Plan Review Details - Permit 17080711
Plan Review Stops For Permit 17080711
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-05 Cont ID  
Sent By rmcdouga Date 2017-10-05 Time 07:25 Rev Time 0.00
Received By rmcdouga Date 2017-10-05 Time 06:52 Sent To G
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-09-01 Cont ID  
Sent By rmcdouga Date 2017-09-01 Time 18:23 Rev Time 0.00
Received By rmcdouga Date 2017-09-01 Time 18:23 Sent To  
Notes
2017-09-01 18:23:50PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE STRUCTURE AND GENERATOR ARE LOCATED WITHIN 600
 FEET OF THE INTRACOASTAL WATERWAY. BASED ON
 FBC-R301.2.1.4.3, THE GENERATOR IS LOCATED IN EXPOSURE
 'D'. THE REQUIRED DESIGN PRESSURE FOR THE GENERATOR ON
 THE DOCUMENTS THAT WERE SUBMITTED IS 50 PSF. THE
 ALLOWABLE PRESSURE ON THE DOCUMENTS FOR THE PAD ARE
 39.20 PSF, WHICH DOES NOT MEET THE REQUIRED WIND LOADS.
 FBC-R301.2.1
  
 2) THE TWO SETS OF SITE SPECIFIC DESIGN PRESSURE
 REQUIREMENTS FOR THIS PROJECT AS REQUIRED BY GENERAL
 NOTE #2 ON THE GENERATOR PAD DRAWINGS THAT WERE
 SUBMITTED ARE FROM A FLORIDA LICENSED ENGINEER AND ARE
 REQUIRED TO BE SEALED AND HAVE THE ENGINEER'S
 HANDWRITTEN SIGNATURE. FAC 61G15 - 23.002
  
 3) IN ORDER TO MEET WIND LOAD REQUIREMENTS THE CONCRETE
 PAD HAS A MINIMUM WEIGHT REQUIREMENT FOR THE GENERATOR.
 SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS FOR
 THE GENERATOR THAT SPECIFY THE WEIGHT OF IT. FBC
 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-23 Cont ID  
Sent By rmcdouga Date 2017-08-23 Time 14:32 Rev Time 0.00
Received By rmcdouga Date 2017-08-23 Time 11:44 Sent To P
Notes
2017-08-23 14:32:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE
 ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS
 AND DOCUMENTS.
  
 2) SUBMIT TWO SETS OF THE JOB SITE SPECIFIC DESIGN
 PRESSURES FOR THIS PROJECT AS REQUIRED BY GENERAL NOTE
 #2 ON THE GENERATOR PAD DRAWINGS. FBC 107.2.1
  
 3) IN ORDER TO MEET WIND LOAD REQUIREMENTS THE CONCRETE
 PAD HAS A MINIMUM WEIGHT REQUIREMENT FOR THE GENERATOR.
 SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS FOR
 THE GENERATOR THAT SPECIFY THE WEIGHT OF IT. FBC
 107.2.1
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-18 Cont ID  
Sent By jleahy Date 2017-08-18 Time 14:44 Rev Time 0.00
Received By jleahy Date 2017-08-18 Time 14:44 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2017-10-18 Cont ID  
Sent By thunt Date 2017-10-18 Time 14:48 Rev Time 0.00
Received By thunt Date 2017-10-18 Time 14:48 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-10-05 Cont ID  
Sent By thunt Date 2017-10-05 Time 12:43 Rev Time 0.00
Received By thunt Date 2017-10-05 Time 12:43 Sent To I
Notes
2017-10-05 12:49:3310/5/17 3RD GAS REVIEW**DENIED**
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE INCLUDING EXIST
 SYTEM PER 2014 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR
 2014 FBC-RES SEC. G2413
  
 2) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE FOR BOTH REGULATORS USED. COMPLY WITH 2014
 FBC-FUEL GAS TABLE 402.4 (28) FOR THE PROPER PIPE SIZE
 AND BTU LOAD
  
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM.YOU ONLY INCLUDED THE P.E
 CHART (22) BUT YOU MUST INCLUDE ALL CHARTS FOR ALL PIPE
 TYPES AND PREESURES USED IN THE NEW AND EXISTING SYSTEM
 REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4, 401.8 THRU
 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR 2014
 FBC-RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
  
 4) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE NEW AND EXISTING. WPB AMENDMENTS TO FBC
 SEC.107.2.1.
  
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION YOU PROVIDED SPECS FOR L.P LISTED AND
 APPROVED REGUALTORS WHILE YOUR SYSTEM IS NAT. 2014 FGC
 SEC.410.1
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-09-01 Cont ID  
Sent By thunt Date 2017-09-01 Time 12:55 Rev Time 0.00
Received By thunt Date 2017-09-01 Time 12:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-08-23 Cont ID  
Sent By thunt Date 2017-08-23 Time 16:32 Rev Time 0.00
Received By thunt Date 2017-08-23 Time 16:09 Sent To  
Notes
2017-08-23 16:32:271ST REVIEW DENIED**YOU ARE CURRENTLY USING AN OUT DATED
 VERSION OF ARE GAS PERMIT APPLICATION REQUIREMENTS
 DATED 04/09/09**
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ( ALL CUT SECTIONS OF PIPE) PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413
  
 4) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3
  
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-10-18 Cont ID  
Sent By cpuell Date 2017-10-18 Time 14:57 Rev Time 0.00
Received By cpuell Date 2017-10-16 Time 13:06 Sent To  
Notes
2017-10-17 13:07:04RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-05 Cont ID  
Sent By cpuell Date 2017-10-05 Time 15:15 Rev Time 0.00
Received By cpuell Date 2017-10-02 Time 13:06 Sent To  
Notes
2017-10-03 13:06:26RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-01 Cont ID  
Sent By rmcdouga Date 2017-09-01 Time 18:24 Rev Time 0.00
Received By rmcdouga Date 2017-08-31 Time 09:54 Sent To  
Notes
2017-09-01 09:54:49RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-23 Cont ID  
Sent By thunt Date 2017-08-23 Time 16:32 Rev Time 0.00
Received By thunt Date 2017-08-15 Time 16:14 Sent To  
Notes
2017-08-16 16:14:45ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-18 Cont ID  
Sent By njwira Date 2017-08-18 Time 13:50 Rev Time 0.00
Received By njwira Date 2017-08-17 Time 16:12 Sent To  
Notes
***NONE***