Plan Review Details - Permit 17080682
Plan Review Stops For Permit 17080682
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-11-27 Time   Rev Time 0.00
Received By cthroop Date 2017-11-27 Time 14:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-14 Cont ID  
Sent By cthroop Date 2017-09-14 Time 16:30 Rev Time 0.00
Received By cthroop Date 2017-09-14 Time 07:28 Sent To M
Notes
2017-09-14 16:39:49BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE MECHANICAL PLAN.
 2. PROVIDE ENERGY SUBMITTAL.
 3. PROVIDE SITE PLAN.
 4. PROVIDE EXTERIOR BLDG. ELEVATIONS.
 5. PROVIDE DETAIL FOR EXTERIOR WALL IN-FILL.
 6. PROVIDE FRAMING PLAN FOR OVERHEAD DOOR IN-FILL.
 7. THERE ARE THREE DIFFERENT FLOOR PLANS IN THIS
 SUBMITTAL. PLEASE CLARIFY.
 8. PRODUCT APPROVAL SUBMITTED FOR NEW WINDOW. SHOW
 LOCATION OF NEW WINDOW ON FLOOR PLAN.
 9. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-12-07 Cont ID  
Sent By jpearson Date 2017-12-07 Time 13:49 Rev Time 0.00
Received By jpearson Date 2017-12-07 Time 13:49 Sent To P
Notes
2017-12-07 13:49:10NO CHANGES TO PREVIOUSLY APPROVED PLANS, STAMPED NEW
 SETS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-22 Cont ID  
Sent By jpearson Date 2017-11-22 Time 15:19 Rev Time 0.00
Received By jpearson Date 2017-11-22 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By jpearson Date 2017-08-30 Time 10:37 Rev Time 0.00
Received By jpearson Date 2017-08-30 Time 10:37 Sent To  
Notes
2017-08-30 10:37:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE 3703.4,
 3901.6
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION PER CODE.
 PROVIDE FULL FLOOR PLAN, SHOW ON PLAN ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1
 4. PLAN IS REQUIRED TO BE SIGNED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-20 Cont ID  
Sent By tklarge Date 2017-12-20 Time 06:52 Rev Time 0.00
Received By tklarge Date 2017-12-06 Time 10:52 Sent To I
Notes
2017-12-07 10:52:22RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-29 Cont ID  
Sent By shill Date 2017-11-29 Time 10:36 Rev Time 0.00
Received By shill Date 2017-10-30 Time 13:13 Sent To I
Notes
2017-10-31 13:13:13R13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-15 Cont ID  
Sent By hmoser Date 2017-09-15 Time 09:34 Rev Time 0.00
Received By hmoser Date 2017-08-14 Time 12:09 Sent To  
Notes
2017-08-15 12:09:49R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-12-27 Cont ID  
Sent By cthroop Date 2017-12-27 Time 16:54 Rev Time 0.00
Received By cthroop Date 2017-12-27 Time 16:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-09-14 Cont ID  
Sent By cthroop Date 2017-09-14 Time 16:29 Rev Time 0.00
Received By cthroop Date 2017-09-14 Time 07:28 Sent To  
Notes
2017-09-14 16:30:39BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-11-29 Cont ID  
Sent By hmoser Date 2017-11-29 Time 09:40 Rev Time 0.00
Received By hmoser Date 2017-11-29 Time 09:16 Sent To B
Notes
2017-11-29 09:42:43NO MECHANICAL WORK BEING DONE ON THIS SITE. HM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By hmoser Date 2017-09-15 Time 09:32 Rev Time 0.00
Received By hmoser Date 2017-09-15 Time 09:32 Sent To  
Notes
2017-09-15 09:33:50NO AIR CONDITIONING PLAN SUBMITTED
 HM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-12-20 Cont ID  
Sent By tklarge Date 2017-12-20 Time 06:52 Rev Time 0.00
Received By tklarge Date 2017-12-20 Time 06:30 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-11-29 Cont ID  
Sent By tklarge Date 2017-11-29 Time 06:01 Rev Time 0.00
Received By tklarge Date 2017-11-29 Time 05:00 Sent To  
Notes
2017-11-29 06:01:111) AN AIR ADMITTANCE VALVE CANNOT BE USED TO VENT THE
 ADDED BATHROOM GROUP. THE VENT SYSTEM SERVING EACH
 BUILDING DRAIN SHALL HAVE AT LEAST ONE VENT PIPE THAT
 EXTENDS TO THE OUTDOORS. FBCR SEC.P3102.1.
 2) SHT. A3 NOTES THAT ALL PLUMBING LINES SHALL SLOPE A
 MINIMUM OF 1/8 INCH PER FOOT. PIPING 2 1/2 INCHES OR
 LESS SHALL BE SLOPED A MINIMUM OF 1/4 INCH PER FOOT PER
 FBCR SEC.P3005.4.2.
 3) THE WATER SUPPLY VALVES FOR THE STACKABLE WASHER AND
 DDRYER SHALL BE ACCESSIBLE. FBCR SEC.P2903.9.3.
 4) THE SANITARY RISER SUPPLIED BY THE PLUMBING
 CONTRACTOR NOTES CORE DRILLING THROUGH THE FOOTER. SHOW
 THE SIZE OF THE DRILLED OPENING. TWO COPIES OF A SIGNED
 AND SEALED LETTER FROM THE ARCHITECT OF RECORD SHALL BE
 SUBMITTED VERIFYING THAT THE CORE DRILLING OF THE
 FOOTING WILL NOT COMPROMISE THE STRUCTURAL INTEGRITY OF
 THE FOOTING FOR HANDLING ALL IMPOSED LOADS.FBCR SEC.
 R301, FBCR SEC. R403.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-08-29 Cont ID  
Sent By thunt Date 2017-08-29 Time 15:13 Rev Time 0.00
Received By thunt Date 2017-08-29 Time 15:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-11-16 Cont ID  
Sent By ajones Date 2017-11-16 Time 15:39 Rev Time 0.00
Received By ajones Date 2017-11-06 Time 16:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-17 Cont ID  
Sent By njwira Date 2017-08-17 Time 16:37 Rev Time 0.00
Received By njwira Date 2017-08-17 Time 16:19 Sent To  
Notes
2017-08-17 16:38:118/17/17- FAILED
  
 MUST INCLUDE A SITE PLAN AND SURVEY TO SCALE
 MUST INCLUDE BUILDING ELEVATIONS
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  