Plan Review Details - Permit 17080665
Plan Review Stops For Permit 17080665
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-07 Cont ID  
Sent By shill Date 2019-03-07 Time 15:51 Rev Time 0.00
Received By shill Date 2019-03-07 Time 15:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-06 Cont ID  
Sent By jwitmer Date 2017-09-06 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2017-09-06 Time 06:31 Sent To  
Notes
2017-09-06 06:50:36BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080665
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONSTRUCTION CO.
 TEL: 561-832-1616
 E-MAIL: [email protected] / ED HANRATTY
  
 2010 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. SEPT. 06/ 2017
 ACTION: DENIED
  
 1) EVAPCO?S WIND STRUCTURAL ANALYSIS REPORT, WIND
 COMPLIANCE FOR AT COOLING TOWERS IS A PAPER COPY THAT
 WAS SCANNED INTO THE COMPUTER WITH A SCANNED IN COPY OF
 A SIGNATURE AND SEAL. JAMES A. MARX, JR. PE FLORIDA
 LICENSE NO. 45024.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-03-07 Time   Rev Time 0.00
Received By shill Date 2019-03-07 Time 15:52 Sent To  
Notes
2019-03-07 15:52:29PAPER ORIGINALS TO CC DESK
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-19 Cont ID  
Sent By shill Date 2019-02-19 Time 13:17 Rev Time 0.00
Received By shill Date 2019-02-01 Time 08:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-09-06 Time   Rev Time 0.00
Received By cpuell Date 2017-08-25 Time 09:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-03-07 Cont ID  
Sent By ccole Date 2019-03-07 Time 16:40 Rev Time 0.00
Received By ccole Date 2019-03-07 Time 16:40 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-02-15 Cont ID  
Sent By ccole Date 2019-02-15 Time 16:29 Rev Time 0.00
Received By ccole Date 2019-02-15 Time 16:14 Sent To  
Notes
2019-02-15 16:33:542ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17080665
 2/15/19
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LETTER FROM ROBERT B. BAKER- GLOBAL PRODUCT
 MANAGER- COOLING TOWERS SHALL BE REVIEWED AND APPROVED
 BY THE ENGINEER OF RECORD- SECTION 107 WEST PALM BEACH
 AMENDMENTS TO THE FBC.
  
 2) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS- SEE
 COMMENT BELOW.
  
 2) THE LETTER FROM P.E. JAMES A. MARX JR CERTIFYING THE
 COOLING TOWER STRUCTURE AND ANCHORAGE DESIGN PER THE
 WIND STRUCTURAL ANALYSIS REPORT IS REQUIRED TO BE
 ELECTRONICALLY SIGNED AND SEALED- SECTION 61G15-23.005
 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-06 Cont ID  
Sent By ccole Date 2017-09-06 Time 10:19 Rev Time 0.00
Received By ccole Date 2017-09-06 Time 10:19 Sent To  
Notes
2017-09-06 11:04:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080665
 9/6/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE VERIFICATION THE COOLING TOWER IS LISTED IN
 ACCORDANCE WITH UL 1995- SECTION 908.1.
  
 2) THE LETTER FROM P.E. JAMES A. MARX JR CERTIFYING THE
 COOLING TOWER STRUCTURE AND ANCHORAGE DESIGN PER THE
 WIND STRUCTURAL ANALYSIS REPORT IS REQUIRED TO BE
 ELECTRONICALLY SIGNED AND SEALED- SECTION 61G15-23.005
 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-03-07 Cont ID  
Sent By ccole Date 2019-03-07 Time 16:40 Rev Time 0.00
Received By ccole Date 2019-03-07 Time 16:40 Sent To  
Notes
2019-02-01 14:58:092/1/19 HARD COPIES SUBMITTED, LOCATED IN LIBRARY. LEM