Plan Review Details - Permit 17080637
Plan Review Stops For Permit 17080637
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-11-17 Cont ID  
Sent By jgomez Date 2017-11-17 Time 16:03 Rev Time 0.00
Received By jgomez Date 2017-11-17 Time 15:05 Sent To  
Notes
2017-11-17 15:06:4911/16/17 REVISED PLANS SUBMITTED. JG.
  
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) EXTERIOR SWING DOORS AS SHOWN ON PLANS. NOA
 01-0122.09 SUBMITTED EXPIRED ON APRIL 25, 2007. NEED
 CURRENT NOA.
 2- ARCHITECT OF RECORD TO APPROVE IN WRITING ABOVE
 PRODUCT APPROVAL.
 3- SPECIFY ALL FRAMING MEMBERS AND CONNECTORS ON THE
 TYP. EXTERIOR WALL FRAMING DETAIL ON SHEET A-4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-11-14 Cont ID  
Sent By jgomez Date 2017-11-14 Time 18:22 Rev Time 0.00
Received By jgomez Date 2017-11-14 Time 11:53 Sent To  
Notes
2017-11-14 12:17:23RESIDENTIAL (R3) ALTERATION THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOWS AND TYPE AND SIZE OF PROPOSED BEDROOM WINDOWS
 TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS. SEC.
 704 OF FBC-EXISTING BUILDING, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. SIZES OF WINDOWS SHOWN ON THE
 FLOOR PLAN ON SHEET A-2 DON'T MATCH SIZES SHOWN ON THE
 EXTERIOR ELEVATIONS ON SHEET A-3. REVISE AS REQUIRED TO
 MATCH. MASTER BEDROOM AND BEDROOM #2 WINDOW SIZE SHOWN
 ON PLAN DON'T MATCH THOSE SHOWN ON THE ELEVATIONS.
 NOTE: THE ONLY WINDOW SIZES THAT COMPLY WITH ALL THE
 EGRESS REQUIREMENTS ARE THE 36" X 63" SINGLE HUNG
 WINDOW SPECIFIED FOR BEDROOM #2 ON THE EAST ELEVATION
 AND THE 36" X 72" SINGLE HUNG WINDOWS SPECIFIED FOR THE
 MASTER BEDROOM. THE OTHER WINDOW SIZES DON'T SEEM TO
 COMPLY WITH THE MIN. 24" CLEAR HEIGHT OPENING. REVISE
 PLANS AS REQUIRED.
  
 NOTE: ARCHITECT MAY BE CHARGED 4 TIMES THE PLAN REVIEW
 FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR
 MULTIPLE PLAN REVIEW REJECTIONS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR SWING DOORS AS SHOWN ON PLANS. NOA
 01-0122.09 SUBMITTED EXPIRED ON APRIL 25, 2007. NEED
 CURRENT NOA.
 RESPONSE: NO PRODUCT APPROVAL SUBMITTED AT THIS TIME.
 NOTE: THIS MAY BE SUBMITTED AFTER PERMIT IS ISSUED, BUT
 BEFORE INSPECTIONS TO AVOID CONFLICT/DELAYS.
  
 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES THAT WERE ALREADY SUBMITTED) AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE. REPEAT COMMENT.
  
 4- NEW SHEET T-1:
 A) THE CONSTRUCTION TYPE SPECIFIED UNDER THE LOCATION
 MAP IS INCORRECT. THIS IS A TYPE VB CONSTRUCTION NOT
 TYPE III. SEC. 602 FBC-5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT.
  
 B) AS REQUESTED ON PREVIOUS CHECKLIST THE SCOPE OF WORK
 WAS REVISED TO SAY ALTERATION LEVEL 3 INSTEAD OF LEVEL
 2. THIS WAS DONE, BUT THERE IS STILL REFERENCE FOR
 ALTERATION LEVEL 2 BELOW THE FRONT ELEVATION SHOWN ON
 THE UPPER RIGHT CORNER OF THIS DRAWING. CLARIFY/REVISE
 AS REQUIRED TO MATCH THE SCOPE OF WORK. SEC. 107.2.1
 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-19 Cont ID  
Sent By jgomez Date 2017-10-19 Time 15:51 Rev Time 0.00
Received By jgomez Date 2017-10-18 Time 15:38 Sent To  
Notes
2017-10-18 15:50:29RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- THERE ARE TWO STRUCTURES SHOWN ON PLANS SUBMITTED.
 THE MAIN HOUSE AND THE REAR STRUCTURE. NEED TO SUBMIT A
 PERMIT APPLICATION FOR EACH STRUCTURE. 105.1 AND SEC.
 107.2.1.4 CITY AMENDMENTS.
 RESPONSE: REVISED PLANS SPECIFY THAT REAR STRUCTURE IS
 GOING TO BE DEMOLISHED. NEED TO SUBMIT SEPARATE PERMIT
 APPLICATION FOR THE DEMOLITION OF THE REAR BUILDING.
 COORDINATE WITH THE HISTORIC PLANNER.
  
 2- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOWS AND TYPE AND SIZE OF PROPOSED BEDROOM WINDOWS
 TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS. SEC.
 704 OF FBC-EXISTING BUILDING, 5TH EDITION (2014).
 RESPONSE: SIZES OF WINDOWS SHOWN ON THE FLOOR PLAN ON
 SHEET A-2 DON'T MATCH SIZES SHOWN ON THE EXTERIOR
 ELEVATIONS ON SHEET A-3. REVISE AS REQUIRED TO MATCH.
 ALSO, TO AVOID CONFLICTS, PLEASE USE THE SAME FORMAT TO
 SPECIFY SIZE OF WINDOWS (FOR EXAMPLE 37"W X 63"H SINGLE
 HUNG WINDOWS). NOTE: THERE ARE SOME BEDROOM WINDOWS
 THAT DON'T SEEM TO COMPLY WITH THE EGRESS REQUIREMENTS.
 ALL BEDROOMS NEED TO COMPLY WITH THE EGRESS
 REQUIREMENTS. CLEARLY SHOW THE ACTUAL SIZE OF THE
 BEDROOM WINDOWS THAT COMPLY WITH THE EGRESS
 REQUIREMENTS SPECIFIED ON THE EGRESS WINDOWS NOTES ON
 SHEET A-2 AND A-3. SEE PGT SINGLE HUNG PRODUCT APPROVAL
 SUBMITTED FOR STANDARD SIZES.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR SWING DOORS AS SHOWN ON PLANS. NOA
 01-0122.09 SUBMITTED EXPIRED ON APRIL 25, 2007. NEED
 CURRENT NOA.
 RESPONSE: REPEAT COMMENT.
  
 B) CLARIFY IF NEW ROOFING IS GOING TO BE INSTALLED OR
 NOT. IF SO, THEN NEED TO PROVIDE PRODUCT APPROVAL. AND,
 CLEARLY MARK APPROVED ASSEMBLY TO BE INSTALLED AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 REQUIRED.
 RESPONSE: REPEAT COMMENT.
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES THAT WERE ALREADY SUBMITTED) AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE. REPEAT COMMENT.
  
 5- NEW SHEET T-1:
 A) ALTERATION LEVEL WAS CHANGED FROM LEVEL 3 TO LEVEL
 2. THE WORK AREA EXCEEDS 50 PERCENT OF THE AREA OF THE
 BUILDING. THEREFORE, THE ALTERATION LEVEL IS 3. REVISE
 AS REQUIRED. SEC. 505 FBC-EXISTING BUILDING, 5TH
 EDITION (2014).
  
 B) THE CONSTRUCTION TYPE SPECIFIED UNDER SITE DATA AND
 UNDER THE LOCATION MAP IS INCORRECT. THIS IS A TYPE VB
 CONSTRUCTION NOT TYPE III. SEC. 602 FBC-5TH EDITION
 (2014).
  
 6- SHEET A-4:
 A) POST BASE CONNECTOR "A1" IS NOT CLEAR. WHAT'S "HBC
 POST BASE"? CLEARLY SPECIFY SPECIFIC POST BASE MODEL TO
 BE USED AND PROVIDE CURRENT FLORIDA PRODUCT APPROVAL
 NUMBER.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 B) STUCCO ON WOOD FRAMED BUILDINGS REQUIRES 2 WATER
 RESISTIVE BARRIERS AS REQUIRED BY SEC. R703.6.3
 FBC-RESIDENTIAL. REVISE SPECIFICATIONS ON THE TYPICAL
 WALL SECTION AS REQUIRED.
  
 C) CLARIFY IF NEW ROOFING IS GOING TO BE INSTALLED OR
 NOT. IF SO, THEN NEED TO PROVIDE PRODUCT APPROVAL. FAC
 61G20-3.001. CLARIFY WHY BOTH WALL SECTIONS PROVIDE
 SPECIFICATIONS FOR THE FLAT ROOF. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 D) SPECIFY ALL FRAMING MEMBERS AND CONNECTORS ON THE
 TYPICAL EXTERIOR WALL FRAMING DETAIL. SEC. R301.1
 FBC-RESIDENTIAL.
  
 7- BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS
 (INCLUDING ALL THE MECHANICAL AND ELECTRICAL WORK SHOWN
 ON PLANS) THE VALUE DECLARED IN THE PERMIT APPLICATION
 IS TOO LOW. VALUE TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. CONTRACTOR TO UPDATE VALUE AND ADD THE FEES
 FOR THE DESIGN PROFESSIONAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By jgomez Date 2017-09-13 Time 16:14 Rev Time 0.00
Received By jgomez Date 2017-09-13 Time 10:59 Sent To  
Notes
2017-09-13 11:28:38RESIDENTIAL (R3) ALTERATIONS BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- THERE ARE TWO STRUCTURES SHOWN ON PLANS SUBMITTED.
 THE MAIN HOUSE AND THE REAR STRUCTURE. NEED TO SUBMIT A
 PERMIT APPLICATION FOR EACH STRUCTURE. SAME SET OF
 PLANS CAN BE USED FOR BOTH STRUCTURES. THERE IS NO NEED
 TO SUBMIT SEPARATE PLANS FOR EACH STRUCTURE. SEC. 105.1
 AND SEC. 107.2.1.4 CITY AMENDMENTS. NOTE: THE SEPARATE
 PERMITS ARE FOR PROPER INSPECTIONS OF EACH STRUCTURE
 AND FOR THE PROPER RECORD RETENTION.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG) FOR IMPACT FEES ASSESSMENT. BRING
 BACK COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF
 FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS IS FOR THE CONVERSION OF THE GARAGE TO
 HABITABLE AREA.
  
 3- SHEET CS-1:
 A) REAR STRUCTURE SHOWN ON THE SITE PLAN STATES "EXIST.
 ONE STORY PLAYROOM TO BE REMODELED 626 S.F.". ACCORDING
 TO CITY RECORDS THE REAR STRUCTURE IS A GARAGE AND
 HABITABLE AREA. THERE ARE NO CITY RECORDS SHOWING ANY
 PERMIT FOR THE PLAYROOM. REVISE PLANS AS REQUIRED. SHOW
 ALL WORK AS BEING PROPOSED NOT EXISTING. SAME COMMENT
 APPLIES TO FLOOR PLAN ON SHEET A-1 SEC. 105.1 AND SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) CLARIFY WHAT DOES "IMPORTANCE FACTOR = 1.21"
 SPECIFIED ON THE DESIGN LOAD SCHEDULE STANDS FOR? .
 DOES ARCHITECT MEANS RISK CATEGORY?. IF SO, SEE TABLE
 1604.5 FBC-BUILDING, 5TH EDITION (2014) FOR THE CORRECT
 RISK CATEGORY. REVISE AS REQUIRED.
  
 C) CLARIFY THE NOTE AT THE BOTTOM OF THE DESIGN LOAD
 SCHEDULE. WHY THE WINDOW AND DOOR MANUFACTURERS SHALL
 MULTIPLY THE DOORS AND WINDOWS GIVEN DESIGN PRESSURES
 BY THE APPROPRIATE FACTORS TO OBTAIN TEST PRESSURES?
 THIS IS NOT CLEAR. DOORS AND WINDOWS NEED TO MEET THE
 DESIGN PRESSURES THAT ARE CALCULATED BY THE ARCHITECT
 OF RECORD. THERE IS NO NEED TO OBTAIN THE TEST
 PRESSURES. THESE PRESSURES ARE USUALLY GIVEN IN THE
 PRODUCT APPROVAL. CLARIFY/REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) PROVIDE CORRECT SCOPE OF WORK AND ALTERATION LEVEL
 FOR THE REAR STRUCTURE. THIS IS NOT JUST ALTERATION
 LEVEL 3. THIS IS A "CHANGE OF USE" OF GARAGE TO
 HABITABLE SPACE. REVISE AS REQUIRED. SEC. 506
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 4- SHEET A-1:
 A) PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THE
 SECTIONS OF THE EXTERIOR WALLS TO BE REPAIRED,
 INCLUDING ALL FRAMING MEMBERS AND CONNECTORS. SEC.
 R301.1 FBC-RESIDENTIAL.5TH EDITION (2014).
  
 B) CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOWS AND TYPE AND SIZE OF PROPOSED BEDROOM WINDOWS
 TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF
 SEC. 704 OF FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 C) ARCHITECT TO PROVIDE SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE REQUIRED HEATING ON EACH ROOM OF
 THE PROPOSED PLAYROOM CONVERSION. SEC. R303.9
 FBC-RESIDENTIAL.
  
 5- SPECIFY ALL FRAMING MEMBERS AND CONNECTORS ON ALL
 EXTERIOR WALL FRAMING DETAILS ON SHEET A-3. SEC. R301.1
 FBC-RESIDENTIAL.
  
 6- CLARIFY IF SCOPE OF WORK INCLUDES RE-ROOFING. SEC.
 107.2.1 CITY AMENDMENTS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FLAT ROOF IF RE-ROOFING IS PART OF THE SCOPE OF
 WORK. COORDINATE WITH ITEM #6 ABOVE. CLEARLY IDENTIFY
 FLAT ROOF ASSEMBLY TO BE INSTALLED AND PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES.
  
 B) GLASS BLOCK AS SHOWN ON PLANS. NOTE: COORDINATE WITH
 HISTORIC PLANER IF GLASS BLOCK IS ALLOWED.
  
 C) INSULATED EXTERIOR SWING DOOR. JELD-WEN NOA
 01-0122.09 SUBMITTED EXPIRED ON APRIL 25, 2007. NEED
 CURRENT NOA.
  
 D) SLIDING WINDOWS A SHOWN ON PLANS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIC CONNECTOR OR
 ARCHITECT OF RECORD TO LIST THE CURRENT FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-27 Cont ID  
Sent By jpearson Date 2017-10-27 Time 12:38 Rev Time 0.00
Received By jpearson Date 2017-10-27 Time 12:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By jpearson Date 2017-08-30 Time 11:47 Rev Time 0.00
Received By jpearson Date 2017-08-30 Time 11:47 Sent To  
Notes
2017-08-30 11:47:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. PROVIDE PANEL
 SCHEDULE INDICATING ANY NEW OR ALTERED CIRCUITS, THE
 WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR
 GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE.
 NEC 210.8, 210.12, 215.5, 408.4; FBC RE3706.2, RE3902FS
 471.003(2)(H); 471.025; FBC 107.2.1, 107.3.5
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-11-28 Cont ID  
Sent By fmittner Date 2017-11-28 Time 13:24 Rev Time 0.00
Received By fmittner Date 2017-11-28 Time 13:24 Sent To  
Notes
2017-11-14 17:46:16NEW DRAWINGS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-10-11 Cont ID  
Sent By fmittner Date 2017-10-11 Time 14:50 Rev Time 0.00
Received By fmittner Date 2017-10-11 Time 14:50 Sent To  
Notes
2017-10-11 14:50:48SEPERATE PERMIT REQUIRED FOR DEMO OF REAR BUILDING

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-08-25 Cont ID  
Sent By fmittner Date 2017-08-25 Time 09:49 Rev Time 0.00
Received By fmittner Date 2017-08-25 Time 09:49 Sent To  
Notes
2017-08-25 09:51:13FLOOR PLANS AND ELEVATIONS DO NOT MATCH FOR WINDOW
 STYLES/OPENINGS. NO NEW GLASS BLOCK PERMITTED, ALL
 WINDOWS TO BE SH, VERTICALLY ORIENTED WITH RAISED
 EXTERIOR MUNTINS.
  
 QUESTIONS, CONTACT:
  
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 (561) 822-1457

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-28 Cont ID  
Sent By cpuell Date 2017-11-28 Time 14:57 Rev Time 0.00
Received By cpuell Date 2017-11-08 Time 13:21 Sent To  
Notes
2017-11-09 13:21:55R12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-27 Cont ID  
Sent By jpearson Date 2017-10-27 Time 12:38 Rev Time 0.00
Received By jpearson Date 2017-10-02 Time 14:28 Sent To  
Notes
2017-10-03 14:28:54R35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-13 Cont ID  
Sent By jgomez Date 2017-09-13 Time 16:32 Rev Time 0.00
Received By jgomez Date 2017-08-14 Time 09:31 Sent To  
Notes
2017-08-15 09:32:12R02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-10-18 Cont ID  
Sent By jgomez Date 2017-10-18 Time 16:46 Rev Time 0.00
Received By jgomez Date 2017-10-18 Time 16:46 Sent To  
Notes
2017-10-18 16:47:21ACCORDING TO PLANS REAR STRUCTURE IS GOING TO BE
 DEMOLISHED. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By jgomez Date 2017-09-13 Time 11:32 Rev Time 0.00
Received By jgomez Date 2017-09-13 Time 11:28 Sent To  
Notes
2017-09-13 11:34:581- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG) FOR IMPACT FEES ASSESSMENT. BRING
 BACK COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF
 FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS IS FOR THE CONVERSION OF THE GARAGE TO
 HABITABLE AREA.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-10-26 Cont ID  
Sent By hmoser Date 2017-10-26 Time 13:32 Rev Time 0.00
Received By hmoser Date 2017-10-26 Time 13:03 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-10-27 Cont ID  
Sent By jgomez Date 2017-10-19 Time 17:20 Rev Time 0.00
Received By jpearson Date 2017-10-19 Time 16:35 Sent To  
Notes
2017-10-27 12:44:37ADDED "N" STATUS TO THIS STEP BECAUSE IT WAS ORIGINALLY
 LEFT BLANK AND IT HAS BEEN APPROVED AT A LATER DATE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-09-13 Cont ID  
Sent By jgomez Date 2017-09-13 Time 16:12 Rev Time 0.00
Received By jgomez Date 2017-09-13 Time 16:12 Sent To  
Notes
2017-09-13 16:13:17NO MECHANICAL WORK SHOWN. ANY MECHANICAL WORK REQUIRES
 COMPLETE INFORMATION UNDER SEPARATE PERMIT. JG.

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-11-17 Cont ID  
Sent By jgomez Date 2017-11-17 Time 16:03 Rev Time 0.00
Received By jgomez Date 2017-11-17 Time 15:42 Sent To  
Notes
2017-11-17 16:03:15NEW PLANS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-11-14 Cont ID  
Sent By jgomez Date 2017-11-14 Time 18:29 Rev Time 0.00
Received By jgomez Date 2017-11-14 Time 18:29 Sent To  
Notes
2017-11-14 17:47:55NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-13 Cont ID  
Sent By lcrespo Date 2017-10-13 Time 14:36 Rev Time 0.00
Received By lcrespo Date 2017-10-13 Time 14:35 Sent To  
Notes
2017-10-13 14:37:5010/13/17 APPROVED SUB PLUMBING PERMIT APPLICATION AND
 PLANS WILL BE REQUIRED LAC
2017-10-02 14:31:00NEW SET OF PLANS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-08-29 Cont ID  
Sent By thunt Date 2017-08-29 Time 14:02 Rev Time 0.00
Received By thunt Date 2017-08-29 Time 13:44 Sent To  
Notes
2017-08-29 14:03:05SUB PLUMBING PERMIT APPLICATION AND PLANS WILL BE
 REQUIRED

Review Stop Z ZONING
Rev No 3 Status P Date 2017-11-28 Cont ID  
Sent By fmittner Date 2017-11-28 Time 13:24 Rev Time 0.00
Received By fmittner Date 2017-11-28 Time 13:24 Sent To  
Notes
2017-11-17 17:23:23NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-10-11 Cont ID  
Sent By fmittner Date 2017-10-11 Time 14:51 Rev Time 0.00
Received By fmittner Date 2017-10-11 Time 14:51 Sent To  
Notes
2017-10-02 14:31:24NEW SET OF PLANS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-25 Cont ID  
Sent By fmittner Date 2017-08-25 Time 09:49 Rev Time 0.00
Received By fmittner Date 2017-08-25 Time 09:49 Sent To  
Notes
***NONE***