| Plan Review Stops For Permit 17080743 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2018-10-31 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-31 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-31 |
Time |
11:24 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-08-16 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-10 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2018-08-16 10:10:59 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 17080743 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 5TH REVIEW: FBC FIFTH EDITION (2014) | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) COMPLIED. | | | | | | 2) COMPLIED. | | | | | | 3) PARTICAL COMPLIANCE. EXPLAIN WHAT THE "INSIDE | | | BITUMEN FOAM" MEANS ON SHEET A3.0. ON SHEET A3.0 THE | | | ROOFING MATERIAL IS SPECIFIED AS ASPHALT TILE ROOF ON A | | | 90# HOT MOPPED TO A 30# BASE SHEET. PLEASE CLARIFY. FBC | | | 107.2.1 WILL ASPHALT SHINGLES OR CONCRETE ROOF TILE BE | | | INSTALLED? HOT MOPPED 90# IS NOT USED AS AN | | | UNDERLAYMENT FOR ASPHALT SHINGLES. | | | PATIALLY ADDRESSED-WHAT IS THE BITUMEN FOAM FOR? IF | | | ATTACHMENT THAN PRODUCT APPROVAL NEEDED. | | | THE NAILS SHOULD BE AS FOLLOWS: | | | FBC R803.2.3.1]SHEATHING FASTENING. | | | SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113) | | | | | | 4) COMPLIED. | | | | | | 5) COMPLIED. | | | | | | 6) COMPLIED. | | | | | | 10) COMPLIED. | | | | | | 11) COMPLIED. | | | | | | 12) COMPLIED. | | | | | | NEW COMMENTS: | | | | | | 13) SEE #3 | | | | | | 14) COMPLIED. | | | | | | NEW COMMENTS 8/15/18: | | | | | | 15. [FBC EXISTING 807.2]WHAT ARE THE NEW TRUSSES | | | BEARING ON? PROVIDE ENGINEERING THAT THE EXISTING WALLS | | | CAN BEAR THE NEW TRUSSES AND ROOF. TRUSSES APPEAR TO BE | | | HANGING FROM EXISTING AT LAUNDY ROOM WALL. IS THAT THE | | | CASE AND HOW CAN EXISTING SUPPORT THE NEW LOADS? | | | | | | 16. [FBC EXISTING 807.2]WHERE REMOVING EXTERIOR WALL IT | | | APPEARS THAT AN 8? X 8? BEAM IS LEFT BEHIND TO BEAR THE | | | EXISTING AND THE NEW TRUSSES. PROVIDE ENGINEERING TO | | | SHOW THAT BEAM WOULD BE SUFFICIENT TO SUPPORT ALL | | | LOADS. | | | I SEE THAT YOU END THE ADDITION EVEN WITH THE LAUNDRY. | | | CONSIDER PUSHING THE ADDITION BACK A COUPLE OF FEET SO | | | THAT THE EXISTING EXTERIOR WALL CAN REMAIN WITHOUT LOSS | | | OF NEW BEDROOM SIZE. | | | | | | 17. [FBC R802.11]SHOW CONNECTOR FOR EACH TRUSS. | | | | | | 18. [FBC 2319.17.2.4.4]WHAT IS THE GABLE END MATERIAL. | | | PROVIDE DETAIL OF GABLE END AND HOW ID TRANSITIONS TO | | | THE BEAM. | | | | | | 19. PLEASE SHOW SKLIGHTS ON ROOFING PLAN FOR NUMBER OF | | | SKYLIGHTS AND LOCATION. | | | | | | 20. [FBC ENERGY R401.2]THE PERMIT HA TWO ENERGY CALCS | | | ATTACHED. ONE IS PERFORMANCE AND ONE IS ENVELOPE. BASED | | | ON DATE IT LOOKS LIKE THE ENERGY CALCS BASED ON | | | PERFORMANCE IS THE CURRENT. IF SO, THERE ARE SOME | | | ERRORS ON THE REPORT. | | | OWNER, DESIGN LOCATION, BUILDER NAME, CLIMATE, ROOF, | | | ATTIC AND SKYLIGHTS NEED TO BE ADDED. | | | | | | NOTE: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2018-07-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-11 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-10 |
Time |
16:38 |
Sent To |
I |
|
| Notes |
| 2018-07-11 11:44:16 | PLAN | | | REVIEW COMMENTS | | | | | | 4TH REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) COMPLIED. | | | | | | 2) COMPLIED. | | | | | | 3) PARTIAL COMPLIANCE. EXPLAIN WHAT THE "INSIDE BITUMEN | | | FOAM" MEANS ON SHEET A3.0. ON SHEET A3.0 THE ROOFING | | | MATERIAL IS SPECIFIED AS ASPHALT TILE ROOF ON A 90# HOT | | | MOPPED TO A 30# BASE SHEET. PLEASE CLARIFY. FBC 107.2.1 | | | WILL ASPHALT SHINGLES OR CONCRETE ROOF TILE BE | | | INSTALLED? HOT MOPPED 90# IS NOT USED AS AN | | | UNDERLAYMENT FOR ASPHALT SHINGLES. | | | | | | 4) COMPLIED. | | | | | | 5) PARTIAL COMPLIANCE. STILL NEED THE PRODUCT APPROVALS | | | FOR THE SKYLIGHT AND THE ROOF COVERING MATERIAL. FBC | | | 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR | | | THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 | | | PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA | | | NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM | | | DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING | | | MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL MULLIONS, | | | SKYLIGHTS AND EXTERIOR DOOR TYPES. | | | | | | 6) COMPLIED. | | | | | | 10) COMPLIED. | | | | | | 11) COMPLIED. | | | | | | 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT | | | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | NEW COMMENTS: | | | | | | 13) ON SHEET A3.0, THE REVISED NOTES SPECIFY 10D NAILS | | | FOR THE ROOF SHEATHING AND THE PREVIOUS NOTE SPECIFIES | | | 8D RING SHANK NAILS. SPECIFY ONE OR THE OTHER. FBC | | | 107.2.1 | | | | | | 14) THE WINDOW AND DOOR SCHEDULE AND PRESSURES ON SHEET | | | A4.0 HAVE NUMEROUS ERRORS. THIS PROJECT IS LOCATED IN | | | EXPOSURE "C" WITH A 170MPH VULT WINDSPEED. THE ROUGH | | | OPENING SIZES FOR THE WINDOWS AND SLIDING GLASS DOOR | | | ARE INCORRECT. THE ROUGH OPENINGS SHOULD BE LARGER THAN | | | THE WINDOW AND DOOR SIZES. THE REQUIRED PRESSURES FOR | | | THE SLIDING GLASS DOOR SHOULD BE +33.9, -42.8 PSF. THE | | | SIZE OF THE DOOR IN THE SCHEDULE DOES NOT MATCH THE | | | ELEVATIONS. THE REQUIRED PRESSURES FOR THE WINDOWS | | | SHOULD BE +37.9, -50.7 PSF FOR WALL ZONE 5 AND +37.9, | | | -41.1 PSF FOR WALL ZONE 4. LOOK IN THE PRODUCT APPROVAL | | | NOAS FOR THE APPROVED DESIGN PRESSURES FOR THE WINDOWS | | | AND DOOR. THE OLD OUTDATED NOA NUMBERS WERE NOT REMOVED | | | FROM THE SCHEDULES. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-05-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-18 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-16 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2018-05-18 09:07:53 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) COMPLIED. | | | | | | 2) COMPLIED. | | | | | | 3) ON SHEET A3.0 THE ROOFING MATERIAL IS SPECIFIED AS | | | ASPHALT TILE ROOF ON A 90# HOT MOPPED TO A 30# BASE | | | SHEET. PLEASE CLARIFY. FBC 107.2.1 WILL ASPHALT | | | SHINGLES OR CONCRETE ROOF TILE BE INSTALLED? HOT MOPPED | | | 90# IS NOT USED AS AN UNDERLAYMENT FOR ASPHALT | | | SHINGLES. | | | | | | 4) THE PRODUCT APPROVAL NUMBERS THAT ARE SPECIFIED ON | | | THE PLANS FOR THE WINDOWS IN THE SCHEDULE ON SHEET A4.0 | | | AND THE TRUSS CONNECTORS ON SHEET S2.0 ARE EXPIRED. | | | PLEASE REMOVE FROM PLANS OR UPDATE THEM. | | | | | | 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | | ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL | | | MULLIONS, SKYLIGHTS AND EXTERIOR DOOR TYPES. | | | | | | 6) COMPLIED. | | | | | | 10) COMPLIED. | | | | | | 11) THE VALUATION LISTED ON THE PERMIT APPLICATION OF | | | $12,000.00 IS LOW. PLEASE PROVIDE AN ADEQUATE VALUATION | | | BASED ON FBC 109.3 BUILDING PERMIT VALUATION. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. SUBMIT | | | A COPY OF THE SIGNED CONTRACT FOR THIS PROJECT. | | | | | | 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT | | | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | 13) NEW COMMENT: A PRODUCT APPROVAL WAS SUBMITTED FOR A | | | SR PRODUCTS BUILT-UP ROOF SYSTEM OVER RECOVER DECKS. | | | THIS PRODUCT WILL NOT WORK FOR THIS PROJECT. THIS IS | | | FOR A ROOF OVER OR A RECOVER. THE MAXIMUM DESIGN | | | PRESSURES ARE -45 PSF WHICH ARE TOO LOW AND LIMITATION | | | #9 DOES NOT ALLOW THE PRESSURES TO BE INCREASED USING | | | RATIONAL ANALYSIS OR EXTRAPOLATION | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-29 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-26 |
Time |
18:33 |
Sent To |
I |
|
| Notes |
| 2018-03-29 16:57:04 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THESE PLANS ARE NOT BASED ON THE CURRENT 2014 | | | FLORIDA BUILDING CODE AND THE CURRENT EDITIONS OF THE | | | STANDARDS THAT ARE REFERENCED BY THE 2014 FBC. PLEASE | | | UPDATE THE PLANS TO THE 2014 FBC, THE 2014 FLORIDA FIRE | | | PREVENTION CODE, AND THE 2012 EDITION OF NFPA 1 AND | | | 101. THERE ARE STILL SOME CORRECTIONS THAT WERE MISSED. | | | SEE SHEET 1 OF 10 AND SHEET A1.0. | | | | | | 2) REVISE THE CODE SECTIONS THAT ARE SPECIFIED ON THE | | | PLANS TO CORRESPOND WITH THE APPROPRIATE SECTIONS IN | | | THE 2014 FBC. ON SHEET 1 OF 10, SECTION 504 AND 504.1 | | | OF THE 2014 FBC EXISTING BUILDING ARE THE SECTIONS FOR | | | LEVEL 2 ALTERATIONS. | | | | | | 3) ON SHEET A3.0 THE ROOFING MATERIAL IS SPECIFIED AS | | | ASPHALT TILE ROOF ON A 90# HOT MOPPED TO A 30# BASE | | | SHEET. PLEASE CLARIFY. FBC 107.2.1 WILL ASPHALT | | | SHINGLES OR CONCRETE ROOF TILE BE INSTALLED? HOT MOPPED | | | 90# IS NOT USED AS AN UNDERLAYMENT FOR ASPHALT | | | SHINGLES. | | | | | | 4) THE PRODUCT APPROVAL NUMBERS THAT ARE SPECIFIED ON | | | THE PLANS FOR THE WINDOWS IN THE SCHEDULE ON SHEET A4.0 | | | AND THE TRUSS CONNECTORS ON SHEET S2.0 ARE EXPIRED. | | | PLEASE UPDATE. | | | | | | 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | | ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL | | | MULLIONS, SKYLIGHTS AND EXTERIOR DOOR TYPES. | | | | | | 6) ON SHEET S1.0, UNDER GENERAL STRUCTURAL NOTES THE | | | WINDSPEED IS INCORRECT AND THE EDITIONS OF ACI 318 AND | | | ASCE 7 ARE INCORRECT. THE 2014 FBC REFERENCES ACI 318 - | | | 11 AND ASCE 7 - 10. PLEASE CORRECT FBC-R CHAPTER 46. | | | | | | 10) THE WF12 MONOLITHIC FOUNDATION THAT IS SPECIFIED ON | | | SHEET S1.0 FOR THE NEW ADDITION IS NOT ADEQUATE FOR THE | | | EXTERIOR CBS WALL CONSTRUCTION. THERE IS ONLY ONE #5 | | | CONTINUOUS RE-BAR SPECIFIED. THE FOOTER WILL HAVE TO BE | | | A MINIMUM OF 16" THICK. FBC-R404.1.6 HEIGHT ABOVE | | | FINISHED GRADE. CONCRETE AND MASONRY FOUNDATION WALLS | | | SHALL EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE | | | FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM) | | | WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES | | | (152 MM) ELSEWHERE. R403.1.4 MINIMUM DEPTH. ALL | | | EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES | | | (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. THE | | | EXTERIOR FOOTINGS THAT WILL SUPPORT THE NEW EXTERIOR | | | CBS WALLS SHOULD BE LABELED DIFFERENTLY FROM THE 12" X | | | 12" THICKENED EDGE THAT IS AGAINST THE EXISTING | | | FOUNDATION WHERE THE DOWELS WILL BE INSTALLED. PROVIDE | | | A SECTION FOR EACH OF THE DIFFERENT FOUNDATION TYPES. | | | | | | 11) THE VALUATION LISTED ON THE PERMIT APPLICATION OF | | | $12,000.00 IS LOW. PLEASE PROVIDE AN ADEQUATE VALUATION | | | BASED ON FBC 109.3 BUILDING PERMIT VALUATION. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT | | | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-09-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-09-18 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-09-15 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2017-09-15 16:52:31 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THESE PLANS ARE NOT BASED ON THE CURRENT 2014 | | | FLORIDA BUILDING CODE AND THE CURRENT EDITIONS OF THE | | | STANDARDS THAT ARE REFERENCED BY THE 2014 FBC. PLEASE | | | UPDATE THE PLANS TO THE 2014 FBC, THE 2014 FLORIDA FIRE | | | PREVENTION CODE, AND THE 2012 EDITION OF NFPA 1 AND | | | 101. | | | | | | 2) REVISE THE CODE SECTIONS THAT ARE SPECIFIED ON THE | | | PLANS TO CORRESPOND WITH THE APPROPRIATE SECTIONS IN | | | THE 2014 FBC. FOR EXAMPLE ON SHEET 1 OF 10, SECTION 505 | | | IS THE CURRENT ONE FOR LEVEL 3 ALTERATIONS. | | | | | | 3) ON SHEET 1, THIS PROJECT IS SPECIFIED AS A LEVEL 3 | | | ALTERATION AND A LEVEL 2 ALTERATION. REFER TO THE 2014 | | | FBC- EXISTING BUILDING AND SELECT THE APPROPRIATE LEVEL | | | OF ALTERATION AND SPECIFY IT ON THE PLANS. | | | | | | 4) SPECIFY THE ROOF SLOPE ON THE PLANS. FBC 107.2.1 & | | | R301.1 | | | | | | 5) THE NEW SKYLIGHT #4 AND ITEM #5 ON SHEET A1.0 ARE | | | NOT IDENTIFIED IN THE SCHEDULE ON SHEET A4.0. PLEASE | | | CLARIFY. FBC 107.2.1 | | | | | | 6) ON SHEET A3.0 THE ROOFING MATERIAL IS SPECIFIED AS | | | ASPHALT TILE ROOF ON A 90# HOT MOPPED TO A 30# BASE | | | SHEET. PLEASE CLARIFY. FBC 107.2.1 | | | | | | 7) THE PRODUCT APPROVALS THAT ARE SPECIFIED ON THE | | | PLANS FOR THE WINDOWS, DOORS, TRUSS HANGERS AND | | | CONNECTORS ARE ALL EXPIRED. PLEASE UPDATE. | | | | | | 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | | ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL | | | MULLIONS, SKYLIGHTS AND EXTERIOR DOOR TYPES. | | | | | | 9) ON SHEET S1.0, UNDER GENERAL STRUCTURAL NOTES THE | | | WINDSPEED IS INCORRECT AND THE EDITIONS OF ACI 318 AND | | | ASCE 7 ARE INCORRECT. THE 2014 FBC REFERENCES ACI 318 - | | | 11 AND ASCE 7 - 10. PLEASE CORRECT FBC-R CHAPTER 46. | | | | | | 10) THE W12 MONOLITHIC FOUNDATION THAT IS SPECIFIED ON | | | SHEET S1.0 FOR THE NEW ADDITION IS NOT ADEQUATE FOR THE | | | EXTERIOR CBS WALL CONSTRUCTION. THERE IS ONLY ONE #5 | | | CONTINUOUS RE-BAR SPECIFIED. THE FOOTER WILL HAVE TO BE | | | A MINIMUM OF 16" THICK. FBC-R404.1.6 HEIGHT ABOVE | | | FINISHED GRADE. CONCRETE AND MASONRY FOUNDATION WALLS | | | SHALL EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE | | | FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM) | | | WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES | | | (152 MM) ELSEWHERE. R403.1.4 MINIMUM DEPTH. ALL | | | EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES | | | (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. | | | | | | 11) THE VALUATION LISTED ON THE PERMIT APPLICATION OF | | | $12,000.00 IS LOW. PLEASE PROVIDE AN ADEQUATE VALUATION | | | BASED ON FBC 109.3 BUILDING PERMIT VALUATION. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT | | | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-03-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-03-19 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-03-19 |
Time |
12:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-09-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-09-07 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-09-07 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2017-09-07 09:59:05 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION PER CODE. | | | SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING | | | OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3, | | | FBC 107.2.1 | | | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR | | | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM | | | BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, | | | 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC | | | 107.2.1 | | | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 | | | 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC | | | RE3706.2, RE3902 | | | 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A | | | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-12-05 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2018-12-05 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2018-12-05 |
Time |
11:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-05-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-18 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2018-05-15 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-03-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2018-03-07 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2018-02-28 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2018-03-07 13:48:20 | COMMENTS FROM FIRST REVIEW NOT ADDRESSED. COA NOT | | | SUBMITTED. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-08-25 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2017-08-25 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2017-08-25 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2017-08-25 10:51:09 | PROPERTY IN HISTORIC DISTRICT, REQUIRES SUBMITTAL OF | | | COA. | | | | | | QUESTIONS, CONTACT FRIEDERIKE MITTNER, CITY HISTORIC | | | PRESERVATION PLANNER AT (561) 822-1457 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2018-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-12-07 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-12-05 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2018-12-07 10:07:39 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2018-12-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-12-07 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-10-26 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2018-10-30 11:07:02 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-08-16 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-03 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2018-08-07 10:55:20 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-07-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-11 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-03 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2018-07-05 15:27:11 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-05-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-18 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-03 |
Time |
10:39 |
Sent To |
HIST |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-29 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-02-23 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-09-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-09-18 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-15 |
Time |
11:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2018-05-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-17 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-16 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2018-05-17 15:10:04 | MU-2018-14592, PAID $180.65 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-09-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-09-15 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-09-15 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2017-09-15 09:58:38 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2018-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-12-07 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-12-07 |
Time |
15:07 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2018-10-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-10-31 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-10-31 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2018-10-31 07:42:55 | PLAN | | | REVIEW COMMENTS | | | | | | 6TH REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE LOCATION OF THE MINI-SPLIT EQUIPMENT IS NOT | | | SHOWN ON THE MECHANICAL PLANS. FBC 107.2.1 | | | | | | 2) THE 2017 EDITION OF FORM R405 WAS SUBMITTED. THIS | | | PROJECT WAS APPLIED FOR UNDER THE 2014 FBC. SUBMIT THE | | | FORMS AND CALCULATIONS FOR THE 2014 EDITION. PROVIDE | | | HEATING AND COOLING EQUIPMENT SIZING CALCULATIONS FOR | | | THE NEW ADDITION. FBCR-M1401.3 | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-08-16 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-16 |
Time |
10:37 |
Sent To |
I |
|
| Notes |
| 2018-08-16 10:48:06 | PLAN | | | REVIEW COMMENTS | | | | | | 5TH REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | 1) SEE BUILDING REVIEW COMMENTS FOR ENERGY CODE | | | COMPLIANCE. | | | | | | 2) PROVIDE HEATING AND COOLING EQUIPMENT SIZING | | | CALCULATIONSFOR THE NEW ADDITION. FBCR-M1401.3 | | | | | | 3) CLARIFY THAT THE PROPOSED MINI-SPLIT SYSTEM WILL | | | PROVIDE THE REQUIRED HEATING FOR THE NEW ADDITION. FBC | | | 107.2.1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-10 |
Time |
18:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-10 |
Time |
17:13 |
Sent To |
|
|
| Notes |
| 2018-07-10 17:36:57 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) COMPLIED. | | | 2) COMPLIED. | | | 3) COMPLIED. | | | 4) THE ATTIC VENT RATIO IS LISTED AS 300 SQFT ON THE | | | ENERGY FORMS. FBC-R 806.2 THE MINIMUM NET FREE | | | VENTILATION AREA SHALL BE 1/150 OF THE VENTED SPACE. | | | THE EXCEPTION THAT ALLOWS THE 1/300 NET VENTILATION | | | REQUIRES THAT AT LEAST 40 PERCENT AND NOT MORE THAN 50 | | | PERCENT OF THE REQUIRED VENTILATING AREA IS PROVIDED BY | | | VENTILATORS LOCATED IN THE UPPER PORTION OF THE ATTIC | | | OR RAFTER SPACE. UPPER VENTILATORS SHALL BE LOCATED NO | | | MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST | | | POINT OF THE SPACE, MEASURED VERTICALLY, WITH THE | | | BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR | | | CORNICE VENTS. WHERE THE LOCATION OF WALL OR ROOF | | | FRAMING MEMBERS CONFLICTS WITH THE INSTALLATION OF | | | UPPER VENTILATORS, INSTALLATION MORE THAN 3 FEET (914 | | | MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE SHALL | | | BE PERMITTED. THE PLANS DO NOT SHOW | | | 5) COMPLIED. | | | | | | NEW COMMENTS: | | | THE ENERGY FORMS CONTAIN NUMEROUS ERRORS. SEE NEW | | | COMMENTS BELOW. | | | 1) THE DESIGN LOCATION ON THE ENERGY FORMS IS LISTED AS | | | ST LUCIE, THIS PROJECT IS LOCATED IN WEST PALM BEACH, | | | FL. WHICH IS IN PALM BEACH COUNTY. ON PAGE 2, THE TMY | | | SITE IS INCORRECTLY LISTED AS VERO BEACH. | | | | | | 2) THE ROOF IS LISTED AS BARREL TILE INSTEAD OF ASPHALT | | | SHINGLES. | | | | | | 3) ON PAGE 1, THERE IS A WOOD FRAME EXTERIOR WALL | | | LISTED AND ALL OF THE EXTERIOR WALLS OF THE ADDITION | | | ARE CBS. | | | | | | 4) LIST THE OWNER'S AND BUILDER'S NAMES IN THE AREA AT | | | THE TOP OF PAGE 1. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2018-05-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-18 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-18 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2018-05-18 09:50:18 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) COMPLIED. | | | | | | 2) THIS PROJECT IS PERMITTED UNDER THE 2014 FBC. THE | | | R405 ENERGY FORM THAT WAS SUBMITTED IS FOR THE 2017 | | | FBC. SUBMIT TWO SETS OF THE R405-2014 ENERGY FORMS. | | | | | | 3) THE ENERGY FORMS R405-2014 ARE REQUIRED TO BE SIGNED | | | BY THE OWNER/AGENT. FBC ENERGY CONSERVATION SECTION | | | R103.1.1.2. | | | | | | 4) THE ATTIC VENT RATIO IS LISTED AS 300 SQFT ON THE | | | ENERGY FORMS. FBC-R 806.2 THE MINIMUM NET FREE | | | VENTILATION AREA SHALL BE 1/150 OF THE VENTED SPACE. | | | THE EXCEPTION THAT ALLOWS THE 1/300 NET VENTILATION | | | REQUIRES THAT AT LEAST 40 PERCENT AND NOT MORE THAN 50 | | | PERCENT OF THE REQUIRED VENTILATING AREA IS PROVIDED BY | | | VENTILATORS LOCATED IN THE UPPER PORTION OF THE ATTIC | | | OR RAFTER SPACE. UPPER VENTILATORS SHALL BE LOCATED NO | | | MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST | | | POINT OF THE SPACE, MEASURED VERTICALLY, WITH THE | | | BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR | | | CORNICE VENTS. WHERE THE LOCATION OF WALL OR ROOF | | | FRAMING MEMBERS CONFLICTS WITH THE INSTALLATION OF | | | UPPER VENTILATORS, INSTALLATION MORE THAN 3 FEET (914 | | | MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE SHALL | | | BE PERMITTED. THE PLANS DO NOT SHOW | | | | | | 5) COMPLIED. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-29 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-26 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2018-03-29 16:24:44 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL | | | PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS | | | PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. THE MANUAL | | | J EQUIPMENT SIZING CALCULATIONS THAT WERE SUBMITTED | | | SPECIFY A 12000 BTUH PTAC UNIT. SHOW IT'S LOCATION ON | | | THE PLANS AND PROVIDE AN EQUIPMENT SCHEDULE FRO IT. | | | NOTE: FBC-R 303.9 REQUIRES THE ADDITION TO BE HEATED. | | | | | | 2) THIS PROJECT IS PERMITTED UNDER THE 2014 FBC. THE | | | R405 ENERGY FORM THAT WAS SUBMITTED IS FOR THE 2017 | | | FBC. SUBMIT TWO SETS OF THE R405-2014 ENERGY FORMS. | | | | | | 3) THE ENERGY FORMS R405-2014 ARE REQUIRED TO BE SIGNED | | | BY THE OWNER/AGENT. FBC ENERGY CONSERVATION SECTION | | | R103.1.1.2. | | | | | | 4) THE ATTIC VENT RATIO IS LISTED AS 300 SQFT ON THE | | | ENERGY FORMS. FBC-R 806.2 THE MINIMUM NET FREE | | | VENTILATION AREA SHALL BE 1/150 OF THE VENTED SPACE. | | | THE EXCEPTION THAT ALLOWS THE 1/300 NET VENTILATION | | | REQUIRES THAT AT LEAST 40 PERCENT AND NOT MORE THAN 50 | | | PERCENT OF THE REQUIRED VENTILATING AREA IS PROVIDED BY | | | VENTILATORS LOCATED IN THE UPPER PORTION OF THE ATTIC | | | OR RAFTER SPACE. UPPER VENTILATORS SHALL BE LOCATED NO | | | MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST | | | POINT OF THE SPACE, MEASURED VERTICALLY, WITH THE | | | BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR | | | CORNICE VENTS. WHERE THE LOCATION OF WALL OR ROOF | | | FRAMING MEMBERS CONFLICTS WITH THE INSTALLATION OF | | | UPPER VENTILATORS, INSTALLATION MORE THAN 3 FEET (914 | | | MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE SHALL | | | BE PERMITTED. THE PLANS DO NOT SHOW | | | | | | 5) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-09-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-09-15 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-09-15 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2017-09-15 16:33:09 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL | | | PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS | | | PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. | | | | | | 2) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR | | | R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE | | | FORMS AS REQUIRED. | | | | | | 3) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-03-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-20 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-20 |
Time |
11:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-09-07 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2017-09-07 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2017-09-07 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2017-09-07 14:48:41 | 9/7/17 1ST REVIEW PLUMBING DENIED | | | | | | 1) PLANS LIST BUILDING CODE AS 2010. WE ARE CURRENTLY | | | UNDER THE 2014 FIFTH EDITION FBC | | | | | | 2) P1 SHOWS A 2 HANDLE SHOWER VALVE. FBC-PLB 424.3 | | | REQUIRES SHOWER VALVES TO BE PRESSURE BALANCED, | | | THERMOSTATIC, OR A COMBINATION OF BOTH | | | | | | 3) SHOWER COMPARTMENTS PER FBC-PLB REQUIRE A MIN OF 900 | | | SQ IN. PLEASE SHOW SHOWER DIMENSIONS | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-08-16 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-16 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2018-08-16 10:13:03 | PRODUCT APPROVAL FOR SHINGLE OK. | | | NAILING TO BE ADDRESSED IN BUILDING COMMENTS. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-10 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-10 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2018-07-10 18:50:34 | NO ROOFING PRODUCT APPROVALS WERE SUBMITTED. ASPHALT | | | SHINGLES ARE SPECIFIED ON THE PLANS. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2018-05-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-18 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-17 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2018-05-18 10:30:36 | NO ACCEPTABLE PRODUCT APPROVALS WERE SUBMITTED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-29 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-26 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2018-03-29 17:44:21 | NO ROOFING PRODUCT APPROVALS WERE SUBMITTED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-09-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-09-18 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-09-18 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2017-09-18 08:28:10 | NO ROOFING PRODUCT APPROVALS WERE SUBMITTED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2018-12-05 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2018-12-05 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2018-12-05 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-05-15 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2018-05-15 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2018-05-15 |
Time |
13:31 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-03-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2018-03-07 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2018-03-07 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2018-03-07 13:47:39 | INITIAL COMMENTS OF SIDE SETBACK NOT ADDRESSED |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2017-08-18 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-08-18 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-08-18 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2017-08-18 09:25:37 | 8/18/17- FAILED | | | | | | 94-82(B)2(E)1- 6FT. 8IN. SIDE SETBACK HAS A CUMALATIVE | | | SIDE SETBACK OF 12FT. 5IN. AND THIS SITE REQUIRES A | | | 15FT. CUMULATIVE SETBACK | | | 94-82(B)4-A- WHAT IS THE LOT COVERAGE? | | | 94-82(B)5-A- WHAT IS THE FLOOR TO AREA RATIO? | | | 94-449- NO TREES MAYBE MOVED WITHOUT A TREE ALTERATION | | | PERMIT | | | | | | | | | PLEASE CONTACT | | | NATHAN WIRA- ZONING TECHNICIAN | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING | | | DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST. | | | WEST PALM BEACH, FL 33402 | | | OFFICE HOURS: M-F 8AM - 5PM | | | (561)822-1442 | | | [email protected] | | | |
|
|