| Plan Review Stops For Permit 17080429 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2018-03-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-03-12 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-03-12 |
Time |
15:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-03-09 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-03-09 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2018-03-09 12:57:44 | | | | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, FOURTH | | | BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE | | | COMPLIANCE CERTIFICATION. | | | THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | | RENOVATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-02-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-02-02 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-02-02 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2018-02-02 15:15:27 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, THIRD | | | BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- ENERGY CALCULATIONS SUBMITTED: | | | A) COOLING SYSTEM AND EFFICIENCY SPECIFIED ON ITEM #12A | | | AND 12B DON'T MATCH PLANS. THERE IS NO DUCTLESS MINI | | | SPLIT UNIT SPECIFIED ON PLANS. SEE PLANS AND REVISE AS | | | REQUIRED. SEC. R101.5.1.1.1 FBC -ENERGY CONSERVATION. | | | | | | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, | | | INCLUDING BUILDER NAME, PERMITTING OFFICE. SEC. | | | R101.5.1.1.1 FBC -ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | | | | C) WINDOW AREA SPECIFIED ON ITEM #6(C) DOESN'T MATCH | | | PLANS. NOTE: THERE ARE TWO WINDOWS SHOWN ON PLANS. SEE | | | PLAN FOR SIZES AND REVISE AS REQUIRED. SEC. | | | R101.5.1.1.1 FBC -ENERGY CONSERVATION. | | | | | | D) REVISE ITEM #9. WALL TYPE IS MASONRY NOT WOOD FRAME. | | | CALCULATIONS NEED TO SHOW THE R-4.1 INSULATION ON ITEM | | | # 9A2 NOT 9A1. REVISE AS REQUIRED. SEC. R101.5.1.1.1 | | | FBC -ENERGY CONSERVATION. | | | | | | NOTE: | | | WINDOW NEED LABEL SHOWING THE ENERGY U-FACTOR AND SHGC | | | FACTOR SPECIFIED ON THE ON THE ENERGY CALCULATIONS | | | SUBMITTED. MAKE SURE THE WINDOWS MEET THIS CRITERIA | | | PRIOR TO PURCHASING THEM TO AVOID CONFLICTS. | | | | | | 2- NEW COMMENT: | | | A) THE BUILDING CODE UNDER WHICH THIS PERMIT | | | APPLICATION WAS SUBMITTED WAS THE 2014 FBC. CLARIFY WHY | | | THE DESIGN PARAMETERS AND CODES FOR REFERENCE | | | INFORMATION AND STRUCTURAL NOTE #1 WAS CHANGED ON SHEET | | | A.1 TO REFERENCE THE 2017 FBC?. THERE IS NO REASON TO | | | CHANGE THE REFERENCED CODE. REVISE AS REQUIRED TO | | | REFERENCE THE CORRECT CODE, THE 2014 FBC AS REQUIRED BY | | | CHAPTER 553 FLORIDA STATUTE. | | | | | | B) THE CURRENT ASCE STANDARD IS THE ASCE 7-10 NOT ASCE | | | 7-16. REVISE DESIGN PARAMETERS INFORMATION AND | | | STRUCTURAL NOTE #2(C) AS REQUIRED BY CHAPTER 46 | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-11-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-11-14 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-11-13 |
Time |
18:21 |
Sent To |
|
|
| Notes |
| 2017-11-13 18:44:17 | | | | NOTE: | | | 01/05/18 OWNER P/U PLUMBING/MECHANICAL DRAWING TO GET | | | NAME AND SIGNATURE OF DESIGNER OF RECORD. JG. | | | | | | | | | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, SECOND | | | BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT. | | | BRING BACK COUNTY STAMPED PLANS AND COPY OF IMPACT FEES | | | PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | RESPONSE: THIS MAY BE DONE LATER AFTER THE PLANS ARE | | | APPROVED BY ALL TRADES AND PERMIT IS READY TO BE | | | ISSUED. | | | | | | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED | | | BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED AT ALL. | | | | | | 3- THE PROPOSED BEDROOM NEEDS THE EMERGENCY ESCAPE AND | | | RESCUE OPENING AS REQUIRED BY SEC. R310.1 | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | RESPONSE: | | | SINGLE HUNG WINDOW SIZE SPECIFIED ON PLANS DON'T COMPLY | | | WITH THE MINIMUM CLEAR HEIGHT REQUIRED BY SEC. R310.1.2 | | | FBC-RESIDENTIAL. FLOOR PLAN ON SHEET A.1 SPECIFIES 53 X | | | 51 SINGLE HUNG WINDOW. THIS WINDOW SIZE DOESN'T PROVIDE | | | THE 24" CLEAR HEIGHT OPENING. ALSO, FLOOR PLAN ON SHEET | | | A.1 SPECIFIES SH-25, WHILE SOUTH ELEVATION ON SHEET A.2 | | | SPECIFIES SH-34. INFORMATION DOESN'T MATCH. CLEARLY | | | SPECIFY ONE SIZE OF WINDOW THAT COMPLIES WITH ALL THE | | | EGRESS REQUIREMENTS. | | | | | | NOTE: ENGINEER OF RECORD MAY BE CHARGED 4 TIMES THE | | | PLAN REVIEW AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) | | | FOR MULTIPLE PLAN REVIEW REJECTIONS. | | | | | | 4- PLANS SPECIFY EXISTING 3'-0 X 6'-8" ENTRY DOOR AND | | | EXISTING SINGLE HUNG WINDOW. THERE ARE NO CITY RECORDS | | | FOR THE INSTALLATION OF THE ENTRY DOOR. ALSO, PHOTOS ON | | | THE INTERNET WHEN THE HOUSE WAS FOR SALE SHOW A GARAGE | | | WITH NO DOORS, EXCEPT FOR THE OPENING FOR A GARAGE | | | DOOR. AND THE WINDOW SEEMS TO BE FAIRLY NEW. SEE | | | ATTACHED PHOTO. PERMIT IS REQUIRED FOR THE INSTALLATION | | | OF NEW DOOR AND REPLACEMENT OF WINDOWS. PRODUCT | | | APPROVALS WILL BE REQUIRED. SEE ITEM # 8 BELOW. REVISE | | | INFORMATION ON PLANS AND PROVIDE COMPLETE INFORMATION | | | FOR THE FRAMING OF THE ENTRY DOOR. SEC. R301.1 | | | FBC-RESIDENTIAL. | | | RESPONSE: | | | PLANS STILL CALL FOR EXISTING DOOR. PLANS WERE REVISED | | | SHOWING THE VERTICAL REINFORCEMENT FOR THE WINDOW, BUT | | | DON'T SHOW THE VERTICAL REINFORCEMENT FOR THE ENTRY | | | DOOR. REVISE ALL PLANS AS REQUIRED. | | | | | | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) ENTRY DOOR AS SHOWN ON PLANS. | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | B) SINGLE HUNG WINDOW AS SHOWN PLANS. | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | C) HURRICANE SHUTTERS IF WINDOW AND DOORS WITH GLAZING | | | DON'T HAVE IMPACT GLAZING. AND, PROVIDE COMPLETE | | | INSTALLATION SCHEDULE. SEE CITY SAMPLE. | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 7- ENGINEER OF RECORD TO CLARIFY WHY THE ROOF LIVE LOAD | | | SPECIFIED ON THE DESIGN PARAMETERS AND STRUCTURAL NOTE | | | #2 ON SHEET A.1 IS ONLY 10PSF?. WHERE IS THIS DESIGN | | | CRITERIA TAKEN FROM? PROVIDE WRITTEN RESPONSE. SEC. | | | R301.1 FBC-RESIDENTIAL. | | | RESPONSE: | | | LOADS SPECIFIED ON "DESIGN PARAMETERS" DON'T MATCH | | | LOADS SPECIFIED ON "STRUCTURAL NOTES" ON THE SAME | | | SHEET. ENGINEER TO REVISE INFORMATION AS REQUIRED TO | | | MATCH. | | | | | | 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN | | | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY | | | AMENDMENTS. | | | | | | NOTE: WHEN SURVEY IS SUBMITTED ADDITIONAL COMMENTS MAY | | | APPLY DEPENDING ON THE DISTANCE FROM THE STRUCTURE TO | | | THE PROPERTY LINES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-08-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-08-23 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-08-22 |
Time |
18:27 |
Sent To |
|
|
| Notes |
| 2017-08-22 19:00:11 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, BUILDING | | | REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT. | | | BRING BACK COUNTY STAMPED PLANS AND COPY OF IMPACT FEES | | | PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | | | | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED | | | BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | | | | 3- THE PROPOSED BEDROOM NEEDS THE EMERGENCY ESCAPE AND | | | RESCUE OPENING AS REQUIRED BY SEC. R310.1 | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | 4- PROVIDE COMPLIANCE WITH THE LIGHT AND VENTILATION | | | REQUIREMENTS FOR EACH ROOM AS REQUIRED BY SEC. R303.1 | | | FBC-RESIDENTIAL. | | | | | | 5- PROVIDE COMPLIANCE WITH THE HEATING REQUIREMENTS FOR | | | EACH ROOM AS REQUIRED BY SEC. R303.9 FBC-RESIDENTIAL. | | | | | | 6- ENGINEER OF RECORD TO SPECIFY THE DESIGN PRESSURES | | | FOR THE DOORS AND WINDOWS. SEC. R301.1 FBC-RESIDENTIAL. | | | | | | 7- PLANS SPECIFY EXISTING 3'-0 X 6'-8" ENTRY DOOR AND | | | EXISTING SINGLE HUNG WINDOW. THERE ARE NO CITY RECORDS | | | FOR THE INSTALLATION OF THE ENTRY DOOR. ALSO, PHOTOS ON | | | THE INTERNET WHEN THE HOUSE WAS FOR SALE SHOW A GARAGE | | | WITH NO DOORS, EXCEPT FOR THE OPENING FOR A GARAGE | | | DOOR. AND THE WINDOW SEEMS TO BE FAIRLY NEW. SEE | | | ATTACHED PHOTO. PERMIT IS REQUIRED FOR THE INSTALLATION | | | OF NEW DOOR AND REPLACEMENT OF WINDOWS. PRODUCT | | | APPROVALS WILL BE REQUIRED. SEE ITEM # 8 BELOW. REVISE | | | INFORMATION ON PLANS AND PROVIDE COMPLETE INFORMATION | | | FOR THE FRAMING OF THE ENTRY DOOR. SEC. R301.1 | | | FBC-RESIDENTIAL. | | | | | | 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) ENTRY DOOR AS SHOWN ON PLANS. | | | | | | B) SINGLE HUNG WINDOW AS SHOWN PLANS. | | | | | | C) HURRICANE SHUTTERS IF WINDOW AND DOORS WITH GLAZING | | | DON'T HAVE IMPACT GLAZING. AND, PROVIDE COMPLETE | | | INSTALLATION SCHEDULE. SEE CITY SAMPLE. | | | | | | 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 10- REVISE CODES FOR REFERENCE INFORMATION ON SHEET | | | A.1: THIS IS ALTERATION LEVEL 3 NOT 2 AND CHANGE OF | | | OCCUPANCY. REVISE AS REQUIRED. SEE SEC. 505 AND 506 | | | FBC-EXISTING BUILDING, 5TH EDITION (2014). | | | | | | 11- ENGINEER OF RECORD TO CLARIFY WHY THE ROOF LIVE | | | LOAD SPECIFIED ON THE DESIGN PARAMETERS AND STRUCTURAL | | | NOTE #2 ON SHEET A.1 IS ONLY 10PSF?. WHERE IS THIS | | | DESIGN CRITERIA TAKEN FROM? PROVIDE WRITTEN RESPONSE. | | | SEC. R301.1 FBC-RESIDENTIAL. ALSO, CLARIFY WHY THE | | | BOTTOM CHORD DEAD LOAD IS 30PSF?. WHAT IS THIS TRUSS | | | SUPPORTING?. | | | | | | 12- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | | CONTRACTOR'S OVERHEAD AND PROFIT (EVEN FOR | | | OWNER/BUILDERS) AND ALL DESIGN PROFESSIONAL FEES AS | | | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE THE | | | VALUATION AS REQUIRED. | | | | | | NOTE: WHEN SURVEY IS SUBMITTED ADDITIONAL COMMENTS MAY | | | APPLY DEPENDING ON THE DISTANCE FROM THE STRUCTURE TO | | | THE PROPERTY LINES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-03-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-03-05 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-03-05 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2018-03-05 11:12:03 | NO CHANGES TO PREVIOUSLY APPROVED PLAN STAMPED SHEETS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-02-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-02-06 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-02-06 |
Time |
08:29 |
Sent To |
|
|
| Notes |
| 2018-02-02 17:17:35 | NEW DRAWINGS SUBMITTED. JG. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-12-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-12-05 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-12-05 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-08-22 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-08-22 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-08-22 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2017-08-22 16:35:44 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE | | | DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN, A | | | LICENSED PROFESSIONAL. FBC 107.2.1, FS 471, 481 | | | 2. PROVIDE REQUIRED SMOKE ALARMS. PROVIDE FLOOR PLAN OF | | | THE REMAINDER OF THE HOME, SHOWING EXISTING LOCATIONS | | | OF SMOKE ALARMS. IF NONE ARE EXISTING, OR NOT TO CODE, | | | SHOW AS NEW INSTALLATIONS. FBC R314.3 | | | 3. AFCI PROTECTION IS NOT INDICATED FOR ANY OF THE NEW | | | CIRCUITS. ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE | | | BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT | | | FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, | | | LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, | | | CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL | | | HAVE AFCI PROTECTION. PROVIDE CORRECTION. NEC 210.12; | | | FBC RE3902.12 | | | 4. BEDROOM DOES NOT COMPLY WITH THE WALL SPACING | | | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE | | | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG | | | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET | | | FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC | | | 210.52; FBC RE3901.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
P |
Date |
2018-03-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-03-12 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-03-12 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2018-03-12 15:01:23 | OWNER SIGNED ENERGY CALCS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-03-09 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-02-15 |
Time |
13:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-02-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-02-06 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-01-22 |
Time |
15:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-12-06 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-12-06 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-11-06 |
Time |
13:24 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-08-25 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2017-08-25 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2017-08-08 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2018-02-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-02-02 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-02-02 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2018-02-02 15:51:15 | NO FEES. MU-18-1752. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2017-11-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-11-14 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-11-14 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2017-11-14 08:26:39 | | | | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT. | | | BRING BACK COUNTY STAMPED PLANS AND COPY OF IMPACT FEES | | | PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-08-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-08-23 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-08-23 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2017-08-23 12:38:21 | | | | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT. | | | BRING BACK COUNTY STAMPED PLANS AND COPY OF IMPACT FEES | | | PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-03-09 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-03-09 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2018-02-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-02-02 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-02-02 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2018-02-02 17:26:12 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, THIRD | | | MECHANICAL REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE NOT | | | ACCEPTABLE. THEY ARE NOT DONE WITH AN APPROVED METHOD. | | | NEED TO PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS | | | BASED ON THE ORIENTATION OF THE BUILDING AS REQUIRED BY | | | SEC. R403.6 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | NOTE: PLEASE MAKE SURE EQUIPMENT LISTED IN THE | | | EQUIPMENT SIZING CALCULATIONS MATCHES EQUIPMENT LISTED | | | IN THE A/C PLAN TO AVOID CONFLICTS/DELAYS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-11-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-11-14 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-11-14 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2017-11-14 11:07:38 | | | | | | | NOTE: | | | 01/05/18 OWNER P/U PLUMBING/MECHANICAL DRAWING TO GET | | | NAME AND SIGNATURE OF DESIGNER OF RECORD. JG. | | | | | | | | | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, SECOND | | | MECHANICAL REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- DRAWING P/M: PROVIDE THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. | | | 107.2.1 CITY AMENDMENTS. | | | RESPONSE: | | | NEED TO PROVIDE THE NAME OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. ONLY A SIGNATURE WAS PROVIDED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-08-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-08-23 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-08-23 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2017-08-23 17:57:09 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, MECHANICAL | | | REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- EQUIPMENT SCHEDULE ON SHEET P/M SPECIFIES "SPLIT | | | SYSTEM EQUIPMENT SCHEDULE". THERE IS NOT SPLIT SYSTEM | | | SHOWN ON PLANS. REVISE AS REQUIRED. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 2- EQUIPMENT LISTED ON THE EQUIPMENT SCHEDULE DOESN'T | | | PROVIDE HEATING. HEATING IS REQUIRED BY SEC. R303.9 | | | FBC-RESIDENTIAL, 5TH EDITION (2014). IT DOESN'T COMPLY. | | | REVISE AS REQUIRED. | | | | | | 3- DRAWING P/M: PROVIDE THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-03-09 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-03-09 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2018-02-02 17:17:01 | NEW DRAWINGS SUBMITTED. JG. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-12-06 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-12-06 |
Time |
06:24 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-12-06 |
Time |
06:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-08-25 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2017-08-25 |
Time |
06:48 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2017-08-24 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2017-08-25 06:50:14 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) WET BAR CAN NOT DISCHARGE INTO BATHROOM GROUP** | | | | | | 912.1 HORIZONTAL WET VENT PERMITTED.ANY COMBINATION OF | | | FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME | | | FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL | | | WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR | | | THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF | | | THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE | | | DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN | | | CONNECTION TO THE HORIZONTAL BRANCH DRAIN. EACH | | | WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO | | | THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL | | | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2018-02-28 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-02-28 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-02-28 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-01-31 |
|
|
Cont ID |
|
| Sent By |
AW |
Date |
2018-02-01 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-01-31 |
Time |
11:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-11-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2017-11-27 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-11-27 13:42:34 | ******************************ZONING REVIEW | | | FAILED**************************************** | | | | | | THE GARAGE CONVERSION IS PERMITTED, BUT IT WILL NOT BE | | | PERMITTED TO HAVE A FULL KITCHEN. PLEASE PROVIDE A | | | SURVEY SHOWING THE EXISTING PROPERTY WITH THE GARAGE | | | AND PRINCIPAL BUILDING. PLEASE LET ME KNOW WHAT | | | QUESTIONS YOU MAY HAVE. | | | | | | THANKS, | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2017-08-11 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2017-08-11 |
Time |
10:49 |
Rev Time |
|
| Received By |
awooten |
Date |
2017-08-11 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-08-11 10:48:57 | ******************************ZONING REVIEW | | | FAILED**************************************** | | | | | | PLEASE PROVIDE A SURVEY SHOWING THE SETBACKS OF THE | | | ACCESSORY STRUCTURE AND PRINCIPAL STRUCTURE. PLEASE LET | | | ME KNOW WHAT QUESTIONS YOU MAY HAVE. | | | | | | THANKS, | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|