Plan Review Details - Permit 17080671
Plan Review Stops For Permit 17080671
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 17:04 Rev Time 0.00
Received By shill Date 2018-06-16 Time 17:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-11-27 Cont ID  
Sent By shill Date 2017-11-27 Time 18:23 Rev Time 0.00
Received By shill Date 2017-11-27 Time 18:23 Sent To  
Notes
2017-11-27 18:30:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM FIRST REVIEW:
  
 1. FBC A 404.2.4, SEE ALSO FIGURE 404.2.4.1(A), 18"
 MANEUVERING CLEARANCE REQUIRED FOR DOOR 1. SEE ALSO FBC
 A 203.9 REGARDING EMPLOYEE WORK AREAS. IF ARCHITECT
 FEELS THAT THIS DOOR IS EXEMPT, PLEASE SEND RATIONALE
 VIA EMAIL PRIOR TO RESUBMITTING. PLAN WILL BE REQUIRED
 TO BE REVISED TO INCLUDE RATIONALE IF THE 18"
 MANEUVERING CLEARANCE IS NOT PROVIDED.
  
 2ND REVIEW, ARCHITECT'S RESPONSE (A LETTER WHICH IS NOT
 SIGNED AND SEALED AND IS NOT A PART OF THE PERMIT
 DOCUMENTS) IS THAT THIS IS A CONVENIENCE DOOR AND
 DISABLED EMPLOYEES CAN USE ANOTHER ROUTE. PLEASE SEE
 FIRST REVIEW WHICH REQUESTED THAT THIS RATIONALE SENT
 VIA EMAIL FOR PRELIMINARY REVIEW AND TO BE PUT ON THE
 PLAN.
  
 PLEASE SEE FBC A 206.2.8 AND 402. BASED ON ARCHITECT'S
 RESPONSE, IT APPEARS THAT THIS DOOR NEEDS TO COMPLY
 WITH THE REQUIREMENTS OF 404. IF ARCHITECT WOULD LIKE
 TO CLAIM ONE OF THE EXCEPTIONS IN 206.2.8, PLEASE SEND
 RATIONAL VIA EMAIL TO AVOID A 3RD REVIEW SUBMITTAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-03 Cont ID  
Sent By shill Date 2017-10-03 Time 07:45 Rev Time 0.00
Received By shill Date 2017-10-03 Time 07:39 Sent To  
Notes
2017-10-03 07:52:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC A 404.2.4, SEE ALSO FIGURE 404.2.4.1(A), 18"
 MANEUVERING CLEARANCE REQUIRED FOR DOOR 1. SEE ALSO FBC
 A 203.9 REGARDING EMPLOYEE WORK AREAS. IF ARCHITECT
 FEELS THAT THIS DOOR IS EXEMPT, PLEASE SEND RATIONALE
 VIA EMAIL PRIOR TO RESUBMITTING. PLAN WILL BE REQUIRED
 TO BE REVISED TO INCLUDE RATIONALE IF THE 18"
 MANEUVERING CLEARANCE IS NOT PROVIDED.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-21 Cont ID  
Sent By jpearson Date 2018-06-21 Time 10:13 Rev Time 0.00
Received By jpearson Date 2018-06-21 Time 08:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-12-01 Cont ID  
Sent By jpearson Date 2017-12-01 Time 12:28 Rev Time 0.00
Received By jpearson Date 2017-12-01 Time 10:47 Sent To I
Notes
2017-12-01 12:28:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE ARE ELECTRICAL SHEETS,E1, E2, E3, ATTACHED AT
 REAR OF PLAN THAT ARE NOT SIGNED/SEALED. THERE ARE ALSO
 OTHER SHEETS FOR OTHER DISCIPLINES THAT ARE NOT
 SIGNED/SEALED. PER THE WPB AMENDMENTS TO THE FBC, PLAN
 IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. PROVIDE
 CORRECTION. FBC 107.2.1, FS 471, 481
 2. PANEL SCHEDULE SHOWS A 120 AMP BREAKER FOR THE X-RAY
 MACHINE. THIS IS NOT A STANDARD SIZE FOR BREAKERS. IS
 THIS POSSIBLY A TYPO? OR WILL THIS BE A SPECIAL ORDER
 BREAKER. IF SO, PROVIDE SPEC SHEET. PLEASE CLARIFY
 AND/OR CORRECT. NEC 110.3; FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-10-13 Cont ID  
Sent By jleahy Date 2017-10-13 Time 11:04 Rev Time 0.00
Received By jleahy Date 2017-10-13 Time 11:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-06-11 Cont ID  
Sent By pleduc Date 2018-06-11 Time   Rev Time 0.00
Received By pleduc Date 2018-06-11 Time 11:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-16 Cont ID  
Sent By pleduc Date 2017-11-16 Time   Rev Time 0.00
Received By pleduc Date 2017-11-15 Time 16:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-04 Cont ID  
Sent By pleduc Date 2017-10-04 Time   Rev Time 0.00
Received By pleduc Date 2017-10-03 Time 14:40 Sent To  
Notes
2017-10-04 10:09:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 4) ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-23 Cont ID  
Sent By gjohnson Date 2018-06-23 Time 12:39 Rev Time 0.00
Received By gjohnson Date 2018-06-01 Time 15:22 Sent To  
Notes
2018-06-04 15:22:55B34

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-01 Cont ID  
Sent By jpearson Date 2017-12-01 Time 12:28 Rev Time 0.00
Received By jpearson Date 2017-11-14 Time 18:24 Sent To  
Notes
2017-11-14 18:24:11B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-13 Cont ID  
Sent By jleahy Date 2017-10-13 Time 11:05 Rev Time 0.00
Received By jleahy Date 2017-09-29 Time 15:17 Sent To  
Notes
2017-10-02 15:17:28B06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-10-03 Cont ID  
Sent By shill Date 2017-10-03 Time 07:39 Rev Time 0.00
Received By shill Date 2017-10-03 Time 07:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-10-11 Cont ID  
Sent By ccole Date 2017-10-11 Time 17:43 Rev Time 0.00
Received By ccole Date 2017-10-11 Time 15:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2018-06-23 Cont ID  
Sent By gjohnson Date 2018-06-23 Time 12:38 Rev Time 0.00
Received By gjohnson Date 2018-06-23 Time 12:38 Sent To  
Notes
2018-06-23 12:39:18REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: NO PLUMBING WORK SHOWN.
  
 1. MED GAS WORK REMOVED FROM PLAN.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2017-11-29 Cont ID  
Sent By gjohnson Date 2017-11-29 Time 12:06 Rev Time 0.00
Received By gjohnson Date 2017-11-29 Time 12:06 Sent To  
Notes
2017-11-29 12:08:45REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: NO PLUMBING WORK SHOWN.
  
 1. MED GAS WORK REMOVED FROM PLAN.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-10-06 Cont ID  
Sent By gjohnson Date 2017-10-06 Time 09:15 Rev Time 0.00
Received By gjohnson Date 2017-10-05 Time 16:30 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved