| Plan Review Stops For Permit 17080671 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-06-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-16 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-16 |
Time |
17:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-11-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-27 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-11-27 |
Time |
18:23 |
Sent To |
|
|
| Notes |
| 2017-11-27 18:30:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | FROM FIRST REVIEW: | | | | | | 1. FBC A 404.2.4, SEE ALSO FIGURE 404.2.4.1(A), 18" | | | MANEUVERING CLEARANCE REQUIRED FOR DOOR 1. SEE ALSO FBC | | | A 203.9 REGARDING EMPLOYEE WORK AREAS. IF ARCHITECT | | | FEELS THAT THIS DOOR IS EXEMPT, PLEASE SEND RATIONALE | | | VIA EMAIL PRIOR TO RESUBMITTING. PLAN WILL BE REQUIRED | | | TO BE REVISED TO INCLUDE RATIONALE IF THE 18" | | | MANEUVERING CLEARANCE IS NOT PROVIDED. | | | | | | 2ND REVIEW, ARCHITECT'S RESPONSE (A LETTER WHICH IS NOT | | | SIGNED AND SEALED AND IS NOT A PART OF THE PERMIT | | | DOCUMENTS) IS THAT THIS IS A CONVENIENCE DOOR AND | | | DISABLED EMPLOYEES CAN USE ANOTHER ROUTE. PLEASE SEE | | | FIRST REVIEW WHICH REQUESTED THAT THIS RATIONALE SENT | | | VIA EMAIL FOR PRELIMINARY REVIEW AND TO BE PUT ON THE | | | PLAN. | | | | | | PLEASE SEE FBC A 206.2.8 AND 402. BASED ON ARCHITECT'S | | | RESPONSE, IT APPEARS THAT THIS DOOR NEEDS TO COMPLY | | | WITH THE REQUIREMENTS OF 404. IF ARCHITECT WOULD LIKE | | | TO CLAIM ONE OF THE EXCEPTIONS IN 206.2.8, PLEASE SEND | | | RATIONAL VIA EMAIL TO AVOID A 3RD REVIEW SUBMITTAL. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-10-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-03 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-03 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2017-10-03 07:52:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FBC A 404.2.4, SEE ALSO FIGURE 404.2.4.1(A), 18" | | | MANEUVERING CLEARANCE REQUIRED FOR DOOR 1. SEE ALSO FBC | | | A 203.9 REGARDING EMPLOYEE WORK AREAS. IF ARCHITECT | | | FEELS THAT THIS DOOR IS EXEMPT, PLEASE SEND RATIONALE | | | VIA EMAIL PRIOR TO RESUBMITTING. PLAN WILL BE REQUIRED | | | TO BE REVISED TO INCLUDE RATIONALE IF THE 18" | | | MANEUVERING CLEARANCE IS NOT PROVIDED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-06-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-21 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-21 |
Time |
08:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-12-01 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-12-01 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-12-01 |
Time |
10:47 |
Sent To |
I |
|
| Notes |
| 2017-12-01 12:28:29 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. THERE ARE ELECTRICAL SHEETS,E1, E2, E3, ATTACHED AT | | | REAR OF PLAN THAT ARE NOT SIGNED/SEALED. THERE ARE ALSO | | | OTHER SHEETS FOR OTHER DISCIPLINES THAT ARE NOT | | | SIGNED/SEALED. PER THE WPB AMENDMENTS TO THE FBC, PLAN | | | IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND SEALED | | | BY THE PERSON RESPONSIBLE FOR THE DESIGN. PROVIDE | | | CORRECTION. FBC 107.2.1, FS 471, 481 | | | 2. PANEL SCHEDULE SHOWS A 120 AMP BREAKER FOR THE X-RAY | | | MACHINE. THIS IS NOT A STANDARD SIZE FOR BREAKERS. IS | | | THIS POSSIBLY A TYPO? OR WILL THIS BE A SPECIAL ORDER | | | BREAKER. IF SO, PROVIDE SPEC SHEET. PLEASE CLARIFY | | | AND/OR CORRECT. NEC 110.3; FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-10-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-10-13 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-10-13 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-06-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-06-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-06-11 |
Time |
11:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-15 |
Time |
16:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-10-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-10-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-10-03 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2017-10-04 10:09:26 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND | | | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY | | | CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | | | | 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | 4) ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-06-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-23 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-01 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-12-01 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-12-01 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-14 |
Time |
18:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-10-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-10-13 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-09-29 |
Time |
15:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2017-10-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-03 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-03 |
Time |
07:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2017-10-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-11 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-11 |
Time |
15:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2018-06-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-23 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-23 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2018-06-23 12:39:18 | REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: NO PLUMBING WORK SHOWN. | | | | | | 1. MED GAS WORK REMOVED FROM PLAN. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-29 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-29 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2017-11-29 12:08:45 | REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: NO PLUMBING WORK SHOWN. | | | | | | 1. MED GAS WORK REMOVED FROM PLAN. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2017-10-06 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-06 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-05 |
Time |
16:30 |
Sent To |
|
|
| Notes |
|
|