Plan Review Details - Permit 17080485
Plan Review Stops For Permit 17080485
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-09-06 Cont ID  
Sent By tklarge Date 2017-09-06 Time 12:05 Rev Time 0.00
Received By tklarge Date 2017-09-05 Time 10:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-08-25 Cont ID  
Sent By tklarge Date 2017-08-25 Time 12:10 Rev Time 0.00
Received By tklarge Date 2017-08-25 Time 05:37 Sent To  
Notes
2017-08-25 12:10:421) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MP
 REGULATORS.NOTHING HAS BEEN SUBMITTED. 2ND REQUEST.
 2) SHOW THE DISTANCE FROM EACH MP REGULATOR TO THE MOST
 REMOTE OUTLET IN THE BRANCH LINE PER THE 2014FBC-FUEL
 GAS SEC. 402.4.1, 2014 FBCR SEC. G 2413.3. THIS IS FOR
 THE LOW PRESSURE SIDE OF EACH MP REGULATOR.2ND REQUEST.
 3) SUBMIT THE CORRECT CORRESPONDING EHD NUMBER FOR THE
 CSST PIPE SIZES. THERE ARE INCORRECT EHD SIZES NOTED ON
 THE GAS RISER FOR THE CORRESPONDING PIPE SIZES.. COMPLY
 WITH THE SIZING TABLE(S) IN THE 2014 FBC-FUEL GAS OR
 THE WARDFLEX GAS SIZING TABLE.SUBMIT TWO COPIES OF THE
 WARDFLEX PIPE SIZING TABLE FOR REVIEW FOR THE SIZING OF
 THE CSST. WPB AMEND. TO FBC SEC. 107.3.5.3. 2ND REQUEST
 4) I HAVE ADDED THE TOTAL BTU LOAD SEVERAL TIMES AND I
 HAVE CALCULATED 2,229,000 BTU'S. PLEASE CHECK YOUR BTU
 AND REVISE.
 5) THE GAS RISER SHOWS A 1/2 INCH GALVANIZED NEAR THE
 GAS RANGE SUPPLYING A 1 INCH CSST LINE THAT SUPPLIES
 TWO FIREPLACES. IS THIS CORRECT? THE 1/2 INCH
 GALVANIZED LINE IS UNDERSIZED. CLARIFY.
 6) SHOW THE TYPE OF PIPING AND LENGTH FOR THE 1/2 INCH
 DROP TO THE BBQ AND ALSO THE 3/4 INCH RISER TO THE BBQ.
 7) THE 3/4 CSST BRANCH LINE SUPPLYING THE FIREPLACE IN
 THE FIRST FLOOR LOGGIA AND THE SECOND FLOOR MASTER
 TERRACE IS UNDERSIZED.COMPLY WITH 2014 FBC-FUEL GAS
 CHAPTER 4.
 8) SHOW THE LENGTH OF SECTION OF PIPING FOR ALL RISERS
 TO THE 2ND FLOOR. WPB AMEND. TO FBC SEC. 107.3.5.3.
 9) SHT. P103 NOTE ON PLANS REFERS TO THE GAS REGULATORS
 BEING EQUIPPED WITH A LEAK LIMITING DEVICE. VENT
 LIMITING DEVICES ARE USUALLY ONLY APPROVED FOR USE ON
 THE REGULATOR WHEN INSTALLED INDOORS PER THE
 MANUFACTURER AND ARE NOT APPROVED FOR OUTDOORS. THE
 REGULATORS ON THIS SYSTEM ARE SHOWN OUTDOORS.
 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE TANKLESS WATER HEATERS AND THE
 GAS RANGE. THE WATER HEATERS AND RANGE SHALL BE LISTED
 AND LABELED. 2014 FBC-FUEL GAS SEC.301.3. 2ND REQUEST.
  
 I SUGGEST MAKING AN APPOINTMENT WITH THIS REVIEWER TO
 REVIEW THE COMMENTS PRIOR TO RESUBMITTING THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-08-16 Cont ID  
Sent By tklarge Date 2017-08-16 Time 06:40 Rev Time 0.00
Received By tklarge Date 2017-08-16 Time 06:02 Sent To  
Notes
2017-08-16 06:40:031) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE CSST OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
 2) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2014 FBC-FUEL
 GAS SEC.409.4.
 3) SHOW THE DISTANCE FROM EACH MP REGULATOR TO THE MOST
 REMOTE OUTLET IN THE BRANCH LINE PER THE 2014 FBC-FUEL
 GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
 4) SHOW THE CORRESPONDING EHD NUMBER FOR EACH SIZE OF
 CSST. 2014 FBC-FUEL GAS 402.4.
 5) THE CSST ON THE SYSTEM APPEARS TO BE UNDERSIZED BUT
 WITHOUT KNOWING WHICH SIZING TABLE IS BEING USED, A
 COMPREHENSIVE REVIEW COULD NOT BE DONE. ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE FORTHCOMING UPON A SUBSEQUENT
 REVIEW.
 6) ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2014
 FBC-FUEL GAS SEC. 301.3. SUBMIT COPIES OF
 MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHOWING COMPLIANCE.
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MP
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 2014 FGC SEC. 410.1.
 8) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. 2014 FGC SEC.304.1.
 9) PE PIPE SHALL BE INSTALLED OUTDOORS UNDERGROUND
 ONLY. 2014 FGC SEC.404.17.1.
 10) THE LOCATION OF ALL GAS VENTS SHALL COMPLY WITH
 2014 FBC-FUEL GAS SECS. 502 THRU 505 OR 2014 FBC-RES.
 SEC.G2426.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-09-06 Cont ID  
Sent By tklarge Date 2017-09-06 Time 12:06 Rev Time 0.00
Received By tklarge Date 2017-09-05 Time 10:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-25 Cont ID  
Sent By tklarge Date 2017-08-25 Time 12:10 Rev Time 0.00
Received By tklarge Date 2017-08-23 Time 14:11 Sent To  
Notes
2017-08-24 14:11:45RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-16 Cont ID  
Sent By tklarge Date 2017-08-16 Time 06:40 Rev Time 0.00
Received By tklarge Date 2017-08-09 Time 14:48 Sent To  
Notes
2017-08-10 14:48:41PLUMB <5K