Plan Review Details - Permit 17080513
Plan Review Stops For Permit 17080513
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2017-11-14 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-08 Time 14:41 Sent To  
Notes
2017-11-09 14:41:28RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-10-24 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-19 Time 13:31 Sent To  
Notes
2017-10-20 13:31:29RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-10-17 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-13 Time 13:55 Sent To  
Notes
2017-10-16 13:55:27RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-16 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-10 Time 14:11 Sent To  
Notes
2017-08-11 14:11:50ROUTED TO MECH INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-11-14 Cont ID  
Sent By ccole Date 2017-11-14 Time 09:57 Rev Time 0.00
Received By ccole Date 2017-11-14 Time 09:09 Sent To  
Notes
2017-11-14 09:58:51MECHANICAL PROVISOS:
  
 1) STAIRWELL PRESSURIZATION TESTS
 REQUIRED FOR FINAL APPROVAL .
 2) FAN PULLEY AND BELT MODIFICATIONS
 TO BE CHECKED IN FIELD BY MANUFACTURER?S
 REPRESENTATIVE
  
 CCOLE- 11/14/17
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-10-24 Cont ID  
Sent By ccole Date 2017-10-24 Time 12:41 Rev Time 0.00
Received By ccole Date 2017-10-24 Time 12:41 Sent To  
Notes
2017-10-24 13:10:203RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17080513
 10/24/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO THE PREVIOUS REVIEW COMMENT REQUIRING
 EACH PRESSURIZATION FAN TO BE EQUIPPED WITH TWO BELTS,
 THE ENGINEER OF RECORD HAS PROVIDED A RESPONSE AND ALSO
 PLACED NOTES ON THE PLAN STATING THAT THE BELT DRIVES
 ON THE FANS WILL BE MODIFIED IN THE FIELD TO ACCOMODATE
 THE REQUIRED TWO BELTS ON THE PULLEY.
 IN ORDER FOR THE PROPOSED MODIFICATION TO BE APPROVED,
 PLEASE PROVIDE THE FOLLOWING ITEMS:
  
 A) MANUFACTURER'S PRODUCT SUBMITTAL FOR THE FAN MODEL
 THAT IS FACTORY EQUIPPED WITH TWO BELTS.
 B) MODIFICATION INSTRUCTIONS FROM THE MANUFACTURER'S
 TECHNICAL DEPARTMENT TO CONVERT THE SINGLE-BELTED FANS
 IN THE FIELD.
 C) A LETTER FROM THE MANUFACTURER'S TECHNICAL
 DEPARTMENT AUTHORIZING AND OUTLINING THE FIELD
 MODIFICATION AND TESTING PROCESS.
 D) A LETTER FORM THE MANUFACTURER STATING THAT THE
 WARRANTIES FOR THE FANS WILL REMAIN INTACT.
 E) SHOP DRAWING STAMPS ON THE MANUFACTURER'S SUBMITTALS
 BY THE ENGINEER OF RECORD JOHN T.BOYER P.E, AND A
 SIGNED AND SEALED LETTER FROM BOYER CERTIFYING THE
 PROPOSED MODIFICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-10-17 Cont ID  
Sent By ccole Date 2017-10-17 Time 11:29 Rev Time 0.00
Received By ccole Date 2017-10-17 Time 11:29 Sent To  
Notes
2017-10-17 11:33:272ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17080513
 10/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE STAIR PRESSURIZATION FANS SHALL HAVE 1.5 TIMES
 THE NUMBER OF BELTS REQUIRED FOR THE DESIGN DUTY WITH
 THE MINIMUM NUMBER OF BELTS BEING TWO- SECTION
 513.10.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-16 Cont ID  
Sent By ccole Date 2017-08-16 Time 07:40 Rev Time 0.00
Received By ccole Date 2017-08-15 Time 17:37 Sent To  
Notes
2017-08-16 08:29:091ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080513
 8/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED CURB FLASHING DETAIL FROM RAY
 ENGINEERING DOES NOT APPEAR TO BE COMPATIBLE WITH THE
 FAN SUBMITTAL FROM REVERSOMATIC WHICH SHOWS THE FAN
 SUPPORT LEGS ATTACHED TO A CONCRETE BASE. IN ADDITION
 THE ENGINEERING SUBMITTAL IS A COPY OF AN ORIGINAL
 SUBMITTAL BEARING A 10/27/15 DATE. PLEASE SEE SECTION
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE WHICH REQUIRES
  
 ENGINEERS TO PROVIDE ORIGINAL SIGNATURES AND SEALS TO
 CERTIFY THEIR WORK. ALSO LACKING FROM THE SUBMITTAL IS
 THE ENGINEER'S WIND DESIGN CRITERIA FOR INSTALLATION OF
 THE FANS- WIND SPEED, EXPOSURE CATEGORY, RISK CATEGORY,
 HEIGHT ABOVE GRADE, DESIGN PRESSURES ETC.- SEE SECTION
 1609 FBC-14 BUILDING.
  
 2) ADDITIONAL CONFLICTS IN THIS SUBMITTAL: A) THE
 PERMIT APPLICATION INDICATES 3 FANS TO BE REPLACED BUT
 THE REVERSOMATIC SUBMITTAL HAS HANDWRITTEN NOTES THAT
 APPEAR TO INDICATE 7 FANS WILL BE INSTALLED. B) THE
 SUBMITTAL FROM RAY ENGINEERING INDICATES THE FANS WILL
 HAVE TOTAL CAPACITIES OF 20,000 CFMS, HOWEVER THE
 SUBMITTAL FROM REVERSOMATIC INDICATES THE FANS WILL
 EITHER BE 10,000
  
 OR 14,000 CFMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  