Plan Review Details - Permit 17080703
Plan Review Stops For Permit 17080703
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2017-10-26 Cont ID  
Sent By shill Date 2017-10-26 Time 17:34 Rev Time 0.00
Received By shill Date 2017-10-26 Time 17:34 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2017-10-26 Cont ID  
Sent By shill Date 2017-10-26 Time 14:14 Rev Time 0.00
Received By shill Date 2017-10-26 Time 14:14 Sent To  
Notes
2017-10-26 14:14:40AN INCORRECT PARCEL WAS CREATED IN THE PARCEL FILE (HAS
 OWNER AS PALM BEACH OUTLET MALL; CONFIRMED WITH
 PBCOUNTY CLERK THAT THIS WAS NEVER THE OWNER). THE
 FORUM PLACE PARCEL WAS SPLIT INTO THREE CONDO UNITS;
 EACH BUILDING IS A CONDO UNIT. THE NEW APPLICAITON FROM
 APPLICANT HAS A PARCEL ID WHICH IS NOT IN PROPERTY
 APPRAISER. I OBTAINED PARCEL ID INFORMATION FROM MIKE
 ORIO (WHO RECEIVED IT FROM PALM BEACH COUNTY) AND
 REQUESTED THAT SUSAN PALMER ADD THE ADDRESS.
  
 OK TO PASS ADDRESS REVIEW AFTER ADDRESS (PARCEL, OWNER)
 IS CORRECTED ON PERMIT APPLICATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-26 Cont ID  
Sent By shill Date 2017-10-26 Time 13:19 Rev Time 0.00
Received By shill Date 2017-10-26 Time 13:19 Sent To  
Notes
2017-10-26 13:20:22PROVISO - ISSUED AT APPLICANT'S RISK. DOORS LIKELY NEED
 PANIC BARS FBC B 1008
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 12:18 Rev Time 0.00
Received By shill Date 2017-08-29 Time 12:18 Sent To  
Notes
2017-08-29 12:26:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, SEE PREVIOUS LIST, SHEET GN-1D NOTES STATE
 THAT SCOPE IS INTERIOR DEMO, REVISE.
  
 2. FBC 107, SHEETS WERE REPLACED (A101, A102 AND
 OTHERS). THE FIRST VERSION HAD NO FLOOR PLAN AND SHOWED
 ONLY THE SCOPE PROPOSED (WINDOW REPLACEMENT). THE NEW
 PAGES INCLUDE FLOOR PLANS AND WALL SPECIFICATIONS.
 PLEASE REFER TO THE PREVIOUS COMMENT LIST AND MODIFY
 PAGES TO ADDRESS COMMENTS ONLY. FLOOR PLANS SHOULD NOT
 BE INCLUDED IN A WINDOW REPLACEMENT PERMIT AS THAT IS
 BEYOND THE SCOPE OF THIS REVIEW AND SCOPE OF THIS
 PERMIT APPLICATION.
  
 THE WORK PROPOSED (REMOVAL OF MASONRY WALLS, INFILL
 DETAIL, WINDOW REPLACEMENT) IS NO LONGER ON THE PLANS.
 PROJECT NAME IS "THE FORUM HOTEL - RENOVATION WINDOW
 REPLACEMENT". REVISE TO STATE "WINDOW REPLACEMENT" AND
 REVISE PLAN TO RESTORE THE INFORMATION DESCRIBING SCOPE
 WHICH WAS PREVIOUSLY REVIEWED (VERSION 1).
  
 VERSION 2 INCLUDES THE WINDOW LOCATIONS. PLEASE REVISE
 VERSION 1 TO INCLUDE THIS INFORMATION. OR, REVISE
 VERSION 2 TO REMOVE THE FLOOR PLANS AND ADD THE
 INFORMATION FROM VERSION 1.
  
 3. THE APPLICATION DOES NOT INCLUDE DOOR INSTALLATION.
 SEE WINDOW TYPE D; IT IS NOT CLEAR HOW YOU WILL
 ACCOMPLISH THIS INSTALLATION WITHOUT A DOOR. IS THIS A
 PART OF THE SCOPE? EITHER REMOVE FROM SCOPE OR CLARIFY.
 IF DOORS ARE PROPOSED IN THE SCOPE OF THIS PERMIT, A
 PRODUCT APPROVAL IS REQUIRED. WILL DOOR D INCLUDE PANIC
 HARDWARE (APPEARS TO BE REQUIRED, ASSEMBLY OCCUPANCY)?
 IF NOT, A LIFE SAFETY PLAN AND FIRE REVIEW WILL BE
 REQUIRED.
  
 4. THE NOA UPLOADED IS INCOMPLETE. FBC 107, PROVIDE A
 COMPLETE DOCUMENT. IT APPEARS THAT THE LARGE DRAWING
 PAGES WERE PRINTED ON 8 1/2 X 11 PAPER (BUT REQUIRED 11
 X 17 OR CHANGE OF ORIENTATION), SO THE RIGHT HALF OF
 THE PAGE IS MISSING.
  
 5. REVISE PLAN TO SHOW PROPOSED LOCATIONS OF WINDOWS
 SHOWN IN THE SCHEDULE ON A602.
  
 6. IT IS NOT CLEAR WHERE WINDOW E IS IN THE PRODUCT
 APPROVAL, PLEASE DIRECT. SHEET 4 OF 11 ON THE PRODUCT
 APPROVAL APPEARS TO SHOW A LIMIT OF 60" X 120" AND
 APPEARS TO HAVE ONE MULLION. WINDOW E IS 6'6" X 9'8"
 WITH A 2" LINE WHICH APPEARS TO BE A MULLION. REVISE
 PLAN AND MARK UP PRODUCT APPROVAL TO CLARIFY COMPLIANCE
 OF PROPOSED INSTALLATION.
  
 7. WINDOW B, A STRUCTURAL MULLION IS PROPOSED. PROVIDE
 THE PRODUCT APPROVAL, FBC B 1609.
  
 8. THE WINDOW LOCATION INFORMATION IS ON VERSION 2 OF
 THE FLOOR PLANS. PLEASE REVISE VERSION 1 PLAN TO
 INCLUDE THIS INFORMATION.
  
 9. PERMIT APPLICATION DESCRIPTION NOT CLEAR. IT STATES:
 "INSTALLATION OF REPLACEMENT WINDOWS IN PLACE OF
 EXISTING WINDOWS REMOVED AS PART OF DEMOLITION." WINDOW
 REMOVAL IS NOT INCLUDED IN THE SCOPE OF THE DEMO
 PERMIT. WINDOW REMOVAL WILL BE INCLUDED IN THE SCOPE OF
 THIS PERMIT. PROVIDE A CORRECTED APPLICATION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-17 Cont ID  
Sent By shill Date 2017-08-17 Time 06:29 Rev Time 0.00
Received By shill Date 2017-08-17 Time 06:17 Sent To  
Notes
2017-08-17 07:02:26***CORRECTIONS***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. GN-1 DIVISISION 1 GENERAL REQUIREMENTS (AND ANY
 OTHER LOCATIONS IF APPLICABLE), REVISE PLAN TO REMOVE
 REFERENCE TO MARTIN COUNTY, FBC 107.
  
 2. BUILDING CODE SUMMARY, REVISE SCOPE OF WORK
 (CURRENTLY STATES INTERIOR DEMOLITION). REMOVE
 REFERENCE TO MARTIN COUNTY.
  
 3. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA, FBC B
 1603.1.4.
  
 4. REVISE PLAN TO INCLUDE A WINDOW SCHEDULE, FBC B
 1609. THE WINDOWS PROPOSED MUST EITHER MEET THE SIZE
 LIMITATIONS IN THE PRODUCT APPROVAL OR SITE SPECIFIC
 ENGINEERING REQUIRED.
  
 5. OK
  
 6. PLANS STATE TO INSTALL GLAZING AND MASONRY INFILL
 "TO THE EXTENTS INDICATED". WHILE HORIZONTAL DIMENSIONS
 ARE PROVIDED, VERTICAL DIMENSIONS DO NOT APPEAR TO BE
 PROVIDED. IT APPEARS THAT IT IS POSSIBLE THAT SOME
 PAGES WERE INADVERTENTLY NOT SUBMITTED. PROVIDE EITHER
 ELEVATIONS WITH REQUIRED INFORMATION (SEE FBC 107,
 PLANS TO SHOW SCOPE AND NATURE OF PROPOSED WORK), OR A
 SCHEDULE, OR ANY OTHER OPTION WHICH CLEARLY SHOWS
 WINDOW SIZES. IF ALL WINDOWS ARE THE SAME HEIGHT, A
 NOTE WILL SUFFICE. IF A NOTE IS USED, PLEASE PUT IN A
 VISIBLE LOCATION (NOT BURIED IN GENERAL NOTES).
  
 7. FBC EC TABLE C402.3, PROVIDE SPEC SHEETS WHICH SHOW
 U-FACTOR AND SHGC FOR THE PROPOSED WINDOWS, OR REVISE
 THE SIGNED AND SEALED PLAN TO INCLUDE THIS INFORMATION.
  
 8. IT IS NOT CLEAR WHETHER THIS ASPECT OF THE PROJECT
 WILL COMPLY WITH FBC ENERGY CONSERVATION. PLEASE SEE
 FBC EB CHAPTER 2, DEFINITION OF "RENOVATED BUILDING".
 ENERGY CALCS WILL BE REQUIRED FOR THE INTERIOR BUILDOUT
 PERMIT.
  
 IT IS UNDERSTOOD THAT THE INTERIOR IS STILL IN DESIGN
 PHASE. PLEASE CONFIRM, VIA A SIGNED AND SEALED RESPONSE
 LETTER, THAT APPLICANT HAS RESEARCHED THIS ISSUE AND
 CONFIRMS THAT PROPOSED WINDOWS WILL NOT AFFECT
 APPLICANT'S ABILITY TO DESIGN A BUILDOUT WHICH COMPLIES
 WITH FBC ENERGY CONSERVATION REQUIREMENTS. ALSO
 ACKNOWLEDGE THAT APPLICANT PROCEEDS AT APPLICANT'S OWN
 RISK.
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-26 Cont ID  
Sent By shill Date 2017-10-26 Time 14:15 Rev Time  
Received By shill Date 2017-10-24 Time 13:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 13:13 Rev Time 0.00
Received By shill Date 2017-08-24 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-17 Cont ID  
Sent By shill Date 2017-08-17 Time 07:30 Rev Time 0.00
Received By shill Date 2017-08-16 Time 13:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2017-10-26 Cont ID  
Sent By shill Date 2017-10-26 Time 13:20 Rev Time 0.00
Received By shill Date 2017-10-26 Time 13:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2017-08-29 Cont ID  
Sent By shill Date 2017-08-29 Time 13:10 Rev Time 0.00
Received By shill Date 2017-08-29 Time 13:10 Sent To  
Notes
2017-08-29 12:05:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A SHEETS ARE OK - DIGITALLY SIGNED AND SEALED, BUT NEW
 SHEETS NEED TO BE VERIFIED IN REVIEW CYCLE #3
 SHEET S1.01 IS NOT DIGITALLY SIGNED AND SEALED. EITHER
 UPLOAD A DIGITALLY SIGNED AND SEALED PAGE OR PROVIDE A
 PAPER SIGNED AND SEALED ORIGINAL. THIS MAY BE DONE AT
 ANY TIME; SUBMIT AT THE BUILDING DIVISION AND INCLUDE
 "SIGNATURE DOCUMENT" AS THE DESCRIPTION ON THE
 SUBMITTAL FORM.
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-08-17 Cont ID  
Sent By shill Date 2017-08-17 Time 07:29 Rev Time 0.00
Received By shill Date 2017-08-17 Time 07:29 Sent To  
Notes
2017-08-17 07:30:19DIGITAL SIGNATURE/SEAL OK ON ALL SHEETS
 NEW PAGES SUBMITTED REVIEW CYCLE #2 NEED TO BE VERIFIED
  
  