| 2017-09-14 11:51:25 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17080494 |
| | W. P. B. PERMIT: 15111020 |
| | ADD: 1100 S. FLAGLER DR. SUITE: UNIT11-D |
| | CONT: SUFFOLK |
| | TEL: 561-407-496-3168 ED HANRATTY |
| | E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS |
| | E-MAIL ADDRESS REQUIREMENTS, |
| | WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN |
| | RECORD. |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | SUBJECT TO FAIR HOUSING! |
| | |
| | 1ST REVIEW |
| | DATE: THURSDAY SEPT. 14/2017 |
| | ACTION: DENIED |
| | |
| | 1A) SHEET 126_28-A2-90-11D. THE MASTER BEDROOM CLOSET |
| | WITH A SINGLE POCKET DOOR MEASURES IN THE OPEN POSITION |
| | 2.5 FEET CLEAR. FAIR HOUSING REQUIRES A CLEAR WIDTH OF |
| | 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING |
| | SECTION 100.205.(C)(2)(2). |
| | |
| | 1B) SHEET 126_28-A2-90-11D SHOWS A POCKET DOORS LEADING |
| | INTO THE MASTER BEDROOM CLOSET, PLEASE PROVIDE WHAT |
| | TYPE OF HANDLES WILL BE INSTALLED ON THE POCKET DOORS |
| | CANNOT BE FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE |
| | FOR PEOPLE THAT HAVE LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 1C) SHEET 126_28-A2-90-11D. THE POCKET DOOR TO THE |
| | BEDROOM # 4 MEASURES 2.5 FT. CLEAR WIDTH, WILL NEED TO |
| | COMPLY WITH 2014 FBC- ACCESSIBILITY/ FAIR HOUSING |
| | SECTION 100.205.(C)(2)(2). |
| | |
| | 1D) SHEET 126_28-A2-90-11D SHOWS A POCKET DOORS LEADING |
| | INTO THE BEDROOM # 4, PLEASE PROVIDE WHAT TYPE OF |
| | HANDLES WILL BE INSTALLED ON THE POCKET DOORS CANNOT BE |
| | FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE |
| | THAT HAVE LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 1E) SHEET 126_28-A2-90-11D A/V CLOSET SHOWS A DOOR |
| | LABELED U05F WHICH MEASURES TO BE A 30 INCH WIDE DOOR. |
| | WHEN CLOSETS ARE OVER 2 FEET IN DEPTH THEY NEED TO SHOW |
| | COMPLIANCE WITH FAIR HOUSING REQUIRES A CLEAR WIDTH OF |
| | 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING |
| | SECTION 100.205.(C)(2)(2). |
| | |
| | 1F) PLEASE BE AWARE ALL OF THE EXTERIOR SLIDING GLASS |
| | DOORS WILL NEED TO MEET THE 32 INCHES CLEAR AND THE |
| | HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE |
| | LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 2) SHEET 242-_15-A6-66-11D FLOOR FINISHES. BLDG TYPE: |
| | TYPE I/ TYPE II FLOOR INSULATION (FBC-B 2010) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR |
| | PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF |
| | THERE IS A DROP CEILING WITH OR WITHOUT INSULATION: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) THE NARRATIVE LIST SHEETS A0.01C, A2.56B, A6.13B & |
| | A7.55B AS CUSTOM UNIT SUPPLEMENTAL INDEX AND ADDED |
| | REFERENCE NOTES, BUT THESE SHEETS ARE NOT PART OF THE |
| | PLAN SET SUBMITTED? THEN WHY ARE THESE SHEETS LISTED IN |
| | THE INDEX FOR THIS UNIT? 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |