Plan Review Details - Permit 17080743
Plan Review Stops For Permit 17080743
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2018-10-31 Cont ID  
Sent By dbattles Date 2018-10-31 Time 11:24 Rev Time 0.00
Received By dbattles Date 2018-10-31 Time 11:24 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2018-08-16 Cont ID  
Sent By dbattles Date 2018-08-16 Time 10:05 Rev Time 0.00
Received By dbattles Date 2018-08-10 Time 15:13 Sent To  
Notes
2018-08-16 10:10:59****CORRECTIONS****
 W.P.B. PERMIT: 17080743
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 5TH REVIEW: FBC FIFTH EDITION (2014)
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) PARTICAL COMPLIANCE. EXPLAIN WHAT THE "INSIDE
 BITUMEN FOAM" MEANS ON SHEET A3.0. ON SHEET A3.0 THE
 ROOFING MATERIAL IS SPECIFIED AS ASPHALT TILE ROOF ON A
 90# HOT MOPPED TO A 30# BASE SHEET. PLEASE CLARIFY. FBC
 107.2.1 WILL ASPHALT SHINGLES OR CONCRETE ROOF TILE BE
 INSTALLED? HOT MOPPED 90# IS NOT USED AS AN
 UNDERLAYMENT FOR ASPHALT SHINGLES.
 PATIALLY ADDRESSED-WHAT IS THE BITUMEN FOAM FOR? IF
 ATTACHMENT THAN PRODUCT APPROVAL NEEDED.
 THE NAILS SHOULD BE AS FOLLOWS:
 FBC R803.2.3.1]SHEATHING FASTENING.
 SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113)
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 NEW COMMENTS:
  
 13) SEE #3
  
 14) COMPLIED.
  
 NEW COMMENTS 8/15/18:
  
 15. [FBC EXISTING 807.2]WHAT ARE THE NEW TRUSSES
 BEARING ON? PROVIDE ENGINEERING THAT THE EXISTING WALLS
 CAN BEAR THE NEW TRUSSES AND ROOF. TRUSSES APPEAR TO BE
 HANGING FROM EXISTING AT LAUNDY ROOM WALL. IS THAT THE
 CASE AND HOW CAN EXISTING SUPPORT THE NEW LOADS?
  
 16. [FBC EXISTING 807.2]WHERE REMOVING EXTERIOR WALL IT
 APPEARS THAT AN 8? X 8? BEAM IS LEFT BEHIND TO BEAR THE
 EXISTING AND THE NEW TRUSSES. PROVIDE ENGINEERING TO
 SHOW THAT BEAM WOULD BE SUFFICIENT TO SUPPORT ALL
 LOADS.
 I SEE THAT YOU END THE ADDITION EVEN WITH THE LAUNDRY.
 CONSIDER PUSHING THE ADDITION BACK A COUPLE OF FEET SO
 THAT THE EXISTING EXTERIOR WALL CAN REMAIN WITHOUT LOSS
 OF NEW BEDROOM SIZE.
  
 17. [FBC R802.11]SHOW CONNECTOR FOR EACH TRUSS.
  
 18. [FBC 2319.17.2.4.4]WHAT IS THE GABLE END MATERIAL.
 PROVIDE DETAIL OF GABLE END AND HOW ID TRANSITIONS TO
 THE BEAM.
  
 19. PLEASE SHOW SKLIGHTS ON ROOFING PLAN FOR NUMBER OF
 SKYLIGHTS AND LOCATION.
  
 20. [FBC ENERGY R401.2]THE PERMIT HA TWO ENERGY CALCS
 ATTACHED. ONE IS PERFORMANCE AND ONE IS ENVELOPE. BASED
 ON DATE IT LOOKS LIKE THE ENERGY CALCS BASED ON
 PERFORMANCE IS THE CURRENT. IF SO, THERE ARE SOME
 ERRORS ON THE REPORT.
 OWNER, DESIGN LOCATION, BUILDER NAME, CLIMATE, ROOF,
 ATTIC AND SKYLIGHTS NEED TO BE ADDED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-07-11 Cont ID  
Sent By rmcdouga Date 2018-07-11 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2018-07-10 Time 16:38 Sent To I
Notes
2018-07-11 11:44:16PLAN
 REVIEW COMMENTS
  
 4TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) PARTIAL COMPLIANCE. EXPLAIN WHAT THE "INSIDE BITUMEN
 FOAM" MEANS ON SHEET A3.0. ON SHEET A3.0 THE ROOFING
 MATERIAL IS SPECIFIED AS ASPHALT TILE ROOF ON A 90# HOT
 MOPPED TO A 30# BASE SHEET. PLEASE CLARIFY. FBC 107.2.1
 WILL ASPHALT SHINGLES OR CONCRETE ROOF TILE BE
 INSTALLED? HOT MOPPED 90# IS NOT USED AS AN
 UNDERLAYMENT FOR ASPHALT SHINGLES.
  
 4) COMPLIED.
  
 5) PARTIAL COMPLIANCE. STILL NEED THE PRODUCT APPROVALS
 FOR THE SKYLIGHT AND THE ROOF COVERING MATERIAL. FBC
 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001
 PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA
 NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM
 DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING
 MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL MULLIONS,
 SKYLIGHTS AND EXTERIOR DOOR TYPES.
  
 6) COMPLIED.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 NEW COMMENTS:
  
 13) ON SHEET A3.0, THE REVISED NOTES SPECIFY 10D NAILS
 FOR THE ROOF SHEATHING AND THE PREVIOUS NOTE SPECIFIES
 8D RING SHANK NAILS. SPECIFY ONE OR THE OTHER. FBC
 107.2.1
  
 14) THE WINDOW AND DOOR SCHEDULE AND PRESSURES ON SHEET
 A4.0 HAVE NUMEROUS ERRORS. THIS PROJECT IS LOCATED IN
 EXPOSURE "C" WITH A 170MPH VULT WINDSPEED. THE ROUGH
 OPENING SIZES FOR THE WINDOWS AND SLIDING GLASS DOOR
 ARE INCORRECT. THE ROUGH OPENINGS SHOULD BE LARGER THAN
 THE WINDOW AND DOOR SIZES. THE REQUIRED PRESSURES FOR
 THE SLIDING GLASS DOOR SHOULD BE +33.9, -42.8 PSF. THE
 SIZE OF THE DOOR IN THE SCHEDULE DOES NOT MATCH THE
 ELEVATIONS. THE REQUIRED PRESSURES FOR THE WINDOWS
 SHOULD BE +37.9, -50.7 PSF FOR WALL ZONE 5 AND +37.9,
 -41.1 PSF FOR WALL ZONE 4. LOOK IN THE PRODUCT APPROVAL
 NOAS FOR THE APPROVED DESIGN PRESSURES FOR THE WINDOWS
 AND DOOR. THE OLD OUTDATED NOA NUMBERS WERE NOT REMOVED
 FROM THE SCHEDULES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-05-18 Cont ID  
Sent By rmcdouga Date 2018-05-18 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2018-05-16 Time 07:07 Sent To  
Notes
2018-05-18 09:07:53PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) ON SHEET A3.0 THE ROOFING MATERIAL IS SPECIFIED AS
 ASPHALT TILE ROOF ON A 90# HOT MOPPED TO A 30# BASE
 SHEET. PLEASE CLARIFY. FBC 107.2.1 WILL ASPHALT
 SHINGLES OR CONCRETE ROOF TILE BE INSTALLED? HOT MOPPED
 90# IS NOT USED AS AN UNDERLAYMENT FOR ASPHALT
 SHINGLES.
  
 4) THE PRODUCT APPROVAL NUMBERS THAT ARE SPECIFIED ON
 THE PLANS FOR THE WINDOWS IN THE SCHEDULE ON SHEET A4.0
 AND THE TRUSS CONNECTORS ON SHEET S2.0 ARE EXPIRED.
 PLEASE REMOVE FROM PLANS OR UPDATE THEM.
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL
 MULLIONS, SKYLIGHTS AND EXTERIOR DOOR TYPES.
  
 6) COMPLIED.
  
 10) COMPLIED.
  
 11) THE VALUATION LISTED ON THE PERMIT APPLICATION OF
 $12,000.00 IS LOW. PLEASE PROVIDE AN ADEQUATE VALUATION
 BASED ON FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. SUBMIT
 A COPY OF THE SIGNED CONTRACT FOR THIS PROJECT.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 13) NEW COMMENT: A PRODUCT APPROVAL WAS SUBMITTED FOR A
 SR PRODUCTS BUILT-UP ROOF SYSTEM OVER RECOVER DECKS.
 THIS PRODUCT WILL NOT WORK FOR THIS PROJECT. THIS IS
 FOR A ROOF OVER OR A RECOVER. THE MAXIMUM DESIGN
 PRESSURES ARE -45 PSF WHICH ARE TOO LOW AND LIMITATION
 #9 DOES NOT ALLOW THE PRESSURES TO BE INCREASED USING
 RATIONAL ANALYSIS OR EXTRAPOLATION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-29 Cont ID  
Sent By rmcdouga Date 2018-03-29 Time 17:42 Rev Time 0.00
Received By rmcdouga Date 2018-03-26 Time 18:33 Sent To I
Notes
2018-03-29 16:57:04PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THESE PLANS ARE NOT BASED ON THE CURRENT 2014
 FLORIDA BUILDING CODE AND THE CURRENT EDITIONS OF THE
 STANDARDS THAT ARE REFERENCED BY THE 2014 FBC. PLEASE
 UPDATE THE PLANS TO THE 2014 FBC, THE 2014 FLORIDA FIRE
 PREVENTION CODE, AND THE 2012 EDITION OF NFPA 1 AND
 101. THERE ARE STILL SOME CORRECTIONS THAT WERE MISSED.
 SEE SHEET 1 OF 10 AND SHEET A1.0.
  
 2) REVISE THE CODE SECTIONS THAT ARE SPECIFIED ON THE
 PLANS TO CORRESPOND WITH THE APPROPRIATE SECTIONS IN
 THE 2014 FBC. ON SHEET 1 OF 10, SECTION 504 AND 504.1
 OF THE 2014 FBC EXISTING BUILDING ARE THE SECTIONS FOR
 LEVEL 2 ALTERATIONS.
  
 3) ON SHEET A3.0 THE ROOFING MATERIAL IS SPECIFIED AS
 ASPHALT TILE ROOF ON A 90# HOT MOPPED TO A 30# BASE
 SHEET. PLEASE CLARIFY. FBC 107.2.1 WILL ASPHALT
 SHINGLES OR CONCRETE ROOF TILE BE INSTALLED? HOT MOPPED
 90# IS NOT USED AS AN UNDERLAYMENT FOR ASPHALT
 SHINGLES.
  
 4) THE PRODUCT APPROVAL NUMBERS THAT ARE SPECIFIED ON
 THE PLANS FOR THE WINDOWS IN THE SCHEDULE ON SHEET A4.0
 AND THE TRUSS CONNECTORS ON SHEET S2.0 ARE EXPIRED.
 PLEASE UPDATE.
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL
 MULLIONS, SKYLIGHTS AND EXTERIOR DOOR TYPES.
  
 6) ON SHEET S1.0, UNDER GENERAL STRUCTURAL NOTES THE
 WINDSPEED IS INCORRECT AND THE EDITIONS OF ACI 318 AND
 ASCE 7 ARE INCORRECT. THE 2014 FBC REFERENCES ACI 318 -
 11 AND ASCE 7 - 10. PLEASE CORRECT FBC-R CHAPTER 46.
  
 10) THE WF12 MONOLITHIC FOUNDATION THAT IS SPECIFIED ON
 SHEET S1.0 FOR THE NEW ADDITION IS NOT ADEQUATE FOR THE
 EXTERIOR CBS WALL CONSTRUCTION. THERE IS ONLY ONE #5
 CONTINUOUS RE-BAR SPECIFIED. THE FOOTER WILL HAVE TO BE
 A MINIMUM OF 16" THICK. FBC-R404.1.6 HEIGHT ABOVE
 FINISHED GRADE. CONCRETE AND MASONRY FOUNDATION WALLS
 SHALL EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES
 (152 MM) ELSEWHERE. R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. THE
 EXTERIOR FOOTINGS THAT WILL SUPPORT THE NEW EXTERIOR
 CBS WALLS SHOULD BE LABELED DIFFERENTLY FROM THE 12" X
 12" THICKENED EDGE THAT IS AGAINST THE EXISTING
 FOUNDATION WHERE THE DOWELS WILL BE INSTALLED. PROVIDE
 A SECTION FOR EACH OF THE DIFFERENT FOUNDATION TYPES.
  
 11) THE VALUATION LISTED ON THE PERMIT APPLICATION OF
 $12,000.00 IS LOW. PLEASE PROVIDE AN ADEQUATE VALUATION
 BASED ON FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-18 Cont ID  
Sent By rmcdouga Date 2017-09-18 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2017-09-15 Time 09:59 Sent To  
Notes
2017-09-15 16:52:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THESE PLANS ARE NOT BASED ON THE CURRENT 2014
 FLORIDA BUILDING CODE AND THE CURRENT EDITIONS OF THE
 STANDARDS THAT ARE REFERENCED BY THE 2014 FBC. PLEASE
 UPDATE THE PLANS TO THE 2014 FBC, THE 2014 FLORIDA FIRE
 PREVENTION CODE, AND THE 2012 EDITION OF NFPA 1 AND
 101.
  
 2) REVISE THE CODE SECTIONS THAT ARE SPECIFIED ON THE
 PLANS TO CORRESPOND WITH THE APPROPRIATE SECTIONS IN
 THE 2014 FBC. FOR EXAMPLE ON SHEET 1 OF 10, SECTION 505
 IS THE CURRENT ONE FOR LEVEL 3 ALTERATIONS.
  
 3) ON SHEET 1, THIS PROJECT IS SPECIFIED AS A LEVEL 3
 ALTERATION AND A LEVEL 2 ALTERATION. REFER TO THE 2014
 FBC- EXISTING BUILDING AND SELECT THE APPROPRIATE LEVEL
 OF ALTERATION AND SPECIFY IT ON THE PLANS.
  
 4) SPECIFY THE ROOF SLOPE ON THE PLANS. FBC 107.2.1 &
 R301.1
  
 5) THE NEW SKYLIGHT #4 AND ITEM #5 ON SHEET A1.0 ARE
 NOT IDENTIFIED IN THE SCHEDULE ON SHEET A4.0. PLEASE
 CLARIFY. FBC 107.2.1
  
 6) ON SHEET A3.0 THE ROOFING MATERIAL IS SPECIFIED AS
 ASPHALT TILE ROOF ON A 90# HOT MOPPED TO A 30# BASE
 SHEET. PLEASE CLARIFY. FBC 107.2.1
  
 7) THE PRODUCT APPROVALS THAT ARE SPECIFIED ON THE
 PLANS FOR THE WINDOWS, DOORS, TRUSS HANGERS AND
 CONNECTORS ARE ALL EXPIRED. PLEASE UPDATE.
  
 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL
 MULLIONS, SKYLIGHTS AND EXTERIOR DOOR TYPES.
  
 9) ON SHEET S1.0, UNDER GENERAL STRUCTURAL NOTES THE
 WINDSPEED IS INCORRECT AND THE EDITIONS OF ACI 318 AND
 ASCE 7 ARE INCORRECT. THE 2014 FBC REFERENCES ACI 318 -
 11 AND ASCE 7 - 10. PLEASE CORRECT FBC-R CHAPTER 46.
  
 10) THE W12 MONOLITHIC FOUNDATION THAT IS SPECIFIED ON
 SHEET S1.0 FOR THE NEW ADDITION IS NOT ADEQUATE FOR THE
 EXTERIOR CBS WALL CONSTRUCTION. THERE IS ONLY ONE #5
 CONTINUOUS RE-BAR SPECIFIED. THE FOOTER WILL HAVE TO BE
 A MINIMUM OF 16" THICK. FBC-R404.1.6 HEIGHT ABOVE
 FINISHED GRADE. CONCRETE AND MASONRY FOUNDATION WALLS
 SHALL EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES
 (152 MM) ELSEWHERE. R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 11) THE VALUATION LISTED ON THE PERMIT APPLICATION OF
 $12,000.00 IS LOW. PLEASE PROVIDE AN ADEQUATE VALUATION
 BASED ON FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-19 Cont ID  
Sent By jpearson Date 2018-03-19 Time 16:19 Rev Time 0.00
Received By jpearson Date 2018-03-19 Time 12:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-07 Cont ID  
Sent By jpearson Date 2017-09-07 Time 09:59 Rev Time 0.00
Received By jpearson Date 2017-09-07 Time 09:59 Sent To  
Notes
2017-09-07 09:59:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION PER CODE.
 SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING
 OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3,
 FBC 107.2.1
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2018-12-05 Cont ID  
Sent By fmittner Date 2018-12-05 Time 11:43 Rev Time 0.00
Received By fmittner Date 2018-12-05 Time 11:42 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2018-05-15 Cont ID  
Sent By rmcdouga Date 2018-05-18 Time 10:29 Rev Time 0.00
Received By fmittner Date 2018-05-15 Time 13:31 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2018-03-07 Cont ID  
Sent By fmittner Date 2018-03-07 Time 13:47 Rev Time 0.00
Received By fmittner Date 2018-02-28 Time 08:18 Sent To  
Notes
2018-03-07 13:48:20COMMENTS FROM FIRST REVIEW NOT ADDRESSED. COA NOT
 SUBMITTED.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-08-25 Cont ID  
Sent By fmittner Date 2017-08-25 Time 10:50 Rev Time 0.00
Received By fmittner Date 2017-08-25 Time 10:50 Sent To  
Notes
2017-08-25 10:51:09PROPERTY IN HISTORIC DISTRICT, REQUIRES SUBMITTAL OF
 COA.
  
 QUESTIONS, CONTACT FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER AT (561) 822-1457

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2018-12-07 Cont ID  
Sent By rmcdouga Date 2018-12-07 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2018-12-05 Time 10:07 Sent To  
Notes
2018-12-07 10:07:39RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-12-07 Cont ID  
Sent By lmarchan Date 2018-12-07 Time 10:05 Rev Time 0.00
Received By lmarchan Date 2018-10-26 Time 11:06 Sent To  
Notes
2018-10-30 11:07:02RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-08-16 Cont ID  
Sent By rmcdouga Date 2018-08-16 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2018-08-03 Time 10:55 Sent To  
Notes
2018-08-07 10:55:20RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-11 Cont ID  
Sent By rmcdouga Date 2018-07-11 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2018-07-03 Time 15:27 Sent To  
Notes
2018-07-05 15:27:11RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-18 Cont ID  
Sent By rmcdouga Date 2018-05-18 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2018-05-03 Time 10:39 Sent To HIST
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-29 Cont ID  
Sent By rmcdouga Date 2018-03-29 Time 17:43 Rev Time 0.00
Received By rmcdouga Date 2018-02-23 Time 13:27 Sent To  
Notes
2018-02-26 13:27:40R13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-18 Cont ID  
Sent By rmcdouga Date 2017-09-18 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2017-08-15 Time 11:18 Sent To  
Notes
2017-08-17 11:18:25R05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-05-17 Cont ID  
Sent By rmcdouga Date 2018-05-17 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2018-05-16 Time 07:07 Sent To  
Notes
2018-05-17 15:10:04MU-2018-14592, PAID $180.65

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By rmcdouga Date 2017-09-15 Time 09:58 Rev Time 0.00
Received By rmcdouga Date 2017-09-15 Time 09:58 Sent To  
Notes
2017-09-15 09:58:38BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2018-12-07 Cont ID  
Sent By rmcdouga Date 2018-12-07 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2018-12-07 Time 15:07 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2018-10-31 Cont ID  
Sent By rmcdouga Date 2018-10-31 Time 07:42 Rev Time 0.00
Received By rmcdouga Date 2018-10-31 Time 06:49 Sent To  
Notes
2018-10-31 07:42:55PLAN
 REVIEW COMMENTS
  
 6TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LOCATION OF THE MINI-SPLIT EQUIPMENT IS NOT
 SHOWN ON THE MECHANICAL PLANS. FBC 107.2.1
  
 2) THE 2017 EDITION OF FORM R405 WAS SUBMITTED. THIS
 PROJECT WAS APPLIED FOR UNDER THE 2014 FBC. SUBMIT THE
 FORMS AND CALCULATIONS FOR THE 2014 EDITION. PROVIDE
 HEATING AND COOLING EQUIPMENT SIZING CALCULATIONS FOR
 THE NEW ADDITION. FBCR-M1401.3
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2018-08-16 Cont ID  
Sent By rmcdouga Date 2018-08-16 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2018-08-16 Time 10:37 Sent To I
Notes
2018-08-16 10:48:06PLAN
 REVIEW COMMENTS
  
 5TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 1) SEE BUILDING REVIEW COMMENTS FOR ENERGY CODE
 COMPLIANCE.
  
 2) PROVIDE HEATING AND COOLING EQUIPMENT SIZING
 CALCULATIONSFOR THE NEW ADDITION. FBCR-M1401.3
  
 3) CLARIFY THAT THE PROPOSED MINI-SPLIT SYSTEM WILL
 PROVIDE THE REQUIRED HEATING FOR THE NEW ADDITION. FBC
 107.2.1

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-07-10 Cont ID  
Sent By rmcdouga Date 2018-07-10 Time 18:29 Rev Time 0.00
Received By rmcdouga Date 2018-07-10 Time 17:13 Sent To  
Notes
2018-07-10 17:36:57PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
 2) COMPLIED.
 3) COMPLIED.
 4) THE ATTIC VENT RATIO IS LISTED AS 300 SQFT ON THE
 ENERGY FORMS. FBC-R 806.2 THE MINIMUM NET FREE
 VENTILATION AREA SHALL BE 1/150 OF THE VENTED SPACE.
 THE EXCEPTION THAT ALLOWS THE 1/300 NET VENTILATION
 REQUIRES THAT AT LEAST 40 PERCENT AND NOT MORE THAN 50
 PERCENT OF THE REQUIRED VENTILATING AREA IS PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION OF THE ATTIC
 OR RAFTER SPACE. UPPER VENTILATORS SHALL BE LOCATED NO
 MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST
 POINT OF THE SPACE, MEASURED VERTICALLY, WITH THE
 BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR
 CORNICE VENTS. WHERE THE LOCATION OF WALL OR ROOF
 FRAMING MEMBERS CONFLICTS WITH THE INSTALLATION OF
 UPPER VENTILATORS, INSTALLATION MORE THAN 3 FEET (914
 MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE SHALL
 BE PERMITTED. THE PLANS DO NOT SHOW
 5) COMPLIED.
  
 NEW COMMENTS:
 THE ENERGY FORMS CONTAIN NUMEROUS ERRORS. SEE NEW
 COMMENTS BELOW.
 1) THE DESIGN LOCATION ON THE ENERGY FORMS IS LISTED AS
 ST LUCIE, THIS PROJECT IS LOCATED IN WEST PALM BEACH,
 FL. WHICH IS IN PALM BEACH COUNTY. ON PAGE 2, THE TMY
 SITE IS INCORRECTLY LISTED AS VERO BEACH.
  
 2) THE ROOF IS LISTED AS BARREL TILE INSTEAD OF ASPHALT
 SHINGLES.
  
 3) ON PAGE 1, THERE IS A WOOD FRAME EXTERIOR WALL
 LISTED AND ALL OF THE EXTERIOR WALLS OF THE ADDITION
 ARE CBS.
  
 4) LIST THE OWNER'S AND BUILDER'S NAMES IN THE AREA AT
 THE TOP OF PAGE 1.
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-05-18 Cont ID  
Sent By rmcdouga Date 2018-05-18 Time 09:50 Rev Time 0.00
Received By rmcdouga Date 2018-05-18 Time 09:50 Sent To  
Notes
2018-05-18 09:50:18PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) THIS PROJECT IS PERMITTED UNDER THE 2014 FBC. THE
 R405 ENERGY FORM THAT WAS SUBMITTED IS FOR THE 2017
 FBC. SUBMIT TWO SETS OF THE R405-2014 ENERGY FORMS.
  
 3) THE ENERGY FORMS R405-2014 ARE REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT. FBC ENERGY CONSERVATION SECTION
 R103.1.1.2.
  
 4) THE ATTIC VENT RATIO IS LISTED AS 300 SQFT ON THE
 ENERGY FORMS. FBC-R 806.2 THE MINIMUM NET FREE
 VENTILATION AREA SHALL BE 1/150 OF THE VENTED SPACE.
 THE EXCEPTION THAT ALLOWS THE 1/300 NET VENTILATION
 REQUIRES THAT AT LEAST 40 PERCENT AND NOT MORE THAN 50
 PERCENT OF THE REQUIRED VENTILATING AREA IS PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION OF THE ATTIC
 OR RAFTER SPACE. UPPER VENTILATORS SHALL BE LOCATED NO
 MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST
 POINT OF THE SPACE, MEASURED VERTICALLY, WITH THE
 BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR
 CORNICE VENTS. WHERE THE LOCATION OF WALL OR ROOF
 FRAMING MEMBERS CONFLICTS WITH THE INSTALLATION OF
 UPPER VENTILATORS, INSTALLATION MORE THAN 3 FEET (914
 MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE SHALL
 BE PERMITTED. THE PLANS DO NOT SHOW
  
 5) COMPLIED.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-29 Cont ID  
Sent By rmcdouga Date 2018-03-29 Time 13:55 Rev Time 0.00
Received By rmcdouga Date 2018-03-26 Time 18:34 Sent To  
Notes
2018-03-29 16:24:44PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. THE MANUAL
 J EQUIPMENT SIZING CALCULATIONS THAT WERE SUBMITTED
 SPECIFY A 12000 BTUH PTAC UNIT. SHOW IT'S LOCATION ON
 THE PLANS AND PROVIDE AN EQUIPMENT SCHEDULE FRO IT.
 NOTE: FBC-R 303.9 REQUIRES THE ADDITION TO BE HEATED.
  
 2) THIS PROJECT IS PERMITTED UNDER THE 2014 FBC. THE
 R405 ENERGY FORM THAT WAS SUBMITTED IS FOR THE 2017
 FBC. SUBMIT TWO SETS OF THE R405-2014 ENERGY FORMS.
  
 3) THE ENERGY FORMS R405-2014 ARE REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT. FBC ENERGY CONSERVATION SECTION
 R103.1.1.2.
  
 4) THE ATTIC VENT RATIO IS LISTED AS 300 SQFT ON THE
 ENERGY FORMS. FBC-R 806.2 THE MINIMUM NET FREE
 VENTILATION AREA SHALL BE 1/150 OF THE VENTED SPACE.
 THE EXCEPTION THAT ALLOWS THE 1/300 NET VENTILATION
 REQUIRES THAT AT LEAST 40 PERCENT AND NOT MORE THAN 50
 PERCENT OF THE REQUIRED VENTILATING AREA IS PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION OF THE ATTIC
 OR RAFTER SPACE. UPPER VENTILATORS SHALL BE LOCATED NO
 MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST
 POINT OF THE SPACE, MEASURED VERTICALLY, WITH THE
 BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR
 CORNICE VENTS. WHERE THE LOCATION OF WALL OR ROOF
 FRAMING MEMBERS CONFLICTS WITH THE INSTALLATION OF
 UPPER VENTILATORS, INSTALLATION MORE THAN 3 FEET (914
 MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE SHALL
 BE PERMITTED. THE PLANS DO NOT SHOW
  
 5) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By rmcdouga Date 2017-09-15 Time 16:33 Rev Time 0.00
Received By rmcdouga Date 2017-09-15 Time 16:00 Sent To  
Notes
2017-09-15 16:33:09PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15.
  
 2) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR
 R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE
 FORMS AS REQUIRED.
  
 3) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-20 Cont ID  
Sent By gjohnson Date 2018-03-20 Time 11:47 Rev Time 0.00
Received By gjohnson Date 2018-03-20 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-07 Cont ID  
Sent By thunt Date 2017-09-07 Time 14:43 Rev Time 0.00
Received By thunt Date 2017-09-07 Time 13:46 Sent To  
Notes
2017-09-07 14:48:419/7/17 1ST REVIEW PLUMBING DENIED
  
 1) PLANS LIST BUILDING CODE AS 2010. WE ARE CURRENTLY
 UNDER THE 2014 FIFTH EDITION FBC
  
 2) P1 SHOWS A 2 HANDLE SHOWER VALVE. FBC-PLB 424.3
 REQUIRES SHOWER VALVES TO BE PRESSURE BALANCED,
 THERMOSTATIC, OR A COMBINATION OF BOTH
  
 3) SHOWER COMPARTMENTS PER FBC-PLB REQUIRE A MIN OF 900
 SQ IN. PLEASE SHOW SHOWER DIMENSIONS
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2018-08-16 Cont ID  
Sent By dbattles Date 2018-08-16 Time 10:11 Rev Time 0.00
Received By dbattles Date 2018-08-16 Time 10:11 Sent To  
Notes
2018-08-16 10:13:03PRODUCT APPROVAL FOR SHINGLE OK.
 NAILING TO BE ADDRESSED IN BUILDING COMMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2018-07-10 Cont ID  
Sent By rmcdouga Date 2018-07-10 Time 18:50 Rev Time 0.00
Received By rmcdouga Date 2018-07-10 Time 18:50 Sent To  
Notes
2018-07-10 18:50:34NO ROOFING PRODUCT APPROVALS WERE SUBMITTED. ASPHALT
 SHINGLES ARE SPECIFIED ON THE PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2018-05-18 Cont ID  
Sent By rmcdouga Date 2018-05-18 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2018-05-17 Time 16:44 Sent To  
Notes
2018-05-18 10:30:36NO ACCEPTABLE PRODUCT APPROVALS WERE SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-03-29 Cont ID  
Sent By rmcdouga Date 2018-03-29 Time 17:43 Rev Time 0.00
Received By rmcdouga Date 2018-03-26 Time 18:34 Sent To  
Notes
2018-03-29 17:44:21NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-09-18 Cont ID  
Sent By rmcdouga Date 2017-09-18 Time 08:27 Rev Time 0.00
Received By rmcdouga Date 2017-09-18 Time 08:27 Sent To  
Notes
2017-09-18 08:28:10NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.

Review Stop Z ZONING
Rev No 4 Status P Date 2018-12-05 Cont ID  
Sent By fmittner Date 2018-12-05 Time 11:43 Rev Time 0.00
Received By fmittner Date 2018-12-05 Time 11:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-05-15 Cont ID  
Sent By fmittner Date 2018-05-15 Time 13:31 Rev Time 0.00
Received By fmittner Date 2018-05-15 Time 13:31 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-03-07 Cont ID  
Sent By fmittner Date 2018-03-07 Time 13:47 Rev Time 0.00
Received By fmittner Date 2018-03-07 Time 13:47 Sent To  
Notes
2018-03-07 13:47:39INITIAL COMMENTS OF SIDE SETBACK NOT ADDRESSED

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-18 Cont ID  
Sent By njwira Date 2017-08-18 Time 09:21 Rev Time 0.00
Received By njwira Date 2017-08-18 Time 09:21 Sent To  
Notes
2017-08-18 09:25:378/18/17- FAILED
  
 94-82(B)2(E)1- 6FT. 8IN. SIDE SETBACK HAS A CUMALATIVE
 SIDE SETBACK OF 12FT. 5IN. AND THIS SITE REQUIRES A
 15FT. CUMULATIVE SETBACK
 94-82(B)4-A- WHAT IS THE LOT COVERAGE?
 94-82(B)5-A- WHAT IS THE FLOOR TO AREA RATIO?
 94-449- NO TREES MAYBE MOVED WITHOUT A TREE ALTERATION
 PERMIT
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved