Plan Review Details - Permit 17081008
Plan Review Stops For Permit 17081008
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-11-03 Cont ID  
Sent By rmcdouga Date 2017-11-03 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2017-11-03 Time 15:39 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-06 Cont ID  
Sent By rmcdouga Date 2017-10-06 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2017-10-06 Time 07:14 Sent To  
Notes
2017-10-06 07:48:05PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD CALCULATIONS ARE REQUIRED TO HAVE
 THE FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002
  
 2) THE ENGINEER, RONALD H. WILSON, THAT IS ON THE
 AMERICAST PAD ANCHORING PLAN HAS HAD HIS FLORIDA PE
 LICENSE REVOKED. THE SIGNATURE ON THE PLAN IS NOT AN
 ORIGINAL HANDWRITTEN ONE AS REQUIRED BY FAC
 61G15-23.002.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-28 Cont ID  
Sent By rmcdouga Date 2017-08-28 Time 09:02 Rev Time 0.00
Received By rmcdouga Date 2017-08-28 Time 09:02 Sent To  
Notes
2017-08-28 10:57:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD CALCULATIONS ARE REQUIRED TO HAVE
 THE FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE
 ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS
 AND DOCUMENTS.
  
 2) THIS PROJECT IS LOCATED IN EXPOSURE CATEGORY D WITH
 A 170 MPH WIND SPEED. PROVIDE THE REQUIRED DESIGN
 PRESSURES FOR THE GENERATOR ANCHORING. THE PRESSURES
 INDICATED ON THE GENERATOR PAD DOCUMENTS ARE NOT
 ADEQUATE. FBC-R301.2.1
  
 3) THE PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA. THE GENERATOR EQUIPMENT IS REQUIRED TO BE LOCATED
 ONE FOOT ABOVE THE BFE, WHICH WILL BE 8 FEET NGVD.
 FBC-R322.1.6

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-29 Cont ID  
Sent By jleahy Date 2017-08-29 Time 18:09 Rev Time 0.00
Received By jleahy Date 2017-08-29 Time 18:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-11-02 Cont ID  
Sent By thunt Date 2017-11-02 Time 15:49 Rev Time 0.00
Received By thunt Date 2017-11-02 Time 15:49 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-10-05 Cont ID  
Sent By thunt Date 2017-10-05 Time 14:31 Rev Time 0.00
Received By thunt Date 2017-10-05 Time 14:31 Sent To B1
Notes
2017-10-05 14:42:5810/5/17 2ND GAS REVIEW**DENIED**
  
 1) THE P.E RONALD WILSON LIC #9710 LICENSE HAS BEEN
 REVOKED SINCE 02/28/2017. ALSO ALL SIGNATURES ARE
 REQUIRED TO BE WET (NO COPIES) PER FL ADMIN CODE
 61G15-23.001. PLEASE RESUBMIT
  
 2) YOU ARE STILL MISSING THE SIZING TABLE FOR THE
 SCHEDULE 40 METALLIC PIPE AS A .5LB PLEASE SUBMIT THE
 PROPER TABLE FBC-G 402.3
  
 3) PROVIDE MANUFACTOR SPECS FOR EXISTING GAS REGULATOR
 AS THIS IS NOT A LIKE FOR LIKE SYSTEM. CITY RECORDS
 SHOW A SMALLER EXISTING GENERATOR INSTALLED IN 2006

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-08-28 Cont ID  
Sent By thunt Date 2017-08-28 Time 14:59 Rev Time 0.00
Received By thunt Date 2017-08-28 Time 14:44 Sent To  
Notes
2017-08-28 15:01:30GAS 1ST REVIEW DENIED 8/28/17
  
 1) PROVIDE WHICH GAS IS BEING USED. GAS RISER IS
 SHOWING NATURAL GAS WHILE SIZING CHARTS PROVIDED ARE
 FOR L.P (FBC 107.1)
  
 2) PROVIDE CORRECT SIZING CHARTS THAT COMPLY WITH 402.3
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-03 Cont ID  
Sent By rmcdouga Date 2017-11-03 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2017-10-26 Time 11:47 Sent To  
Notes
2017-10-27 11:48:02RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-06 Cont ID  
Sent By rmcdouga Date 2017-10-06 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2017-10-04 Time 10:06 Sent To  
Notes
2017-10-05 10:07:09RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-29 Cont ID  
Sent By jleahy Date 2017-08-29 Time 18:09 Rev Time 0.00
Received By jleahy Date 2017-08-22 Time 11:19 Sent To  
Notes
2017-08-23 11:20:06ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-25 Cont ID  
Sent By njwira Date 2017-08-25 Time 16:19 Rev Time 0.00
Received By njwira Date 2017-08-24 Time 14:44 Sent To  
Notes
***NONE***