| 2017-08-23 07:45:40 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17080859 |
| | ADD: 1801 S. FLAGLER DR. FLOOR/ SUITE: UNKNOWN |
| | CONT: PHILIP E. JOHNSON |
| | TEL: 561-366-1034 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED./ AUGUST 23/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT NOR THE PLANS PROVIDE THE LOCATION , ON |
| | WHAT FLOOR THIS WORK IS TO OCCUR. THIS IS A HIGH-RISE |
| | BUILDING! |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2 CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED. |
| | |
| | 2) THE DESIGNER OF RECORD NEEDS TO PROVIDE TO WHICH |
| | DESIGN METHOD WAS USED IN DESIGNING THE PLANS. 2014 |
| | FBC-EXISTING BUILDING CODE SECTION 301.1 GENERAL. |
| | THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION |
| | OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY |
| | WITH ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 |
| | THROUGH 301.1.3 AS SELECTED BY THE APPLICANT. |
| | |
| | 3) SHEET A1.01 THE DEMO NOTE # 4 INDICATES THE REMOVAL |
| | OF THE FINISH FLOOR IN THE ATHLETIC ROOM. THE FINISH |
| | FLOOR SCHEDULE INDICATES THE FINISH FLOOR TO BE ECORE |
| | COMMERCIAL/ECO FIR RUBBER FLOORING/ GRANITE RUN 905. |
| | THE PLANS DO NOT PROVIDE WHAT FLOOR THE WORK IS TO |
| | OCCUR. WHEN FLOORING IS ABOVE THE 1ST FLOOR THE CODE |
| | REQUIRES COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND |
| | AND 1207.3 STRUCTURE-BORNE SOUND. PLEASE PROVIDE THE |
| | MANUFACTURERS SPECIFICATIONS FOR THIS PRODUCT. |
| | IT WOULD APPEAR SINCE THIS IS A FINISH FLOOR MATERIAL |
| | THE FLOOR CLASSIFICATION NEEDS TO BE ESTABLISHED TO BE |
| | EITHER A CLASS I OR II MATERIALS AND SHALL BE |
| | CLASSIFIED IN ACCORDANCE WITH NFPA 253. |
| | |
| | 804.3 TESTING AND IDENTIFICATION. INTERIOR FLOOR FINISH |
| | AND FLOOR COVERING MATERIALS SHALL BE TESTED BY AN |
| | AGENCY IN ACCORDANCE WITH NFPA 253 AND IDENTIFIED BY A |
| | HANG TAG OR OTHER SUITABLE METHOD SO AS TO IDENTIFY THE |
| | MANUFACTURER OR SUPPLIER AND STYLE, AND SHALL INDICATE |
| | THE INTERIOR FLOOR FINISH OR FLOOR COVERING |
| | CLASSIFICATION ACCORDING TO SECTION 804.2. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |