2017-08-23 07:23:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE
 ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS
 AND DOCUMENTS. THE SIGNATURE ON THE DRAWINGS IS NOT AN
 ORIGINAL HANDWRITTEN SIGNATURE.
  
 2) THE GENERAC MODELS G007043-0 OR G007042-0 THAT WERE
 INDICATED FROM THE MANUFACTURER'S SPECIFICATIONS ARE
 NOT LISTED FOR USE WITH THE GENERATOR PAD DOCUMENTS
 THAT WERE SUBMITTED. PLEASE SUBMIT THE CORRESPONDING
 DOCUMENTS. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-09-22 Cont ID  
Sent By jleahy Date 2017-08-23 Time 14:28 Rev Time 0.00
Received By jleahy Date 2017-08-23 Time 14:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-10-06 Cont ID  
Sent By thunt Date 2017-10-06 Time 13:55 Rev Time 0.00
Received By thunt Date 2017-10-06 Time 13:55 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-08-24 Cont ID  
Sent By thunt Date 2017-08-24 Time 07:11 Rev Time 0.00
Received By thunt Date 2017-08-24 Time 06:34 Sent To  
Notes
2017-08-24 07:11:391ST REVIEW OF GAS*DENIED
  
 1) ENGINEER OF RECORD LICENSE IS REVOKED AS OF
 2/28/2017 PER MYFLORIDA.COM
  
 2) SIGNATURES ARE REQUIRED TO BE WET
  
 3) LINE 7 OF PROPOSAL LIST CONNECTION OF NAT GAS GRILL
 INCLUDED NOT NOT SHOWN ON DRAWING/ PLAN
  
 4) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 5) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1
 6) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413
  
 7) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 8) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1
  
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-08-18 Cont ID  
Sent By destabro Date 2017-08-18 Time 13:47 Rev Time 0.00
Received By destabro Date 2017-08-18 Time 13:47 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-06 Cont ID  
Sent By cpuell Date 2017-10-06 Time 14:43 Rev Time 0.00
Received By cpuell Date 2017-10-03 Time 13:13 Sent To  
Notes
2017-10-04 13:13:57RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-24 Cont ID  
Sent By thunt Date 2017-08-24 Time 07:11 Rev Time 0.00
Received By thunt Date 2017-08-15 Time 16:12 Sent To  
Notes
2017-08-16 16:12:43ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-10-05 Cont ID  
Sent By njwira Date 2017-10-05 Time 14:23 Rev Time 0.00
Received By njwira Date 2017-10-04 Time 16:58 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-18 Cont ID  
Sent By njwira Date 2017-08-18 Time 13:12 Rev Time 0.00
Received By njwira Date 2017-08-17 Time 16:12 Sent To HIST
Notes
2017-08-18 13:14:008/18/17- FAILED
  
 94-305(B)4- MECHANICAL EQUIPMENT PROJECTS MORE THAN
 4FT. INTO 10FT. MINIMUM 20FT. TOTAL SIDE SETBACK.
 94-305(B)4- MECHANICAL EQUIPMENT DOESN'T MEET 10FT.
 REAR SETBACK
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved