Plan Review Details - Permit 17080563
Plan Review Stops For Permit 17080563
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-09-26 Cont ID  
Sent By rmcdouga Date 2017-09-26 Time 09:16 Rev Time 0.00
Received By rmcdouga Date 2017-09-26 Time 09:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-29 Cont ID  
Sent By rmcdouga Date 2017-08-29 Time 18:52 Rev Time 0.00
Received By rmcdouga Date 2017-08-29 Time 18:47 Sent To  
Notes
2017-08-29 18:52:21PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE AMERICAST GENERATOR PAD DOCUMENTS ARE REQUIRED
 TO HAVE THE FLORIDA ENGINEER'S SEAL AND ORIGINAL
 HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE
 NOT ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES
 ARE ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED
 PLANS AND DOCUMENTS. NOTE: THE ENGINEER ON THE PAD
 DOCUMENTS, RONALD H. WILSON P.E. HAS HAD HIS LICENSE
 REVOKED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By rmcdouga Date 2017-08-22 Time 10:33 Rev Time 0.00
Received By rmcdouga Date 2017-08-22 Time 10:30 Sent To P
Notes
2017-08-22 10:33:38PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE AMERICAST GENERATOR PAD DOCUMENTS ARE REQUIRED
 TO HAVE THE FLORIDA ENGINEER'S SEAL AND ORIGINAL
 HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE
 NOT ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES
 ARE ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED
 PLANS AND DOCUMENTS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-18 Cont ID  
Sent By jleahy Date 2017-08-18 Time 14:40 Rev Time 0.00
Received By jleahy Date 2017-08-18 Time 14:40 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-08-28 Cont ID  
Sent By tklarge Date 2017-08-28 Time 12:04 Rev Time 0.00
Received By tklarge Date 2017-08-28 Time 05:51 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2017-08-23 Cont ID  
Sent By tklarge Date 2017-08-23 Time 05:48 Rev Time 0.00
Received By tklarge Date 2017-08-23 Time 05:22 Sent To  
Notes
2017-08-23 05:49:28GAS IS APPROVED FOR GENERATOR ONLY.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-09-26 Cont ID  
Sent By rmcdouga Date 2017-09-26 Time 09:16 Rev Time 0.00
Received By rmcdouga Date 2017-09-20 Time 14:28 Sent To  
Notes
2017-09-22 14:28:18RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-29 Cont ID  
Sent By rmcdouga Date 2017-08-29 Time 18:52 Rev Time 0.00
Received By rmcdouga Date 2017-08-23 Time 11:00 Sent To  
Notes
2017-08-25 11:00:45RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-23 Cont ID  
Sent By tklarge Date 2017-08-23 Time 05:49 Rev Time 0.00
Received By tklarge Date 2017-08-11 Time 15:40 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By tklarge Date 2017-08-23 Time 05:49 Rev Time 0.00
Received By njwira Date 2017-08-14 Time 16:42 Sent To  
Notes
***NONE***