Plan Review Details - Permit 17080502
Plan Review Stops For Permit 17080502
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-03-19 Cont ID  
Sent By cthroop Date 2018-03-19 Time 07:31 Rev Time 0.00
Received By cthroop Date 2018-03-19 Time 07:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-02-26 Cont ID  
Sent By cthroop Date 2018-02-26 Time 11:11 Rev Time 0.00
Received By cthroop Date 2018-02-26 Time 11:07 Sent To  
Notes
2018-02-26 11:13:17BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 REPEAT COMMENT FROM 3RD REVIEW
  
 1. PROVIDE SITE PLAN. IDENTIFY LOCATION OF PROPOSED
 WORK WITH DEMENSIONS TO PROPERTY LINES.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-11-20 Cont ID  
Sent By cthroop Date 2017-11-20 Time 16:08 Rev Time 0.00
Received By cthroop Date 2017-11-20 Time 16:07 Sent To E
Notes
2017-11-20 16:24:53BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE PLAN. SHOW BUILDING SETBACKS TO
 PROPERTY LINES AND OTHER STRUCTURES ON SITE.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-25 Cont ID  
Sent By cthroop Date 2017-10-25 Time 13:21 Rev Time 0.00
Received By cthroop Date 2017-10-25 Time 11:32 Sent To  
Notes
2017-10-25 13:24:14BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE PLAN. DEMONSTRATE SET BACKS.
 2. DESIGNER TO PRINT NAME AND SIGN PLAN.
 3. CANNOT VERIFY LOCATION OF WORK. APPLICANT MAY COME
 IN TO MEET WITH REVIEWER FOR CLARIFICATION.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By cthroop Date 2017-09-13 Time 10:38 Rev Time 0.00
Received By cthroop Date 2017-09-13 Time 09:27 Sent To M
Notes
2017-09-13 10:56:02BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ONLY ONE SET OF PLANS SUBMITTED. PROVIDE SECOND SET
 OF PLANS UPON RE-SUBMITTAL.
 2. CANNOT VERIFY VALUE.
 3. PROVIDE FLOOR PLAN. IDENTIFY LOCATION OF ALL
 OPENINGS. IDENTIFY USE OF EXISTING ADJOINING ROOM. SHOW
 HOW NEW ROOM WILL COMMUNICATE WITH EXISTING ROOM.
 4. PROVIDE DESIGN WIND LOADS FOR ALL EXTERIOR OPENINGS.
 5. PROVIDE DETAIL OF ALL EXTERIOR ELEVATIONS. IDENTIFY
 LOCATION OF NEW WINDOWS AND DOORS.
 6. IF NEW ROOM COMMUNICATES FREELY WITH EXISTING ROOM
 OR NEW MECHANICAL SYSTEM WILL BE INSTALLED, PROVIDE
 MECHANICAL PLAN.
 7. PROVIDE SITE PLAN. SHOW DEMENSIONS TO PROPERTY LINES
 AND ANY EXISTING STRUCTURES ON PROPERTY.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-02-23 Cont ID  
Sent By jpearson Date 2018-02-23 Time 14:47 Rev Time 0.00
Received By jpearson Date 2018-02-23 Time 14:47 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 09:10 Rev Time 0.00
Received By jpearson Date 2017-11-21 Time 09:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-10-24 Cont ID  
Sent By jpearson Date 2017-10-24 Time 16:20 Rev Time 0.00
Received By jpearson Date 2017-10-24 Time 16:20 Sent To B
Notes
2017-10-24 16:20:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE 2 COPIES OF ELECTRICAL PLAN FOR REVIEW. FBC
 107.2.1, 107.3.5 (PLAN MUST BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. SHOW ELECTRICAL WIRING AND
 OUTLETS PER CODE.)
 2. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION PER CODE.
 SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING
 OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3,
 FBC 107.2.1 (NOT PROVIDED).
 3. SHOW OUTLETS ON PLAN TO COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. NEC 210.52; FBC RE3901.2.1
 (NOT PROVIDED.)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By jpearson Date 2017-08-29 Time 08:36 Rev Time 0.00
Received By jpearson Date 2017-08-29 Time 08:36 Sent To  
Notes
2017-08-29 08:36:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE 2 COPIES OF ELECTRICAL PLAN FOR REVIEW. FBC
 107.2.1, 107.3.5
 2. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION PER CODE.
 SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING
 OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3,
 FBC 107.2.1
 3. SHOW OUTLETS ON PLAN TO COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. NEC 210.52; FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-03-19 Cont ID  
Sent By cthroop Date 2018-03-19 Time 07:31 Rev Time 0.00
Received By cthroop Date 2018-03-09 Time 12:51 Sent To I
Notes
2018-03-12 12:51:18RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-02-26 Cont ID  
Sent By cthroop Date 2018-02-26 Time 11:13 Rev Time 0.00
Received By cthroop Date 2018-02-21 Time 10:14 Sent To I
Notes
2018-02-22 10:14:49RESUB ROUTED TO LLOUIE VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 09:10 Rev Time 0.00
Received By jpearson Date 2017-11-14 Time 10:41 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-25 Cont ID  
Sent By cthroop Date 2017-10-25 Time 13:21 Rev Time 0.00
Received By cthroop Date 2017-10-02 Time 11:16 Sent To  
Notes
2017-10-03 11:19:41R18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-13 Cont ID  
Sent By hmoser Date 2017-09-13 Time 11:46 Rev Time 0.00
Received By hmoser Date 2017-08-10 Time 11:12 Sent To  
Notes
2017-08-11 11:13:03R16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-11-20 Cont ID  
Sent By cthroop Date 2017-11-20 Time 16:07 Rev Time 0.00
Received By cthroop Date 2017-11-20 Time 16:07 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By cthroop Date 2017-09-13 Time 10:24 Rev Time 0.00
Received By cthroop Date 2017-09-13 Time 09:27 Sent To  
Notes
2017-09-13 10:38:35BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CANNOT DETERMINE FROM PLANS SUBMITTED IF NEW SPACE
 WILL COMMUNICATE WITH EXISTING HABITABLE SPACE OR IF
 NEW MECHANICAL SYSTEM WILL BE INSTALLED.
 2, IF THIS SPACE WILL BE CONDITIONED, PROVIDE A
 MECHANICAL PLAN.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-09-13 Cont ID  
Sent By hmoser Date 2017-09-13 Time 11:46 Rev Time 0.00
Received By hmoser Date 2017-09-13 Time 11:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-08-28 Cont ID  
Sent By gjohnson Date 2017-08-28 Time 16:16 Rev Time 0.00
Received By gjohnson Date 2017-08-28 Time 16:08 Sent To  
Notes
2017-08-28 16:16:53NO PLUMBING SHOWN ON PLAN/GPJ

Review Stop Z ZONING
Rev No 5 Status P Date 2018-03-15 Cont ID  
Sent By ajones Date 2018-03-15 Time 12:13 Rev Time 0.00
Received By ajones Date 2018-03-14 Time 10:38 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2018-02-23 Cont ID  
Sent By llouie Date 2018-02-23 Time   Rev Time 0.00
Received By llouie Date 2018-02-22 Time 16:12 Sent To E
Notes
2018-02-23 11:11:57** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) AN UPDATED SURVEY OF THE PROPERTY IS REQUIRED. THE
 SURVEY MUST PROVIDE THE SETBACK DIMENSIONS OF THE
 EXISTING COVERED PATIO (TO BE CONVERTED TO ENCLOSED
 STORAGE SPACE) TO THE PROPERTY LINE(S). [REPEAT COMMENT
 FROM 11/20/17]
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2017-11-16 Cont ID  
Sent By jpearson Date 2017-11-21 Time 09:10 Rev Time 0.00
Received By llouie Date 2017-11-16 Time   Sent To B
Notes
2017-11-20 08:30:37** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) AN UPDATED SURVEY OF THE PROPERTY IS REQUIRED.
  
 2.) SCOPE OF WORK AND PERMIT PLANS NOT CLEAR. STAFF IS
 UNCERTAIN TO WHERE THE WORK IS BEING DONE (I.E.
 CLOSURES).
  
 3.) A SITE PLAN, SHOWING THE PROPOSED NEW BUILDING
 SETBACKS FROM THE PROPERTY LINES ARE REQUIRED.
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 2 Status F Date 2017-10-06 Cont ID  
Sent By njwira Date 2017-10-06 Time 11:56 Rev Time 0.00
Received By njwira Date 2017-10-05 Time 16:29 Sent To  
Notes
2017-10-06 11:57:1510/6/17- FAILED
  
 PLEASE PROVIDE TWO(2) COPIES OF AN ELEVATION DRAWING.
 STILL HAVE NOT PROVIDED TWO(2)COPIES OF A SURVEY
 SHOWING SETBACKS
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-17 Cont ID  
Sent By njwira Date 2017-08-17 Time 17:05 Rev Time 0.00
Received By njwira Date 2017-08-17 Time 16:18 Sent To  
Notes
2017-08-17 17:06:108/17/17- FAILED
  
 REQUIRES TWO(2)COPIES OF A SURVEY SHOWING THE SETBACKS
 OF THE SCREEN ENCLOSURE
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  