Plan Review Details - Permit 17080429
Plan Review Stops For Permit 17080429
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-03-12 Cont ID  
Sent By jgomez Date 2018-03-12 Time 15:18 Rev Time 0.00
Received By jgomez Date 2018-03-12 Time 15:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-03-09 Cont ID  
Sent By jgomez Date 2018-03-09 Time 14:17 Rev Time 0.00
Received By jgomez Date 2018-03-09 Time 12:24 Sent To  
Notes
2018-03-09 12:57:44 
 RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, FOURTH
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE
 COMPLIANCE CERTIFICATION.
 THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-02-05 Cont ID  
Sent By jgomez Date 2018-02-02 Time 17:13 Rev Time 0.00
Received By jgomez Date 2018-02-02 Time 15:14 Sent To  
Notes
2018-02-02 15:15:27RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, THIRD
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) COOLING SYSTEM AND EFFICIENCY SPECIFIED ON ITEM #12A
 AND 12B DON'T MATCH PLANS. THERE IS NO DUCTLESS MINI
 SPLIT UNIT SPECIFIED ON PLANS. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.1 FBC -ENERGY CONSERVATION.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME, PERMITTING OFFICE. SEC.
 R101.5.1.1.1 FBC -ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) WINDOW AREA SPECIFIED ON ITEM #6(C) DOESN'T MATCH
 PLANS. NOTE: THERE ARE TWO WINDOWS SHOWN ON PLANS. SEE
 PLAN FOR SIZES AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.1 FBC -ENERGY CONSERVATION.
  
 D) REVISE ITEM #9. WALL TYPE IS MASONRY NOT WOOD FRAME.
 CALCULATIONS NEED TO SHOW THE R-4.1 INSULATION ON ITEM
 # 9A2 NOT 9A1. REVISE AS REQUIRED. SEC. R101.5.1.1.1
 FBC -ENERGY CONSERVATION.
  
 NOTE:
 WINDOW NEED LABEL SHOWING THE ENERGY U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ON THE ENERGY CALCULATIONS
 SUBMITTED. MAKE SURE THE WINDOWS MEET THIS CRITERIA
 PRIOR TO PURCHASING THEM TO AVOID CONFLICTS.
  
 2- NEW COMMENT:
 A) THE BUILDING CODE UNDER WHICH THIS PERMIT
 APPLICATION WAS SUBMITTED WAS THE 2014 FBC. CLARIFY WHY
 THE DESIGN PARAMETERS AND CODES FOR REFERENCE
 INFORMATION AND STRUCTURAL NOTE #1 WAS CHANGED ON SHEET
 A.1 TO REFERENCE THE 2017 FBC?. THERE IS NO REASON TO
 CHANGE THE REFERENCED CODE. REVISE AS REQUIRED TO
 REFERENCE THE CORRECT CODE, THE 2014 FBC AS REQUIRED BY
 CHAPTER 553 FLORIDA STATUTE.
  
 B) THE CURRENT ASCE STANDARD IS THE ASCE 7-10 NOT ASCE
 7-16. REVISE DESIGN PARAMETERS INFORMATION AND
 STRUCTURAL NOTE #2(C) AS REQUIRED BY CHAPTER 46
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-11-14 Cont ID  
Sent By jgomez Date 2017-11-14 Time 08:23 Rev Time 0.00
Received By jgomez Date 2017-11-13 Time 18:21 Sent To  
Notes
2017-11-13 18:44:17 
 NOTE:
 01/05/18 OWNER P/U PLUMBING/MECHANICAL DRAWING TO GET
 NAME AND SIGNATURE OF DESIGNER OF RECORD. JG.
  
  
 RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, SECOND
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF IMPACT FEES
 PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
 RESPONSE: THIS MAY BE DONE LATER AFTER THE PLANS ARE
 APPROVED BY ALL TRADES AND PERMIT IS READY TO BE
 ISSUED.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 3- THE PROPOSED BEDROOM NEEDS THE EMERGENCY ESCAPE AND
 RESCUE OPENING AS REQUIRED BY SEC. R310.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE:
 SINGLE HUNG WINDOW SIZE SPECIFIED ON PLANS DON'T COMPLY
 WITH THE MINIMUM CLEAR HEIGHT REQUIRED BY SEC. R310.1.2
 FBC-RESIDENTIAL. FLOOR PLAN ON SHEET A.1 SPECIFIES 53 X
 51 SINGLE HUNG WINDOW. THIS WINDOW SIZE DOESN'T PROVIDE
 THE 24" CLEAR HEIGHT OPENING. ALSO, FLOOR PLAN ON SHEET
 A.1 SPECIFIES SH-25, WHILE SOUTH ELEVATION ON SHEET A.2
 SPECIFIES SH-34. INFORMATION DOESN'T MATCH. CLEARLY
 SPECIFY ONE SIZE OF WINDOW THAT COMPLIES WITH ALL THE
 EGRESS REQUIREMENTS.
  
 NOTE: ENGINEER OF RECORD MAY BE CHARGED 4 TIMES THE
 PLAN REVIEW AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B)
 FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
 4- PLANS SPECIFY EXISTING 3'-0 X 6'-8" ENTRY DOOR AND
 EXISTING SINGLE HUNG WINDOW. THERE ARE NO CITY RECORDS
 FOR THE INSTALLATION OF THE ENTRY DOOR. ALSO, PHOTOS ON
 THE INTERNET WHEN THE HOUSE WAS FOR SALE SHOW A GARAGE
 WITH NO DOORS, EXCEPT FOR THE OPENING FOR A GARAGE
 DOOR. AND THE WINDOW SEEMS TO BE FAIRLY NEW. SEE
 ATTACHED PHOTO. PERMIT IS REQUIRED FOR THE INSTALLATION
 OF NEW DOOR AND REPLACEMENT OF WINDOWS. PRODUCT
 APPROVALS WILL BE REQUIRED. SEE ITEM # 8 BELOW. REVISE
 INFORMATION ON PLANS AND PROVIDE COMPLETE INFORMATION
 FOR THE FRAMING OF THE ENTRY DOOR. SEC. R301.1
 FBC-RESIDENTIAL.
 RESPONSE:
 PLANS STILL CALL FOR EXISTING DOOR. PLANS WERE REVISED
 SHOWING THE VERTICAL REINFORCEMENT FOR THE WINDOW, BUT
 DON'T SHOW THE VERTICAL REINFORCEMENT FOR THE ENTRY
 DOOR. REVISE ALL PLANS AS REQUIRED.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) SINGLE HUNG WINDOW AS SHOWN PLANS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 C) HURRICANE SHUTTERS IF WINDOW AND DOORS WITH GLAZING
 DON'T HAVE IMPACT GLAZING. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- ENGINEER OF RECORD TO CLARIFY WHY THE ROOF LIVE LOAD
 SPECIFIED ON THE DESIGN PARAMETERS AND STRUCTURAL NOTE
 #2 ON SHEET A.1 IS ONLY 10PSF?. WHERE IS THIS DESIGN
 CRITERIA TAKEN FROM? PROVIDE WRITTEN RESPONSE. SEC.
 R301.1 FBC-RESIDENTIAL.
 RESPONSE:
 LOADS SPECIFIED ON "DESIGN PARAMETERS" DON'T MATCH
 LOADS SPECIFIED ON "STRUCTURAL NOTES" ON THE SAME
 SHEET. ENGINEER TO REVISE INFORMATION AS REQUIRED TO
 MATCH.
  
 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
  
 NOTE: WHEN SURVEY IS SUBMITTED ADDITIONAL COMMENTS MAY
 APPLY DEPENDING ON THE DISTANCE FROM THE STRUCTURE TO
 THE PROPERTY LINES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-23 Cont ID  
Sent By jgomez Date 2017-08-23 Time 17:09 Rev Time 0.00
Received By jgomez Date 2017-08-22 Time 18:27 Sent To  
Notes
2017-08-22 19:00:11RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, BUILDING
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF IMPACT FEES
 PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 3- THE PROPOSED BEDROOM NEEDS THE EMERGENCY ESCAPE AND
 RESCUE OPENING AS REQUIRED BY SEC. R310.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- PROVIDE COMPLIANCE WITH THE LIGHT AND VENTILATION
 REQUIREMENTS FOR EACH ROOM AS REQUIRED BY SEC. R303.1
 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLIANCE WITH THE HEATING REQUIREMENTS FOR
 EACH ROOM AS REQUIRED BY SEC. R303.9 FBC-RESIDENTIAL.
  
 6- ENGINEER OF RECORD TO SPECIFY THE DESIGN PRESSURES
 FOR THE DOORS AND WINDOWS. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- PLANS SPECIFY EXISTING 3'-0 X 6'-8" ENTRY DOOR AND
 EXISTING SINGLE HUNG WINDOW. THERE ARE NO CITY RECORDS
 FOR THE INSTALLATION OF THE ENTRY DOOR. ALSO, PHOTOS ON
 THE INTERNET WHEN THE HOUSE WAS FOR SALE SHOW A GARAGE
 WITH NO DOORS, EXCEPT FOR THE OPENING FOR A GARAGE
 DOOR. AND THE WINDOW SEEMS TO BE FAIRLY NEW. SEE
 ATTACHED PHOTO. PERMIT IS REQUIRED FOR THE INSTALLATION
 OF NEW DOOR AND REPLACEMENT OF WINDOWS. PRODUCT
 APPROVALS WILL BE REQUIRED. SEE ITEM # 8 BELOW. REVISE
 INFORMATION ON PLANS AND PROVIDE COMPLETE INFORMATION
 FOR THE FRAMING OF THE ENTRY DOOR. SEC. R301.1
 FBC-RESIDENTIAL.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS.
  
 B) SINGLE HUNG WINDOW AS SHOWN PLANS.
  
 C) HURRICANE SHUTTERS IF WINDOW AND DOORS WITH GLAZING
 DON'T HAVE IMPACT GLAZING. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- REVISE CODES FOR REFERENCE INFORMATION ON SHEET
 A.1: THIS IS ALTERATION LEVEL 3 NOT 2 AND CHANGE OF
 OCCUPANCY. REVISE AS REQUIRED. SEE SEC. 505 AND 506
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 11- ENGINEER OF RECORD TO CLARIFY WHY THE ROOF LIVE
 LOAD SPECIFIED ON THE DESIGN PARAMETERS AND STRUCTURAL
 NOTE #2 ON SHEET A.1 IS ONLY 10PSF?. WHERE IS THIS
 DESIGN CRITERIA TAKEN FROM? PROVIDE WRITTEN RESPONSE.
 SEC. R301.1 FBC-RESIDENTIAL. ALSO, CLARIFY WHY THE
 BOTTOM CHORD DEAD LOAD IS 30PSF?. WHAT IS THIS TRUSS
 SUPPORTING?.
  
 12- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT (EVEN FOR
 OWNER/BUILDERS) AND ALL DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE THE
 VALUATION AS REQUIRED.
  
 NOTE: WHEN SURVEY IS SUBMITTED ADDITIONAL COMMENTS MAY
 APPLY DEPENDING ON THE DISTANCE FROM THE STRUCTURE TO
 THE PROPERTY LINES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-03-05 Cont ID  
Sent By jpearson Date 2018-03-05 Time 11:12 Rev Time 0.00
Received By jpearson Date 2018-03-05 Time 11:12 Sent To  
Notes
2018-03-05 11:12:03NO CHANGES TO PREVIOUSLY APPROVED PLAN STAMPED SHEETS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-02-06 Cont ID  
Sent By jpearson Date 2018-02-06 Time 13:07 Rev Time 0.00
Received By jpearson Date 2018-02-06 Time 08:29 Sent To  
Notes
2018-02-02 17:17:35NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-05 Cont ID  
Sent By jpearson Date 2017-12-05 Time 09:21 Rev Time 0.00
Received By jpearson Date 2017-12-05 Time 09:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By jpearson Date 2017-08-22 Time 16:35 Rev Time 0.00
Received By jpearson Date 2017-08-22 Time 16:35 Sent To  
Notes
2017-08-22 16:35:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN, A
 LICENSED PROFESSIONAL. FBC 107.2.1, FS 471, 481
 2. PROVIDE REQUIRED SMOKE ALARMS. PROVIDE FLOOR PLAN OF
 THE REMAINDER OF THE HOME, SHOWING EXISTING LOCATIONS
 OF SMOKE ALARMS. IF NONE ARE EXISTING, OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. FBC R314.3
 3. AFCI PROTECTION IS NOT INDICATED FOR ANY OF THE NEW
 CIRCUITS. ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE
 BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL
 HAVE AFCI PROTECTION. PROVIDE CORRECTION. NEC 210.12;
 FBC RE3902.12
 4. BEDROOM DOES NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status P Date 2018-03-12 Cont ID  
Sent By jgomez Date 2018-03-12 Time 15:18 Rev Time 0.00
Received By jgomez Date 2018-03-12 Time 15:00 Sent To  
Notes
2018-03-12 15:01:23OWNER SIGNED ENERGY CALCS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-03-09 Cont ID  
Sent By jgomez Date 2018-03-09 Time 15:07 Rev Time 0.00
Received By jgomez Date 2018-02-15 Time 13:08 Sent To  
Notes
2018-02-16 13:08:49R35

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-06 Cont ID  
Sent By jgomez Date 2018-02-06 Time 14:59 Rev Time 0.00
Received By jgomez Date 2018-01-22 Time 15:47 Sent To  
Notes
2018-01-23 15:47:39R06

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-06 Cont ID  
Sent By tklarge Date 2017-12-06 Time 06:35 Rev Time 0.00
Received By tklarge Date 2017-11-06 Time 13:24 Sent To I
Notes
2017-11-07 13:24:16R05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-25 Cont ID  
Sent By thunt Date 2017-08-25 Time 06:50 Rev Time 0.00
Received By thunt Date 2017-08-08 Time 11:25 Sent To  
Notes
2017-08-09 11:26:04R20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-02-02 Cont ID  
Sent By jgomez Date 2018-02-02 Time 15:50 Rev Time 0.00
Received By jgomez Date 2018-02-02 Time 15:41 Sent To  
Notes
2018-02-02 15:51:15NO FEES. MU-18-1752.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-11-14 Cont ID  
Sent By jgomez Date 2017-11-14 Time 08:26 Rev Time 0.00
Received By jgomez Date 2017-11-14 Time 08:26 Sent To  
Notes
2017-11-14 08:26:39 
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF IMPACT FEES
 PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-08-23 Cont ID  
Sent By jgomez Date 2017-08-23 Time 12:38 Rev Time 0.00
Received By jgomez Date 2017-08-23 Time 12:38 Sent To  
Notes
2017-08-23 12:38:21 
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF IMPACT FEES
 PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-03-09 Cont ID  
Sent By jgomez Date 2018-03-09 Time 14:30 Rev Time 0.00
Received By jgomez Date 2018-03-09 Time 14:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-02-05 Cont ID  
Sent By jgomez Date 2018-02-02 Time 17:25 Rev Time 0.00
Received By jgomez Date 2018-02-02 Time 17:25 Sent To  
Notes
2018-02-02 17:26:12RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, THIRD
 MECHANICAL REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE NOT
 ACCEPTABLE. THEY ARE NOT DONE WITH AN APPROVED METHOD.
 NEED TO PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS
 BASED ON THE ORIENTATION OF THE BUILDING AS REQUIRED BY
 SEC. R403.6 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 NOTE: PLEASE MAKE SURE EQUIPMENT LISTED IN THE
 EQUIPMENT SIZING CALCULATIONS MATCHES EQUIPMENT LISTED
 IN THE A/C PLAN TO AVOID CONFLICTS/DELAYS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-14 Cont ID  
Sent By jgomez Date 2017-11-14 Time 11:04 Rev Time 0.00
Received By jgomez Date 2017-11-14 Time 07:55 Sent To  
Notes
2017-11-14 11:07:38 
  
 NOTE:
 01/05/18 OWNER P/U PLUMBING/MECHANICAL DRAWING TO GET
 NAME AND SIGNATURE OF DESIGNER OF RECORD. JG.
  
  
 RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, SECOND
 MECHANICAL REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- DRAWING P/M: PROVIDE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS.
 RESPONSE:
 NEED TO PROVIDE THE NAME OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. ONLY A SIGNATURE WAS PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-23 Cont ID  
Sent By jgomez Date 2017-08-23 Time 17:40 Rev Time 0.00
Received By jgomez Date 2017-08-23 Time 12:35 Sent To  
Notes
2017-08-23 17:57:09RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, MECHANICAL
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SCHEDULE ON SHEET P/M SPECIFIES "SPLIT
 SYSTEM EQUIPMENT SCHEDULE". THERE IS NOT SPLIT SYSTEM
 SHOWN ON PLANS. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- EQUIPMENT LISTED ON THE EQUIPMENT SCHEDULE DOESN'T
 PROVIDE HEATING. HEATING IS REQUIRED BY SEC. R303.9
 FBC-RESIDENTIAL, 5TH EDITION (2014). IT DOESN'T COMPLY.
 REVISE AS REQUIRED.
  
 3- DRAWING P/M: PROVIDE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-03-09 Cont ID  
Sent By jgomez Date 2018-03-09 Time 14:47 Rev Time 0.00
Received By jgomez Date 2018-03-09 Time 14:47 Sent To  
Notes
2018-02-02 17:17:01NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-12-06 Cont ID  
Sent By tklarge Date 2017-12-06 Time 06:24 Rev Time 0.00
Received By tklarge Date 2017-12-06 Time 06:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-25 Cont ID  
Sent By thunt Date 2017-08-25 Time 06:48 Rev Time 0.00
Received By thunt Date 2017-08-24 Time 16:56 Sent To  
Notes
2017-08-25 06:50:14PLUMBING 1ST REVIEW**DENIED**
  
 1) WET BAR CAN NOT DISCHARGE INTO BATHROOM GROUP**
  
 912.1 HORIZONTAL WET VENT PERMITTED.ANY COMBINATION OF
 FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR
 THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF
 THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE
 DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION TO THE HORIZONTAL BRANCH DRAIN. EACH
 WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO
 THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2018-02-28 Cont ID  
Sent By awooten Date 2018-02-28 Time 15:45 Rev Time 0.00
Received By awooten Date 2018-02-28 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-01-31 Cont ID  
Sent By AW Date 2018-02-01 Time 11:56 Rev Time 0.00
Received By awooten Date 2018-01-31 Time 11:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2017-11-27 Time   Rev Time 0.00
Received By   Date 2017-11-27 Time   Sent To  
Notes
2017-11-27 13:42:34******************************ZONING REVIEW
 FAILED****************************************
  
 THE GARAGE CONVERSION IS PERMITTED, BUT IT WILL NOT BE
 PERMITTED TO HAVE A FULL KITCHEN. PLEASE PROVIDE A
 SURVEY SHOWING THE EXISTING PROPERTY WITH THE GARAGE
 AND PRINCIPAL BUILDING. PLEASE LET ME KNOW WHAT
 QUESTIONS YOU MAY HAVE.
  
 THANKS,
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-11 Cont ID  
Sent By awooten Date 2017-08-11 Time 10:49 Rev Time  
Received By awooten Date 2017-08-11 Time   Sent To  
Notes
2017-08-11 10:48:57******************************ZONING REVIEW
 FAILED****************************************
  
 PLEASE PROVIDE A SURVEY SHOWING THE SETBACKS OF THE
 ACCESSORY STRUCTURE AND PRINCIPAL STRUCTURE. PLEASE LET
 ME KNOW WHAT QUESTIONS YOU MAY HAVE.
  
 THANKS,
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]