Plan Review Details - Permit 17080546
Plan Review Stops For Permit 17080546
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By shill Date 2017-10-25 Time 06:21 Rev Time 0.00
Received By shill Date 2017-10-24 Time 17:47 Sent To  
Notes
2017-10-25 06:28:49****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. CONTACT ENGINEERING DEPARTMENT REGARDING NEW CIVIL
 SHEETS (E17040016).
  
 2. CIVIL PAGES SUBMITTED WITH THIS REVISION APPEAR TO
 BE REQUIRED TO BE SUBMITTED WITH THE PAVING PERMIT
 APPLICATION 17021166, PLEASE SUBMIT AS A "RESUBMITTAL".
 DO NOT HAVE THE PERMIT ISSUED AT THIS TIME.
  
 3. INFORMATIONAL ONLY - APPLICANT ALSO HAS A LANDSCAPE
 PERMIT WHICH IS AT THE FRONT COUNTER READY FOR PICKUP
 (NEEDS APPLICATION AND FEES PAID), 17021164.
  
 4. SEE ISSUED PERMIT (MASTER SHELL PERMIT #17021163),
 PAGE S-TD1, SEPARATE PERMIT IS REQUIRED FOR DUMPSTER
 ENCLOSURE, FBC 107. PLEASE REMOVE THIS PAGE AND SUBMIT
 A SEPARATE PERMIT APPLICATION.
  
 5. SEE ISSUED PERMIT (MASTER SHELL PERMIT #17021163), A
 ROOF PERMIT IS REQUIRED PRIOR TO COMMENCEMENT OF ANY
 ROOFING WORK.
  
 6. INTERIOR BUILDOUT PERMIT APPLICATION #17031082 WAS
 ON HOLD DUE TO THE MASTER SHELL PERMIT (17021163) NOT
 YET ISSUED. THIS CAN NOW BE ISSUED WITH A LETTER OF
 AGREEMENT BETWEEN THE TWO CONTRACTORS (SHELL,
 INTERIOR). OR, APPLICANT CAN WAIT UNTIL WORK UNDER THIS
 PERMIT IS COMPLETE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-16 Cont ID  
Sent By shill Date 2017-08-16 Time 15:10 Rev Time 0.00
Received By shill Date 2017-08-16 Time 15:10 Sent To  
Notes
2017-08-16 15:56:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS471. CIVIL PAGES ARE NOT SIGNED AND DATED.
  
 2. FBC B TABLE 1607.1(26), ROOFS SUBJECT TO MAINTENANCE
 WORKERS TO BE DESIGNED TO 300# CONCENTRATED LIVE LOAD.
 EITHER REVISE PLAN AND CALCULATIONS ACCORDINGLY OR
 CONTACT ME TO DISCUSS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-02 Cont ID  
Sent By jpearson Date 2017-11-02 Time 11:50 Rev Time 0.00
Received By jpearson Date 2017-11-02 Time 11:50 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-21 Cont ID  
Sent By jleahy Date 2017-08-21 Time 14:19 Rev Time 0.00
Received By jpearson Date 2017-08-21 Time 14:19 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2017-11-14 Cont ID  
Sent By squinone Date 2017-11-14 Time   Rev Time 0.00
Received By squinone Date 2017-11-07 Time   Sent To I
Notes
2017-11-14 15:15:55CIVIL PLANS WILL BE REVIEWED THROUGH ENGINEERING
 PERMIT, E170040016. PLEASE SUBMIT THE LATEST PLAN SET
 TO ENGINEERING.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-10-25 Cont ID  
Sent By squinone Date 2017-10-25 Time   Rev Time 0.00
Received By squinone Date 2017-10-25 Time   Sent To  
Notes
2017-10-25 10:21:59ADDRESS BUILDING COMMENTS. CIVIL PLANS WILL BE REVIEWED
 THROUGH ENGINEERING PERMIT, E170040016.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By pleduc Date 2017-10-17 Time   Rev Time 0.00
Received By pleduc Date 2017-10-17 Time 11:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-18 Cont ID  
Sent By wjolin Date 2017-08-18 Time   Rev Time 0.00
Received By pleduc Date 2017-08-18 Time 11:14 Sent To  
Notes
2017-08-18 11:23:00REVISION REVIEW
  
 APPOVED FOR SHELL ONLY. FUTURE TENANT SPACE BUILDOUTS
 SHALL REQUIRE SEPARATE PERMITS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-14 Cont ID  
Sent By cpuell Date 2017-11-14 Time 17:42 Rev Time 0.00
Received By cpuell Date 2017-11-02 Time 13:31 Sent To  
Notes
2017-11-03 13:31:49RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-02 Cont ID  
Sent By jpearson Date 2017-11-02 Time 11:50 Rev Time 0.00
Received By jpearson Date 2017-10-13 Time 14:49 Sent To  
Notes
2017-10-16 14:54:42C30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-25 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-10 Time 10:02 Sent To  
Notes
2017-08-11 10:02:30C16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-30 Cont ID  
Sent By ccole Date 2017-10-30 Time 17:07 Rev Time 0.00
Received By ccole Date 2017-10-30 Time 17:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-25 Cont ID  
Sent By ccole Date 2017-08-25 Time 10:12 Rev Time 0.00
Received By ccole Date 2017-08-25 Time 10:05 Sent To  
Notes
2017-08-25 10:19:461ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080546
 8/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 MINI SPLIT AC SYSTEM- SECTION 312.
  
 2) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLER- SECTION 307.
  
 3) THE PLAN SHEETS MUST BE PLACED IN SETS THAT ARE
 NEATLY BOUND TOGETHER FOR REVIEW- SECTION 107.2.1.4 WPB
 AMENDMENTS TO THE FBC
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-11-07 Cont ID  
Sent By gjohnson Date 2017-11-07 Time 16:31 Rev Time 0.00
Received By gjohnson Date 2017-11-07 Time 16:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-10-30 Cont ID  
Sent By thunt Date 2017-10-30 Time 14:39 Rev Time 0.00
Received By gjohnson Date 2017-10-30 Time 14:39 Sent To  
Notes
2017-10-30 15:16:101ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. A SEPARATE PERMIT IS REQUIRED FOR BACKFLOWS PER WPB
 UTILITIES DEPARTMENT. PLEASE PLACE NOTE ON PLAN. PER
 WPB AMEND TO FBC 107.2.1
  
 2. SHT. P-2.0 SHOWS ROOF DRAIN, OVER FLOW DRAINS AND
 RAIN WATER LEADERS SHT. P-3.0 SHOWS SCUPPER DRAIN AND
 EMERGENCY SCUPPERS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 3. PLEASE PROVIDE DETAIL MAIN SCUPPER AND EMERGENCY
 SCUPPER SHALL COMPLY WITH FBC PL TABLE 1106.7 AND
 1108.3
  
 4. SHT. P-2.0 SHOWS SQFT FOR ALL 4 OF THE ROOF DRAINS
 AS 2431SQFT SHT. P3.0 ONLY 3 SUPPERS ONLY 1 AT 3200SQFT
 1 AT 3100SQFT AND 1 AT 200SQFT PLEASE CLARIFY
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-08-23 Cont ID  
Sent By tklarge Date 2017-08-23 Time 16:02 Rev Time 0.00
Received By thunt Date 2017-08-23 Time 15:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By llouie Date 2017-10-26 Time   Rev Time 0.00
Received By llouie Date 2017-10-26 Time 16:40 Sent To  
Notes
2017-10-26 17:50:51ZONING PROVISOS:
  
 1.) THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF FDOT
 RIGHT-OF-WAY IMPROVEMENTS (I.E. LANDSCAPING,
 IRRIGATION, PAVING AND PLANTERS) ON S. DIXIE HWY. A
 SEPARATE PERMIT IS REQUIRED FROM FDOT.
  
 2.) BICYCLE RACK AND PAD SHALL COMPLY WITH THE MINIMUM
 DIMENSIONS REQUIRED BY THE CITY'S BICYCLE PARKING
 STANDARDS.
  
 3.) SEPARATE PERMIT REQUIRED FOR LANDSCAPE
 IMPROVEMENTS/MODIFICATIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-15 Cont ID  
Sent By llouie Date 2017-08-15 Time   Rev Time  
Received By llouie Date 2017-08-15 Time   Sent To  
Notes
2017-08-15 15:55:01** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE PROPOSED NEW LOCATION FOR THE BICYCLE RACK IS
 NOT ACCEPTABLE, AS IT DOES NOT MEET THE CITY'S MINIMUM
 STANDARDS FOR THE LOCATION OF A BICYCLE RACK. PLEASE
 RELOCATE BICYCLE RACK TO ITS ORIGINAL APPROVED
 LOCATION.
  
 2.) PROVIDE DIMENSIONS FOR THE DUMPSTER ENCLOSURE. THE
 CITY HAS MINIMUM DIMENSIONAL REQUIREMENTS AND
 SPECIFICATIONS FOR A DUMPSTER ENCLOSURE. APPROVAL WILL
 ALSO BE REQUIRED FOR THE SANITATION DEPARTMENT. [ZLDR
 S.94-315]
  
 NOTES:
  
 * THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF FDOT
 RIGHT-OF-WAY IMPROVEMENTS (I.E. LANDSCAPING,
 IRRIGATION, PAVING AND PLANTERS) ON SOUTH DIXIE HWY. A
 SEPARATE PERMIT IS REQUIRED FROM FDOT.
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  