30 | GAS 1ST REVIEW DENIED 8/28/17 | | | | | | 1) PROVIDE WHICH GAS IS BEING USED. GAS RISER IS | | | SHOWING NATURAL GAS WHILE SIZING CHARTS PROVIDED ARE | | | FOR L.P (FBC 107.1) | | | | | | 2) PROVIDE CORRECT SIZING CHARTS THAT COMPLY WITH 402.3 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-11-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-11-03 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-10-26 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2017-10-27 11:48:02 | RESUB ROUTED TO THUNT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-10-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-10-06 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-10-04 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2017-10-05 10:07:09 | RESUB ROUTED TO THUNT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-08-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-08-29 |
Time |
18:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-08-22 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2017-08-23 11:20:06 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2017-08-25 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-08-25 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-08-24 |
Time |
14:44 |
Sent To |
|
|
| Notes |
|
|