| 2017-08-16 14:20:49 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17080179 |
| | W. P. B. PERMIT: 16050912 |
| | ADD: 1451 S OLIVE AVE. |
| | CONT: GILBANE |
| | TEL: 561-236-7052/ MIKE IZZO |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUGUST 16/ 2017 |
| | ACTION: DENIED |
| | |
| | SUBMITTAL-07B-075400-017 |
| | |
| | 1) THE COMMERCIAL- RESIDENTIAL STRUCTURAL ENGINEERING, |
| | INC. REPORT ON FASTENING REQUIREMENTS FOR THE |
| | INSULATION BOARD ARE NOT SIGNED AND SEALED EITHER AN |
| | ELECTRONIC SIGNATURE NOR COPY OF A PAPER SIGNED AND |
| | SEALED ORIGINAL. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| | 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| | 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) SUBMITTAL 07B-075400-003 |
| | |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) ROOF HATCHES. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, |
| | MISSING PRODUCT APPROVALS: |
| | SARNATHERM TAPERED 20 PSI STATES IT HAS BOTH MIAMI-DADE |
| | AND FLORIDA STATE APPROVAL |
| | DENSDECK |
| | SARNAFASTENER # 15XP |
| | GRACE ICE & WATER SHIELD HT |
| | BILCO ROOF HATCH TYPE S OR TYPE E |
| | |
| | 3) IN THE ORIGINAL PERMIT 16050912 SHEET 0276_S002 |
| | UNDER THE HEADING STEEL ROOF DECK HAS A NOTE FOR THE |
| | REQUIRED VENTILATION WHEN INSULATION CONCRETE IS |
| | INSTALLED AND THE REQUIREMENT FOR SLOTTED OR PREFORMED |
| | METAL DECKING FOR VENTILATION. THERE IS NO SPEC IN THE |
| | PLANS FOR ROOF TOP INSULATION THIS MAYBE IN THE |
| | MANUFACTURERS SPEC FOR THE PRODUCT? 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | |
| | |
| | |