Plan Review Details - Permit 17080435
Plan Review Stops For Permit 17080435
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-12 Cont ID  
Sent By cthroop Date 2017-10-12 Time 16:56 Rev Time 0.00
Received By cthroop Date 2017-10-12 Time 16:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-11 Cont ID  
Sent By cthroop Date 2017-10-11 Time 11:01 Rev Time 0.00
Received By cthroop Date 2017-10-11 Time 10:55 Sent To M
Notes
2017-10-11 11:28:13BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BELOW COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED
  
 BUILDING #2 356 MARLBOROUGH PLACE
  
 1. OWNER/AGENT TO SIGN ENERGY SUBMITTAL.
 2. PRODUCT APPROVALS/NOA'S FOR WINDOWS AND DOORS ARE TO
 BE DEFERRED.
 3. DESIGNER TO REVIEW AND APPROVE IN WRITING ALL
 PRODUCT APPROVALS.
 4. ROOF DESIGN PRESSURE TABLE ON PLAN PAGE A.4 STATES
 MEAN ROOF HEIGHT IS 15 FT. BOTH STRUCTURES ARE TWO
 STORY. PLEASE CLARIFY.
 5. STAIR DETAIL ON PLAN PAGE A.5 INDICATES MAX. RISER
 HEIGHT TO BE 8" MAX. RISER HEIGHT SHALL NOT EXCEED
 73/4" PER FBC R 311.7.5.1.
 6. PROVIDE LANDING AT STAIRS PER FBC R311.7.6.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By cthroop Date 2017-08-30 Time 12:58 Rev Time 0.00
Received By cthroop Date 2017-08-29 Time 15:23 Sent To M
Notes
2017-08-30 13:04:02BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BUILDING #2 356 MARLBOROUGH PLACE
  
 1. PROVIDE ENERGY SUBMITTAL FOR BLDG. #2, 356
 MARLBOROUGH PL. OWNER/AGENT TO SIGN ENERGY SUBMITTAL.
 2. PRODUCT APPROVALS/NOA'S SUBMITTED DO NOT MATCH
 PRODUCT APPROVAL SCHEDULE ON PLANS (WINDOWS, DOORS &
 ROOFING). PLEASE CLARIFY.
 3. DESIGNER TO REVIEW AND APPROVE IN WRITING ALL
 PRODUCT APPROVALS. INDICATE MODEL OF DOORS TO BE
 INSTALLED.
 4. ROOF DESIGN PRESSURE TABLE ON PLAN PAGE A.4 STATES
 MEAN ROOF HEIGHT IS 15 FT. BOTH STRUCTURES ARE TWO
 STORY. PLEASE CLARIFY.
 5. STAIR DETAIL ON PLAN PAGE A.5 INDICATES MAX. RISER
 HEIGHT TO BE 8" MAX. RISER HEIGHT SHALL NOT EXCEED
 73/4" PER FBC R 311.7.5.1.
 6. PROVIDE LANDING AT STAIRS PER FBC R311.7.6.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 R311.7.5.1 RISERS.
 THE MAXIMUM RISER HEIGHT SHALL BE 73/4 INCHES (196 MM).
 THE RISER SHALL BE MEASURED VERTICALLY BETWEEN LEADING
 EDGES OF THE ADJACENT TREADS. THE GREATEST RISER HEIGHT
 WITHIN ANY FLIGHT OF STAIRS SHALL NOT EXCEED THE
 SMALLEST BY MORE THAN 3/8 INCH (9.5 MM). RISERS SHALL
 BE VERTICAL OR SLOPED FROM THE UNDERSIDE OF THE NOSING
 OF THE TREAD ABOVE AT AN ANGLE NOT MORE THAN 30 DEGREES
 (0.51 RAD) FROM THE VERTICAL. OPEN RISERS ARE PERMITTED
 PROVIDED THAT THE OPENING BETWEEN TREADS DOES NOT
 PERMIT THE PASSAGE OF A 4-INCH-DIAMETER (102 MM)
 SPHERE.
  
 R311.7.6 LANDINGS FOR STAIRWAYS.
 THERE SHALL BE A FLOOR OR LANDING AT THE TOP AND BOTTOM
 OF EACH STAIRWAY. THE MINIMUM WIDTH PERPENDICULAR TO
 THE DIRECTION OF TRAVEL SHALL BE NO LESS THAN THE WIDTH
 OF THE FLIGHT SERVED. LANDINGS OF SHAPES OTHER THAN
 SQUARE OR RECTANGULAR SHALL BE PERMITTED PROVIDED THE
 DEPTH AT THE WALK LINE AND THE TOTAL AREA IS NOT LESS
 THAN THAT OF A QUARTER CIRCLE WITH A RADIUS EQUAL TO
 THE REQUIRED LANDING WIDTH. WHERE THE STAIRWAY HAS A
 STRAIGHT RUN, THE MINIMUM DEPTH IN THE DIRECTION OF
 TRAVEL SHALL BE NOT LESS THAN 36 INCHES (914 MM).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-10-16 Cont ID  
Sent By skennedy Date 2017-10-16 Time 09:39 Rev Time 0.00
Received By skennedy Date 2017-10-16 Time 09:39 Sent To  
Notes
2017-10-16 09:39:38BY JOHN PEARSON

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-10-10 Cont ID  
Sent By jpearson Date 2017-10-10 Time 15:10 Rev Time 0.00
Received By jpearson Date 2017-10-10 Time 15:10 Sent To  
Notes
2017-10-10 15:10:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 ITEMS CORRECTED HAVE BEEN NOTED, ITEMS REMAINING NEED
 FURTHER CORRECTION.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. PROVIDE ACCURATE LOAD CALCULATION. LOAD CALC
 PROVIDED SHOWS A COMPARISON FOR 2 DIFFERENT A/C
 SYSTEMS, BUT ONLY ONE IS SHOWN ON PLAN. IS THERE ONLY
 ONE SYSTEM, OR TWO? THE AHU UNIT IS STATED AS A 10KW
 LOAD, BUT ONLY 3500 IS INCLUDED IN THE CALCULATION. THE
 LARGER OF THE LOADS IS REQUIRED TO BE USED. THE AHU FAN
 SHOULD BE INCLUDED WITH THE AHU TOTAL LOAD, NOT A
 SEPARATE LOAD. NEC 220; FBC RE 3602.2 (LOAD CALCULATION
 DOES NOT INCLUDE PROPER LOAD FOR A/C SYSTEM AS
 SPECIFIED ON MECHANICAL PLAN. SEE FBC RESIDENTIAL
 3602.2 FOR THE PROPER EQUATION FOR THE LOAD CALCULATION
 AND PROVIDE CORRECTION.)
 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3 (THIS IS NOT LOCATED
 IN METER CAN, SEE NEC 250.94 OR FBC RE3609.3)
 9. CORRECTED.
 10.CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-28 Cont ID  
Sent By jpearson Date 2017-08-28 Time 16:21 Rev Time 0.00
Received By jpearson Date 2017-08-28 Time 16:21 Sent To  
Notes
2017-08-28 16:21:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 2. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD. PROVIDE CORRECTION. NEC 422.13; FBC
 RE3702.10
 3. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE, AND THAT OUTLETS SHALL BE INSTALLED IN
 ANY COUNTER SPACE THAT IS 12 INCHES OR WIDER. THE PLAN
 PROVIDED DOES NOT MEET THIS CODE IN SOME AREAS. PROVIDE
 CORRECTION. NEC 210.52(C)(1); FBC RE3901.4
 4. PROVIDE DISCONNECTING MEANS ON THE EXTERIOR OF THE
 BUILDING AT THE SERVICE LOCATION FOR THE ELECTRICAL
 PANEL. SERVICE CONDUCTORS ARE NOT PERMITTED TO BE
 INSIDE THE BUILDING WITHOUT OVER CURRENT PROTECTION.
 NEC 230.71(A)(1); FBC RE3601.6.2
 5. NOTE FOR AFCI PROTECTION STATES THAT ALL OUTLETS IN
 BEDROOMS SHALL HAVE AFCI PROTECTION. CODE STATES: "ALL
 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION." PROVIDE CORRECTION. NEC 210.12; FBC
 RE3902.12
 6. NOTE FOR ENERGY COMPLIANCE STATES THAT "50% OF LAMPS
 SHALL BE 75% EFFICIENT". CODE STATES: "A MINIMUM OF 75
 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED LIGHTING
 FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF
 75 PERCENT OF THE PERMANENTLY INSTALLED LIGHTING
 FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY LAMPS".
 PROVIDE CORRECTION. A NOTE WILL SUFFICE. FBC CE R404.1
 7. PROVIDE ACCURATE LOAD CALCULATION. LOAD CALC
 PROVIDED SHOWS A COMPARISON FOR 2 DIFFERENT A/C
 SYSTEMS, BUT ONLY ONE IS SHOWN ON PLAN. IS THERE ONLY
 ONE SYSTEM, OR TWO? THE AHU UNIT IS STATED AS A 10KW
 LOAD, BUT ONLY 3500 IS INCLUDED IN THE CALCULATION. THE
 LARGER OF THE LOADS IS REQUIRED TO BE USED. THE AHU FAN
 SHOULD BE INCLUDED WITH THE AHU TOTAL LOAD, NOT A
 SEPARATE LOAD. NEC 220; FBC RE 3602.2
 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 9. PROVIDE DETAIL OF METHOD TO DETERMINE THE 25 OHM
 RESISTANCE REQUIRED ON THE GROUND ROD, OR SHOW THE
 ADDITION OF A SUPPLEMENTAL ELECTRODE. NEC 250.53(A)(2);
 FBC RE 3608.4
 10. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". PROVIDE NOTE FOR
 COMPLIANCE. NEC 410.16; FBC RE4003.12
 11. ADDRESS LISTED ON RISER DIAGRAM STATES THIS IS FOR
 345 MARLBOROUGH PLACE. PERMIT APPLICATION STATES THE
 ADDRESS AS 356 MARLBOROUGH PLACE, BUT THIS ADDRESS IS
 NOT FOUND IN PBC PAPA. PROVIDE CORRECTION. FBC 107.2.1
 12. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. BE ADVISED THAT IF ROMEX IS USED,
 THE AMPACITY RATING FOR #8 ROMEX IS 40 AMPS AND FOR #6
 ROMEX IS 50 AMPS. NEC 210.8, 210.12, 215.5, 334.80,
 408.4; FBC RE3706.2, RE3902, RE3705.4.4
 13. SINCE THE ADDRESS FOR THIS APPLICATION DOES NOT
 EXIST, BE ADVISED THAT ONLY ONE SERVICE IS PERMITTED
 PER CODE. PLEASE REVISE RISER DIAGRAM AND SERVICE
 CALCULATIONS FOR BUILDING 1 TO ADDRESS THIS ISSUE. NEC
 230.2: FBC RE 3601.2
 14. WILL THERE BE RECEPTACLES INSTALLED FOR THE GARAGE
 DOOR OPENER? PROVIDE CORRECTION AND/OR CLARIFICATION.
 FBC 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-10-04 Cont ID  
Sent By fmittner Date 2017-10-04 Time 09:37 Rev Time 0.00
Received By fmittner Date 2017-10-04 Time 09:37 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-08-21 Cont ID  
Sent By fmittner Date 2017-08-21 Time 08:21 Rev Time 0.00
Received By fmittner Date 2017-08-21 Time 08:21 Sent To  
Notes
2017-08-21 08:23:18PROPERTY IN HISTORIC DISTRICT.
 ARCHES AND HORIZONTALLY ORIENTED WINDOWS NOT IN KEEPING
 WITH DESIGN GUIDELINES. REQUIRES COA SUBMITTAL.
 QUESTIONS CONTACT:
  
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 (561) 822-1457
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-16 Cont ID  
Sent By skennedy Date 2017-10-16 Time 09:39 Rev Time 0.00
Received By skennedy Date 2017-09-26 Time 15:31 Sent To  
Notes
2017-09-27 15:31:38R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-01 Cont ID  
Sent By hmoser Date 2017-09-01 Time 11:31 Rev Time 0.00
Received By hmoser Date 2017-08-09 Time 09:40 Sent To  
Notes
2017-08-11 09:40:37R14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-16 Cont ID  
Sent By skennedy Date 2017-10-16 Time 09:39 Rev Time 0.00
Received By skennedy Date 2017-10-16 Time 09:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-01 Cont ID  
Sent By hmoser Date 2017-09-01 Time 11:22 Rev Time 0.00
Received By hmoser Date 2017-09-01 Time 11:22 Sent To  
Notes
2017-09-01 11:30:51PLAN DENIED
 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR.
 SHOW SIZE AND WHERE RETURN AIR IS GOING.
 2014 RESIDENTIAL CODE
 2) PROVIDE ENERGY CALCULATIONS FOR BUILDING # 2
 SECTION M1401.3 SIZING 2014 RESIDENTIAL CODE
 3) ENERGY CALCULATIONS FOR BUILDING # 1 DO NOT
 MATCH PLAN
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-06 Cont ID  
Sent By gjohnson Date 2017-10-06 Time 14:47 Rev Time 0.00
Received By gjohnson Date 2017-10-06 Time 14:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-28 Cont ID  
Sent By gjohnson Date 2017-08-28 Time 19:23 Rev Time 0.00
Received By gjohnson Date 2017-08-28 Time 19:23 Sent To  
Notes
2017-08-28 19:23:571ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WASHING MACHINE IS MISSING ON RISER DIAGRAM. PER
 WPB AMEND TO FBC 107.3.5.3(11)
  
 2. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK. PER FBC RES P3005.2.6
  
 3. PROVIDE DETAIL SHOWING RELIEF LINE, PAN AND PAN
 DRAIN FOR WATER HEATER. PER WPB AMEND TO FBC 107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-10-11 Cont ID  
Sent By cthroop Date 2017-10-11 Time 10:55 Rev Time 0.00
Received By cthroop Date 2017-10-11 Time 10:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By cthroop Date 2017-08-30 Time 12:50 Rev Time 0.00
Received By cthroop Date 2017-08-30 Time 11:40 Sent To  
Notes
2017-08-30 12:51:40BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NOA'S SUBMITTED DO NOT MATCH NOA ON PRODUCT APPROVAL
 SCHEDULE, SEE PLAN PAGE A.3.
 2. DESIGNER TO SELECT ROOFING SYSTEM TO BE INSTALLED
 FROM NOA.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-10-04 Cont ID  
Sent By fmittner Date 2017-10-04 Time 09:38 Rev Time 0.00
Received By fmittner Date 2017-10-04 Time 09:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-21 Cont ID  
Sent By fmittner Date 2017-08-21 Time 08:21 Rev Time 0.00
Received By fmittner Date 2017-08-21 Time 08:21 Sent To  
Notes
***NONE***