| 2017-10-20 10:56:04 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 27080289 |
| | ADD: 5851 45TH ST. |
| | CONT: WYNN BUILDERS |
| | TEL: 954-568-9969 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. OCT. 20/2017 |
| | ACTION: DENIED |
| | |
| | 1) THIS BUILDING WILL REQUIRE A RESIDENT INSPECTOR. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 110.3.9 OTHER INSPECTIONS SERVICES. THE |
| | BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY |
| | OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE |
| | MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED |
| | INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION |
| | HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND |
| | RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION |
| | OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH |
| | REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY |
| | A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: |
| | |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER |
| | SQUARE INCH |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION , TILT WALL ( A701, DETAILS 17 |
| | & 20 AS WELL AS STEEL BUILDING WITH GIRTS, PURLINS AND |
| | STEEL WALL & ROOF PANELS. |
| | |
| | 1A) 2ND REQUEST. THE SUBMITTED FORMS ARE FOR SPECIAL |
| | INSPECTOR, OR FOR THRESHOLD BUILDINGS NOT RESIDENT |
| | INSPECTOR FORMS, FORMS MUST BE SIGNED BY ALL PARTIES |
| | NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT. |
| | |
| | 1B)2ND RESPONSE, THE RESPONSE INDICATES RESUME IN |
| | PACKAGE FROM ATC GROUP SERVICE LLC. NOT IN PACKAGE. |
| | FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 1C) 2ND REQUEST. RESPONSE AGAIN STATES THE CONTRACTORS |
| | RESUME IS WITHIN THE PACKAGE, NO CONTRACTOR RESUME? IS |
| | IN THE PACKAGE. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 1D)2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF |
| | DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT |
| | ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS. |
| | |
| | 1E) 2ND REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 110.3.9 AND GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING RESIDENT INSPECTORS. COMMENT # 14. (3) |
| | COPIES OF ALL SHOP DRAWINGS (STAIRS, HANDRAILS, |
| | GUARDRAILS PRECAST WALL PANELS, , BAR JOIST, STEEL |
| | BEAMS, PRODUCT APPROVALS ETC.) MUST BE SUBMITTED TO THE |
| | BUILDING DEPARTMENT. TWO REVIEWED SETS OF CITY STAMPED |
| | DOCUMENTS WILL BE RETURNED TO THE JOB SITE BEFORE ANY |
| | OF THE ABOVE LISTED ITEMS ARE INSTALLED ON THE JOB. |
| | 2 SETS OF PLANS SUBMITTED. |
| | 2 SETS OF BUTLER STEEL BUILDING PLANS. |
| | 2 SIGNED AND SEALED GEOTECHNICAL ENGINEERING REPORTS |
| | SUBMITTED. |
| | 2 STRUCTURAL CALCULATIONS FOR DRY EXPANSION |
| | 2 STRUCTURAL DESIGN DATA REPORTS SUBMITTED. |
| | |
| | 1F) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACHS |
| | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| | FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 2) SEMI-COMPLIED 2 SIGNED AND SEALED SOILS REPORTS WERE |
| | SUBMITTED, NOT 3. THE STRUCTURAL SHEET S0.1 INDICATES |
| | THERE WAS A SOILS REPORT BY TERRACON CONSULTANTS, |
| | HD145102 DATED DEC. 30/2014. PLEASE SUBMIT 3 ORIGINAL |
| | SIGNED AND SEALED SOILS REPORTS. |
| | |
| | 2014 FBC-B 1803.5.2. QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 3) PROVISO: ENW WILL REVIEW TILT WALL PANEL EMBED SHOP |
| | DRAWINGS. |
| | |
| | 4) SEMI- COMPLIED, ONLY 2 SIGNED AND SEALED DOCUMENTS |
| | SUBMITTED, NEED A THIRD SET OF STRUCTURAL CALCULATIONS |
| | FOR DRY EXPANSION BY JOSE PARADA P.E. THIS REPORT THE |
| | COVERSHEET HAS BEEN SIGNED AND SEALED THERE IS NO |
| | REFERENCE AS TO HOW MANY PAGES ARE WITHIN THE REPORT |
| | NOR IS THERE AN INDEX PAGE THAT INDICATES THE AMOUNT OF |
| | PAGES COVERED UNDER THIS SEAL. NOTE IF A INDEX PAGE IS |
| | SUPPLIED, IT TO NEEDS TO BE SIGNED AND SEALED. |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| | COVERED UNDER THE COVER SHEET OR INDEX SHEET. . |
| | |
| | 5) 2ND REQUEST. THE BUTLER MANUFACTURED STEEL BUILDING |
| | DRAWINGS AND STRUCTURAL DESIGN DATA HAVE BEEN SUBMITTED |
| | IN THE PERMIT PACKAGE BUT NOT BEEN REVIEWED BY THE |
| | DESIGNER OF RECORD. ONLY 2 SETS SUBMITTED. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 6)2ND REQUEST. THE RESPONSE INDICATES ON SHEET A302 IN |
| | THE FINISH SCHEDULE THE FLORIDA APPROVAL NUMBERS, BUT |
| | THE ACTUAL FLORIDA PRODUCT APPROVAL COVERSHEETS AND ALL |
| | TECHNICAL SHEETS NEED TO BE SUBMITTED, 3 SETS. IT IS |
| | CRUCIAL TO SEE THE SPANS AND THE ASSOCIATED PRESSURES |
| | FOR THE WALLS AND ROOF CLADDING. |
| | MISSING PRODUCT APPROVALS: 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | (B) WINDOWS |
| | (C) PANEL WALLS: WALL LOUVERS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | |
| | 7) SEMI- COMPLIED, UNTIL THE ACTUAL PRINTED PRODUCT |
| | APPROVAL DOCUMENTS CAN BE VERIFIED THE LISTING THEM IN |
| | THE FINISH SCHEDULE DOES NOT CONSTITUTE CODE |
| | COMPLIANCE, TYPE OF WALL AND ROOF PANELS TO BE |
| | VERIFIED, WIDTH OF PANEL, CONFIGURATION OF PANEL, GAUGE |
| | OF MATERIAL, SPANS OF GURTS AND PURLINS VERSES |
| | PRESSURES, CODE COMPLIANCE CANNOT BE DETERMINED. W. P. |
| | B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 8) 2ND REQUEST. PLEASE PROVIDE THE FL 12492.3 TO VERIFY |
| | CODE COMPLIANCE. |
| | PLEASE NOTE THE STRUCTURAL SHEET S0.1 GIVES THE WIND |
| | DESIGN CRITERIA BUT NO PRESSURES. THE BUTLER BUILDING |
| | PLANS SHEET 2 PROVIDES VASD PRESSURES FOR S1, S2, S3, |
| | S4, S5 & P. IN THE COLUMNS P, S1 S2 & S3 THE PRESSURES |
| | FOR 100 SQ. FT. AND LARGER ARE THE SAME PRESSURE IN |
| | EACH OF THESE COLUMNS. IN REVIEWING THE ASCE 7-10 |
| | FIGURE 30.5-1 ENCLOSED BUILDINGS H< 60 FT. THE PRESSURE |
| | DECREASES IN EACH SQ. FT. CATEGORY. PLEASE PROVIDE WHY |
| | THIS IS? 1609.1.1 DETERMINATION OF WIND LOADS. ASCE |
| | 7-10 FIGURE 30.5.1. |
| | |
| | 9) COMPLIED. IMPACT FEES. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |