Plan Review Details - Permit 17080653
Plan Review Stops For Permit 17080653
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-08-17 Cont ID  
Sent By jwitmer Date 2017-08-17 Time 12:01 Rev Time  
Received By jwitmer Date 2017-08-17 Time 06:45 Sent To  
Notes
2017-08-17 12:28:012014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080653
 ADD: 8170 OKEECHOBEE BLVD. SUITE: 06
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: 561-358-4140
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 17, 2017
 ACTION: BUILDING PROVISO
  
 1) SHEET 2 OF 3 PROVIDES A HVAC EQUIPMENT ROOF CURB W/
 ADAPTOR DETAIL AND CALCULATIONS. THERE IS A NOT FOR THE
 BADGER CURBS ARE GOING TO CREATE A CUSTOM CURB ADAPTOR
 AND TO PROVIDE WIND LOAD CERTIFICATION FOR EACH UNIT.
 SUBMIT TO ARCHITECT AND ENGINEER FOR REVIEW BEFORE
 PROVIDING TO FIELD INSPECTOR AT TIME OF INSPECTION.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-22 Cont ID  
Sent By jpearson Date 2017-08-22 Time 08:26 Rev Time 0.00
Received By jpearson Date 2017-08-22 Time 08:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-16 Cont ID  
Sent By scaldero Date 2017-08-16 Time 09:32 Rev Time 0.00
Received By scaldero Date 2017-08-16 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-08-31 Time 11:26 Sent To  
Notes
2017-09-01 11:26:28B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-30 Cont ID  
Sent By eschneid Date 2017-08-30 Time 08:40 Rev Time 0.00
Received By eschneid Date 2017-08-14 Time 15:43 Sent To  
Notes
2017-08-15 15:44:03B05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-09-19 Cont ID  
Sent By ccole Date 2017-09-19 Time 07:58 Rev Time 0.00
Received By ccole Date 2017-09-19 Time 07:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-25 Cont ID  
Sent By ccole Date 2017-08-25 Time 12:52 Rev Time 0.00
Received By ccole Date 2017-08-25 Time 12:52 Sent To  
Notes
2017-08-25 12:59:041ST REVIEW FBC-2014 MECHANICAL
 PERMIT # 17080653
 8/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF THE NEW 5.0-TON RTU- SECTION 606.2.1. AN
 EXCEPTION TO THE REQUIREMENT CAN BE MADE IF
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM DOES
 NOT HAVE THE CAPACITY TO EXCEED 2000 CFMS OF SUPPLY
 AIR. PLEASE NOTE THAT THE AC SYSTEM INDICATES 1950
 CFRMS OF SUPPLY AIR HOWEVER THE PLAN INDICATES ONLY
 1350 CFMS OF AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-26 Cont ID  
Sent By gjohnson Date 2017-09-26 Time 09:00 Rev Time 0.00
Received By gjohnson Date 2017-09-26 Time 09:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-08-23 Cont ID  
Sent By gjohnson Date 2017-08-23 Time 18:17 Rev Time 0.00
Received By gjohnson Date 2017-08-23 Time 17:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-09-07 Cont ID  
Sent By eschneid Date 2017-09-07 Time 13:44 Rev Time 0.25
Received By eschneid Date 2017-09-07 Time 13:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-30 Cont ID  
Sent By eschneid Date 2017-08-30 Time 08:40 Rev Time 0.25
Received By eschneid Date 2017-08-30 Time 08:40 Sent To  
Notes
***NONE***