Plan Review Details - Permit 17080987
Plan Review Stops For Permit 17080987
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-02-26 Cont ID  
Sent By jwitmer Date 2018-02-26 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2018-02-26 Time 07:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-11-14 Cont ID  
Sent By jwitmer Date 2017-11-14 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2017-11-13 Time 16:57 Sent To  
Notes
2017-11-14 07:52:072014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080987
 W. P. B. PERMIT: 15100589
 ADD: 1600 N. DIXIE HWY.
 CONT: R J S CONSTRUCTION
 TEL: 561-795-4712
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 13/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE FROM THE ISSUED PERMIT THERE HAS BEEN A
 CHANGE IN DESIGN PROFESSIONALS. UNDER THE PERMIT ISSUED
 15100589 THE ARCHITECT WAS NIKI L. NORTON AR 91827,
 UNDER THIS REVISION ARCHITECT VLAD DUMITRESCU AR 93102
 IS SHOWN AS THE ARCHITECT OF RECORD. PLEASE SHOW
 COMPLIANCE WITH THE:
  
 FLORIDA ADMINISTRATIVE CODE 61G-18.002(2) PRIOR TO
 SEALING, SIGNING AND DATING WORK, A SUCCESSOR
 REGISTERED ARCHITECT SHALL BE REQUIRED TO NOTIFY THE
 ORIGINAL REGISTERED ARCHITECT, HIS SUCCESSORS, OR
 ASSIGNS BY CERTIFIED LETTER TO THE LAST KNOWN ADDRESS
 OF THE ORIGINAL REGISTERED ARCHITECT OF THE SUCCESSOR'S
 INTENTION TO USE OR REUSE THE ORIGINAL REGISTERED
 ARCHITECT'S WORK. THE SUCCESSOR REGISTERED ARCHITECT
 WILL TAKE FULL RESPONSIBILITY FOR THE DRAWING AS THOUGH
 THEY WERE THE SUCCESSOR REGISTERED ARCHITECT'S ORIGINAL
 PRODUCT.
  
 2) THE ORIGINAL BUILDING DESIGN WAS LISTED AS A III-B
 UNSPRINKLERED BUILDING, THE NEW BUILDING DESIGN BY THE
 NEW ARCHITECT IS A V-B. THE COVERSHEET A-0 INDICATES
 THE BUILDING IS TO BE FIRE SPRINKLERED, THE WHOLE
 BUILDING OR ONLY THIS TENANT SPACE. NO FIRE SPRINKLER
 PLANS WERE SUBMITTED UNDER THIS REVIEW.107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) THE COVER SHEET INDICATES THIS IS TO BE A BUSINESS
 OCCUPANCY BUT THE FLOOR PLAN INDICATES A SQUARE FOOT
 AREA OF 1309 SQ. FT. OF SALES/ RECEPTION WITH AN
 OCCUPANT LOAD OF 13. PLEASE EXPLAIN WHY THIS AREA IS
 NOT A MERCANTILE OCCUPANCY SINCE IT IS A SALES FLOOR?
 107.2.1.3. THE OTHER ISSUE IN EITHER CASE OCCUPANT
 LOADS ARE NEVER ROUNDED DOWN YOU ALWAYS HAVE OCCUPANTS
 AS WHOLE PEOPLE. THE
  
 4) SHEET A-1 ACCESSIBLE DETAILS:
 4A) THE RESTROOM (WATER CLOSET) GRAB BARS SHOW THE
 DIMENSION FROM THE FINISH FLOOR TO THE CENTERLINE OF
 THE GRAB BAR, PLEASE NOTE UNDER THE 2014
 FBC-ACCESSIBILITY CODE THE DIMENSIONS ARE TAKEN FROM
 THE FINISH FLOOR TO THE TOP OF THE GRASPABLE SURFACE
 THIS WILL MAKE A ? INCH DIFFERENCE IN HEIGHT.
  
 ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 4B) THE ACCESSIBLE DETAIL UPPER LEFT PORTION OF THE
 SHEET SHOWS THE MAXIMUM HEIGHT OF THE MIRROR TO BE 40
 INCHES DRAWN TO THE BOTTOM EDGE OF THE MIRROR, PLEASE
 NOTE THE 40 INCHES MAXIMUM HEIGHT IS TO BE TAKEN FROM
 FINISH FLOOR TO THE BOTTOM EDGE OF THE REFLECTIVE
 MIRROR FINISH SEE ACCESSIBILITY CODE 603.3.
  
 4C) PLEASE NOTE THE HANDICAPPED SIGNAGE WITH TACTILE
 SURFACE IS INDICATED TO BE 5 FEET CANTERED ABOVE THE
 FINISH FLOOR. PLEASE ALSO REVIEW SECTION SIGNAGE.
 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND. TACTILE
 CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES MINIMUM
 ABOVE THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM
 THE BASELINE OF THE LOWEST TACTILE CHARACTER AND 60
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE HIGHEST
 TACTILE CHARACTER.
  
 4D) DETAIL # 3 THE LOUNGE ELEVATION SHOWS A MICROWAVE
 THE BOTTOM AT APPROXIMATELY 4 FOOT 6 INCHES ABOVE
 FINISH FLOOR.
 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 (22.2 N) MAXIMUM.
  
 4E) THE DETAIL # 3 ALSO SHOWS THERE TO BE A SINK IN THE
 LOUNGE AREA BUT THE ELEVATION DETAIL DOES NOT PROVIDE A
 VERTICAL DIMENSION FOR THE SINK ELEVATION. 2014
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-31 Cont ID  
Sent By jwitmer Date 2017-08-31 Time 15:49 Rev Time 0.00
Received By jwitmer Date 2017-08-25 Time 06:30 Sent To  
Notes
2017-08-31 15:49:05FEES NOT PAID NO REVIEW. 08/31/2017. JW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-13 Cont ID  
Sent By jpearson Date 2018-03-13 Time 13:51 Rev Time 0.00
Received By jpearson Date 2018-03-12 Time 16:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-16 Cont ID  
Sent By jleahy Date 2017-11-16 Time 13:02 Rev Time 0.00
Received By jpearson Date 2017-11-16 Time 13:02 Sent To M
Notes
2017-11-16 13:01:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 2. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, 405.2.2.2
 3. MECHANICAL SHEET SHOWS THE RTU'S AS 208 VOLT, BUT
 PANEL SCHEDULE SHOWS THE WIRING AS 120 VOLT. PROVIDE
 CORRECTION. FBC 107.2.1; NEC 408.4
 4. TWO OF THE RTU'S ON POWER PLAN ARE MARKED AS RTU-2.
 PROVIDE CORRECTION. FBC 107.2.1
 5. WIRE SIZE FROM GUTTER TO METER CAN IS SHOWN AS # 3.
 THIS SIZE WIRE IS NOT RATED FOR 200 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16)
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 7. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 9. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1
 10. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1
 11. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER. WITH
 INFORMATION PROVIDED, IT APPEARS THE CIRCUIT TO THIS
 UNIT IS UNDERSIZED. 13,500 WATTS/208 VOLTS = 64.9 AMPS.
 A 60 AMP CIRCUIT IS SHOWN IN PANEL SCHEDULE. NEC 110.3,
 215.2, 310.15(B)(16)
 12. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT ON ROOF PER CODE. NEC 210.63
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-14 Cont ID  
Sent By pleduc Date 2018-02-14 Time   Rev Time 0.00
Received By pleduc Date 2018-02-14 Time 10:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By pleduc Date 2017-08-30 Time   Rev Time 0.00
Received By pleduc Date 2017-08-30 Time 13:02 Sent To  
Notes
2017-08-30 13:38:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 0 - THERE IS AN INDICATION OF A FIRE
 SPRINKLER SYSTEM BY OTHERS. RECORDS INDICATE THAT THIS
 BUILDING IS NOT EQUIPPED WITH AN EXISTING FIRE
 SPRINKLER SYSTEM.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION
 ENGINEERING
 DOCUMENTS.
 (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED
 IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE
 WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND
 DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S),
 MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND
 UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE
 SAFEGUARDING OF LIFE, HEALTH OR PROPERTY.
 (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE
 ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND
 COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES
 AND STANDARDS, WHERE AVAILABLE.
 (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A
 SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION
 SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE
 PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT
 AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE
 TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND
 ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT
 SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED
 BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE
 FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL
 BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS.
 (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION
 FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT
 COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED
 ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER
 OF RECORD FOR THE FIRE PROTECTION SYSTEM.
 (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS,
 SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY
 RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN
 ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,
 UNLESS SHOWN ON OTHER RELATED DOCUMENTS.
 (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER
 OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION
 IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED
 PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE
 SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR
 OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE
 SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED
 4-2-2000, 6-26-01
  
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE:
 (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER
 SUPPLY AS DEFINED BY 633.021(18) F.S.
 (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE
 CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING
 STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND
 CONCLUSIONS.
 (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA.
 (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE,
 DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR
 EACH SEPARATE 42 HAZARD OCCUPANCY.
 (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS
 MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR
 CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE
 NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM
 DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY
 DEMANDING DESIGN AREA.
 (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE
 FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO
 CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION,
 STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH
 RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND
 LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF
 SERVICE.
 (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE
 POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF
 WATER.
 (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF
 RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER
 SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION
 (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE
 LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY
 WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY
 TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND
 THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE
 PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE
 MEASURES.
 (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND
 DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS
 INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
 (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD
 AND INTERIOR FIRE PROTECTION COMPONENTS.
 (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE
 MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL
 DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING
 APPROVAL AND DOCUMENTATION.
 (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE
 INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE
 OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL
 ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE
 CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED
 4-2-2000, 6-26-01, 7-12-05
  
 PLEASE PROVIDE THE REQUIRED DOCUMENTS WITH THIS PERMIT
 EITHER IN DRAWING OR NARRATIVE FORM SIGNED AND SEALED
 BY A QUALIFIED ENGINEER.
  
 SHOP DRAWING CAN THEN BE SUBMITTED SEPARATELY AT A
 LATER DATE BASED ON THE 61G DOCUMENTS.
  
  
  
  
 2) SHEET A 2 - THERE ARE INDICATIONS OF FIRE ALARM
 EQUIPMENT. ANY FIRE ALARM WORK SHALL BE DONE UNDER
 SEPARATE SHOP DRAWING BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-03-14 Cont ID  
Sent By gjohnson Date 2018-03-14 Time 07:09 Rev Time 0.00
Received By gjohnson Date 2018-02-12 Time 14:33 Sent To  
Notes
2018-02-13 14:33:17B21

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-17 Cont ID  
Sent By gjohnson Date 2017-11-17 Time 17:09 Rev Time 0.00
Received By gjohnson Date 2017-11-02 Time 09:23 Sent To  
Notes
2017-11-07 09:23:52B04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-13 Cont ID  
Sent By skennedy Date 2017-09-13 Time 10:03 Rev Time 0.00
Received By skennedy Date 2017-08-29 Time 10:48 Sent To  
Notes
2017-08-29 10:48:48B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-25 Cont ID  
Sent By skennedy Date 2017-08-25 Time 08:33 Rev Time 0.00
Received By skennedy Date 2017-08-21 Time 09:34 Sent To  
Notes
2017-08-25 08:34:17ADVISED APPLICANT TO PAY REVIEW FEES AND TO EXPLAIN
 STATUS OF OTHER EXPIRED PERMITS AT SAME LOCATION.
2017-08-23 09:34:55B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-08-25 Cont ID  
Sent By jwitmer Date 2017-08-25 Time 06:34 Rev Time 0.00
Received By jwitmer Date 2017-08-25 Time 06:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-05 Cont ID  
Sent By ccole Date 2018-03-05 Time 17:18 Rev Time 0.00
Received By ccole Date 2018-03-05 Time 17:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-11-13 Cont ID  
Sent By ccole Date 2017-11-13 Time 13:36 Rev Time 0.00
Received By ccole Date 2017-11-13 Time 13:13 Sent To  
Notes
2017-11-13 13:38:51MECHANICAL PROVISO:
  
 MANUFACTURER'S SPECIFICATIONS FOR THE COOKTOP, OVEN,
 AND EXHAUST HOOD SHALL BE ONSITE AT TIME OF INSPECTION.
 CCOLE-11/13/17

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-14 Cont ID  
Sent By gjohnson Date 2018-03-14 Time 07:08 Rev Time 0.00
Received By gjohnson Date 2018-03-14 Time 06:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By gjohnson Date 2017-11-17 Time 16:32 Rev Time 0.00
Received By gjohnson Date 2017-11-17 Time 10:47 Sent To  
Notes
2017-11-17 17:09:221ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH THE WATER CLOSET SHALL BE
 POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO
 ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION. PER FBC ACC 604.2
  
 2. THE GRAB BARS SHALL BE MEASURE FROM FINISHED FLOOR
 TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 3. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. FBC ACC 604.7
  
 4. THE LOUNGE SINK SHALL COMPY WITH FBC ACC 606.2 CLEAR
 FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5. A GREASE TRAP IS REQUIRED ON KITCHEN SINK ONLY. PER
 FBC PL 1003.3.1
  
 6. WHERE FOOD WASTE GRINDERS CONNECT TO GREASE
 INTERCEPTORS, A SOLIDS INTERCEPTOR SHALL SEPARATE THE
 DISCHARGE BEFORE CONNECTING TO THE GREASE INTERCEPTOR.
 SOLIDS INTERCEPTORS AND GREASE INTERCEPTORS SHALL BE
 SIZED AND RATED FOR THE DISCHARGE OF THE FOOD WASTE
 GRINDER. EMULSIFIERS, CHEMICALS, ENZYMES AND BACTERIA
 SHALL NOT DISCHARGE INTO THE FOOD WASTE GRINDER. PER
 FBC PL 1003.3.2
  
 7. ON SHT A-4 THE SANITARY AND WATER RISER DIAGRAMS ARE
 LABELED INCORRECTLY PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 8. BRANCH DRAIN FROM KITCHEN SHALL CONNECT TO BUILDING
 DRAIN DOWN STREAM OF BATHROOM GROUP. PER FBC PL 912.1
  
 9. HORIZONTAL DRY VENTS ARE PROHIBITED THE WENTS ON THE
 MOP SINK AND MENS WC SHALL COMPLY WITH FBC PL 905.3,
 905.4
  
 10. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 11. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE
 TANKLESS HEATER AND THE GREASE TRAP. PER WPB AMEND TO
 FBC 107.2.1
  
 12. PLEASE PROVIDE SIZING CALCULATIONS FOR GREASE TRAP.
 PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-02-22 Cont ID  
Sent By eschneid Date 2018-02-22 Time 15:24 Rev Time 0.25
Received By eschneid Date 2018-02-22 Time 15:10 Sent To  
Notes
2018-02-22 15:25:09PASSED W/PROVISO
  
 THE PAVING PERMIT NO. 17050422 AND LANDSCAPE PERMIT NO.
 17071228 MUST BE APPROVED, INSTALLED AND PASS
 INSPECTIONS PRIOR TO THE FINAL (104) INSPECTION FOR
 THIS PERMIT (NO. 17080987).
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By eschneid Date 2017-11-14 Time 13:40 Rev Time 0.25
Received By eschneid Date 2017-11-14 Time 10:53 Sent To  
Notes
2017-11-14 14:28:52PASSED W/PROVISO
  
 THE PAVING PERMIT NO. 17050422 AND LANDSCAPE PERMIT NO.
 17071228 MUST BE APPROVED, INSTALLED AND PASS
 INSPECTIONS PRIOR TO THE FINAL (104) INSPECTION FOR
 THIS PERMIT (NO. 17080987).
  
  