Plan Review Details - Permit 17080980
Plan Review Stops For Permit 17080980
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-13 Cont ID  
Sent By cthroop Date 2017-10-13 Time 14:24 Rev Time 0.00
Received By cthroop Date 2017-10-13 Time 14:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-14 Cont ID  
Sent By aclange Date 2017-09-14 Time 14:26 Rev Time 0.00
Received By aclange Date 2017-10-02 Time 08:37 Sent To  
Notes
2017-09-14 14:27:00****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 1. BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 2. PROVIDE PRODUCT APPROVALS FOR DOORS A AND B. PROVIDE
 PRODUCT APPROVAL FOR THE ROOFING PRODUCTS USED.
 FBC 107.3.4 , FBC 107.1 - PROVIDE PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD. SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 3. ROOFING PERMIT REQUIRED. FBC 105.1 PROVIDE ROOF
 SLOPE AND CONFIRM AREAS TO BE RE ROOFED. IT APPEARS
 THAT THE SCOPE OF WORK ON THE PERMIT APPLICATION HAS
 CHANGE.
  
 4. REVISE PERMIT VALUE TO INCLUDE ALL MATERIALS AND
 LABOR.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-12 Cont ID  
Sent By jpearson Date 2017-10-12 Time 15:04 Rev Time 0.00
Received By jpearson Date 2017-10-12 Time 15:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-09-14 Cont ID  
Sent By jpearson Date 2017-09-14 Time 08:13 Rev Time 0.00
Received By jpearson Date 2017-09-14 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-13 Cont ID  
Sent By cthroop Date 2017-10-13 Time 14:24 Rev Time 0.00
Received By cthroop Date 2017-10-10 Time 15:47 Sent To  
Notes
2017-10-11 15:47:32RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-02 Cont ID  
Sent By aclange Date 2017-10-02 Time 08:45 Rev Time 0.00
Received By aclange Date 2017-08-21 Time 09:38 Sent To  
Notes
2017-08-23 09:38:26R19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-10-24 Cont ID  
Sent By cthroop Date 2017-10-24 Time 10:42 Rev Time 0.00
Received By cthroop Date 2017-10-24 Time 10:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-10-13 Cont ID  
Sent By cthroop Date 2017-10-13 Time 14:24 Rev Time 0.00
Received By cthroop Date 2017-10-13 Time 14:08 Sent To  
Notes
2017-10-13 14:25:23BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-09-19 Cont ID  
Sent By hmoser Date 2017-09-19 Time 14:24 Rev Time 0.00
Received By hmoser Date 2017-09-19 Time 14:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-13 Cont ID  
Sent By lcrespo Date 2017-10-13 Time 14:16 Rev Time 0.00
Received By lcrespo Date 2017-10-12 Time 15:37 Sent To  
Notes
2017-10-12 15:38:1810/12/17 APPROVED PLUMBING OF RESUMITTAL, LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By thunt Date 2017-09-15 Time 14:57 Rev Time 0.00
Received By thunt Date 2017-09-14 Time 15:23 Sent To  
Notes
2017-09-15 14:58:329/15/17 PLUMBING 1ST REVIEW DENIED
  
 1) VALUE OF JOB COST SEEMS LOW AND LOOKS TO HAVE BEEN
 MODIFIED AFTER THE OWNER AND CONTRACTOR SIGNED. PROVIDE
 A BONA FIDE SIGNED CONTRACT SHOWING AMOUNT FBC 109.3
  
 2) CITY RECORDS DOES NOT INDICATE A PERMIT BEING ISSUED
 FOR REPLACEMENT OF ANY WATER HEATERS OR TANKLESS WATER
 HEATERS INCLUDING THE REQUIRED ELECTRIC FOR ONE AS
 WELL. EXISTING TANKLESS IS UNDERSIZED AND WITH THE HEAT
 RAISED BASED ON 32 DEGREES INCREASE TO GET HOT WATER OF
 111 DEGREES REQUIRED IT WOULD NOT COMPLY WITH 607.1 AND
 604.3 FBC-PLUMBING . PLEASE INCLUDE A CORRECTLY SIZED
 WATER HEATER IN YOUR PLANS REVISE P-1 ELECTRIC WATER
 HEATER SCHEDULE TO SHOW CORRECT INFORMATION. AS YOU CAN
 SEE FROM THE CHART BELOW A 32 DEGREE HEAT RAISE WOULD
 GET YOU 111 DEGREE WATER WHICH WILL GIVE YOU ENOUGH HOT
 WATER FOR 1 FIXTURE ONLY.
  
 TITAN N-120 TEMPERATURE RISE CHART (? FAHRENHEIT) ABOVE
 YOUR AMBIENT TEMPERATURE
 FLOW RATE 1.0 GPM 1.5 GPM 2.0 GPM 2.5 GPM 3.0 GPM 3.5
 GPM 4.0 GPM
 TEMP RISE 81? 54? 40? 32? 27? 23? 20?
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-09-13 Cont ID  
Sent By njwira Date 2017-09-13 Time 16:05 Rev Time 0.00
Received By njwira Date 2017-08-31 Time 15:43 Sent To  
Notes
***NONE***