| 2017-08-16 09:32:56 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17080162 |
| | W. P. B. PERMIT: 16030381 |
| | ADD: 1301 SUMMIT BLVD. |
| | CONT: GAST CONSTRUCTION |
| | TEL: 561-281-1001 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUGUST 16/2017 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) SHEET A-101, A-200 & A-300 ALL SHOW REVISION # 3 |
| | NOTE # 27 WITH THE REVISION BEING A CHANGE FROM A |
| | FIBERGLASS DOOR TO A 1 ? INCH EXTERIOR GRADE IMPACT |
| | RATED HOLLOW METAL DOOR. PLEASE PROVIDE COMPLIANCE |
| | WITH: |
| | 1A) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | |
| | 1B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) SHEET A-200, A-300 & A-3.01 NOTE # 30 SHOW A |
| | REVISION FROM A MESH GUARD TO 1 ? INCH P. T. WOOD |
| | PICKETS, PLEASE PROVIDE CALCULATIONS FOR THE ANCHORING |
| | OF THE PICKET AND STRUCTURAL STRENGTH OF THE WOOD |
| | PICKET IN COMPLIANCE. PROVIDE SHOP DRAWING AND |
| | CALCULATIONS. |
| | 2014 FBC-B 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND |
| | GUARDS SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED |
| | LOAD OF 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF |
| | ASCE 7. |
| | |
| | 2014 FBC-B 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE |
| | RAILS (ALL THOSE EXCEPT THE HANDRAIL), BALUSTERS AND |
| | PANEL FILLERS SHALL BE DESIGNED TO RESIST A |
| | CONCENTRATED LOAD OF 50 POUNDS IN ACCORDANCE WITH |
| | SECTION 4.5.1 OF ASCE 7. |
| | |