Plan Review Details - Permit 17080143
Plan Review Stops For Permit 17080143
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-08-22 Cont ID  
Sent By jwitmer Date 2017-08-22 Time 16:03 Rev Time 0.00
Received By jwitmer Date 2017-08-18 Time 08:43 Sent To  
Notes
2017-08-22 16:04:09LIFT STATION NOT LOCATED IN A FLOOD ZONE,
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-09-18 Cont ID  
Sent By jpearson Date 2018-09-18 Time 12:40 Rev Time 0.00
Received By jpearson Date 2018-09-18 Time 12:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-27 Cont ID  
Sent By jpearson Date 2018-08-27 Time 15:28 Rev Time 0.00
Received By jpearson Date 2018-08-27 Time 15:28 Sent To I
Notes
2018-08-27 15:13:31CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
  
 NEW COMMENT.:
  
 5. THIS PLAN HAS TWO DIFFERENT ADDRESSES AND TWO PERMIT
 APPLICATIONS IN THE PACKET. IT IS NOT POSSIBLE TO ISSUE
 PART OF A PACKET. IT IS RECOMMENDED THAT THE PLANS BE
 SEPARATED FOR EACH LOCATION AND SUBMITTED AS TWO
 SEPARATE PACKETS WITH THE APPROPRIATE PERMIT
 APPLICATION. THIS PLAN REVIEW WILL REMAIN IN FAILED
 STATUS UNTIL SUCH TIME THAT THE COMMENTS FOR 18070142
 ARE ADDRESSED SATISFACTORILY, OR THE PERMITS ARE
 SEPARATED. WPB FBC 105.1, 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-16 Cont ID  
Sent By jpearson Date 2017-08-16 Time 10:15 Rev Time 0.00
Received By jpearson Date 2017-08-16 Time 10:15 Sent To  
Notes
2017-08-16 10:15:14CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE AIC RATING OF THE SERVICE
 EQUIPMENT, ATS, AND LIFT STATION CONTROL PANEL IS
 ADEQUATE. NEC 110.9, 110.10, 409.110(4)
 2. PROVIDE AIC RATING OF SERVICE DISCONNECT, ATS, AND
 LIFT STATION CONTROL PANEL. NEC 110.3, 110.9,
 409.110(4)
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PLAN SHOWS A 60KW GENERATOR, WHICH HAS A CAPACITY OF
 APPROXIMATELY 72 AMPS AT 480 VOLT. THE DEMAND LOAD
 SUPPLIED STATES THE LOAD IS 97.75 AMPS, WHICH EXCEEDS
 THE CAPACITY OF THE GENERATOR. PROVIDE CORRECTION. NEC
 702.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By pleduc Date 2018-08-21 Time   Rev Time 0.00
Received By pleduc Date 2018-08-20 Time 15:21 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-16 Cont ID  
Sent By pleduc Date 2017-08-16 Time   Rev Time 0.00
Received By pleduc Date 2017-08-15 Time 14:31 Sent To  
Notes
2017-08-15 15:13:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF REVIEW AND/OR COMPLIANCE
 WITH THE REQUIERMENTS OF NFPA 820, STANDARD FOR FIRE
 PROTECTION IN WASTEWATER TREATMENT AND COLLECTION
 FACILITIES, 2012 EDITION.
  
 COMBUSTIBLE GAS DETECTION SYSTEM AND NFPA 72 MONITORING
 MAY BE REQUIRED.
  
 PLEASE PROVIDE A REVIEW TO INCLUDE BUT NOT LIMITED TO:
  
 3.3.48* PUMPING STATION. A STRUCTURE THAT CONTAINS
 PUMPS AND APPURTENANT PIPING, VALVES, AND OTHER
 MECHANICAL AND ELECTRICAL EQUIPMENT FOR PUMPING
 WASTEWATER OR OTHER LIQUID.
 A.3.3.48 PUMPING STATION. ALSO CALLED LIFT STATION.
  
 3.3.72 WELL.
 3.3.72.1* DRY WELL. THE PORTION OF A PUMPING STATION
 DESIGNED TO PROVIDE ISOLATION AND SHELTER OR
 ACCOMMODATIONS FOR CONTROLS OR EQUIPMENT ASSOCIATED
 WITH PUMPING OF WASTEWATER AND DESIGNED TO COMPLETELY
 AND PERMANENTLY EXCLUDE WASTEWATER OR
 WASTEWATER-DERIVED ATMOSPHERES.
 3.3.72.2* WET WELL. THE PORTION OF THE PUMPING STATION
 THAT RECEIVES AND TEMPORARILY STORES WASTEWATER FOR THE
 PURPOSE OF PUMPING.
 A.3.3.72.1 DRYWELL. DRY WELLS CAN CONTAIN ACCIDENTAL
 LEAKAGE OF WASTEWATER FROM SHAFT SEALS OR OCCASIONAL
 SPILLS. A DRY WELL COULD CONTAIN EQUIPMENT SUCH AS
 PUMPS, MOTORS, FANS, WIRING, CONTROLS, LIGHTS AND
 ASSOCIATED
 WIRING DEVICES, AND OTHER ACCESSORIES.
 A.3.3.72.2 WET WELL. A WET WELL MIGHT OR MIGHT NOT
 CONTAIN ELECTRICAL EQUIPMENT SUCH AS PUMPS, MOTORS,
 FANS, WIRING AND WIRING DEVICES, CONTROLS, LIGHTS, AND
 OTHER ACCESSORIES.
  
 4.2* DESIGN AND CONSTRUCTION. THE DESIGN AND
 CONSTRUCTION OF COLLECTION SYSTEM FACILITIES SHALL
 CONFORM TO TABLE 4.2, WHICH SUMMARIZES THE VARIOUS
 COMPONENTS ASSOCIATED WITH WASTEWATER COLLECTION AND
 TRANSPORT SYSTEMS.
  
 D.2.4.7 PUMPING STATIONS THAT HANDLE RAW WASTEWATER
 SHOULD BE CLASSIFIED IN THE SAME MANNER AS WASTEWATER
 PUMPING STATIONS (SEE CHAPTER 4). IN-PLANT PUMPING
 STATIONS SHOULD BE CLASSIFIED ON THE BASIS OF THEIR
 LOCATION IN THE PROCESS TRAIN AND THE TYPE OF MATERIAL
 HANDLED. RESTRICTIVE CLASSIFICATIONS ARE GENERALLY NOT
 NECESSARY FOR PUMPING STATIONS THAT HANDLE FULLY
 TREATED WASTEWATER
  
 CHAPTER 7 FIRE AND EXPLOSION PREVENTION AND PROTECTION
  
 7.1* SCOPE. THIS CHAPTER SHALL ESTABLISH MINIMUM
 REQUIREMENTS FOR OVERALL PROTECTION AGAINST FIRE AND
 EXPLOSION HAZARDS IN WASTEWATER FACILITIES AND
 ASSOCIATED COLLECTION SYSTEMS.
 7.1.1 GASES, LIQUIDS, AND SOLIDS SHALL BE ASSIGNED TO
 ONE OF THE FOLLOWING TWO CATEGORIES:
 (1) FLAMMABLE/COMBUSTIBLE HAZARDS
 (2) SAFETY AND HEALTH HAZARDS
 7.1.2 THIS STANDARD SHALL APPLY TO THE FLAMMABILITY
 ASPECTS OF A PARTICULAR SUBSTANCE, PROCESS, OR AREA
 WITHIN WASTEWATER AND COLLECTION FACILITIES.
 7.1.3 NFPA 70E AND NFPA 101? SHALL BE REFERENCED FOR
 ADDITIONAL REQUIREMENTS TO PROTECT AGAINST SAFETY AND
 HEALTH HAZARDS.
 7.2 FIRE PROTECTION MEASURES.
 7.2.1 GENERAL.
 7.2.1.1 COLLECTION SYSTEMS, LIQUID STREAM TREATMENT
 PROCESSES, AND SOLIDS-HANDLING PROCESSES SHALL BE
 PROVIDED WITH FIRE PROTECTION FOR THE FIRE HAZARDS, AS
 DESCRIBED IN TABLE 4.2, TABLE 5.2, TABLE 6.2(A), AND
 TABLE 6.2(B).
 7.2.1.2 ENCLOSED SPACES CLASSIFIED AS EXPLOSION HAZARD
 AREAS UNDER THIS DOCUMENT SHALL BE PHYSICALLY SEPARATED
 FROM ALL UNCLASSIFIED ENCLOSURES.
 7.2.1.3 IN ADDITION TO THE FIRE PROTECTION SPECIFIED IN
 CHAPTER 8, BUILDINGS, STRUCTURES, AND PROCESS ELEMENTS,
 UNDER SOME CONDITIONS, SHALL BE PROVIDED WITH
 AUTOMATIC-EXTINGUISHING SYSTEMS IN ACCORDANCE WITH THIS
 CHAPTER.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-08-27 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-15 Time 15:56 Sent To  
Notes
2018-08-17 15:53:49RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-31 Cont ID  
Sent By jroach Date 2017-08-31 Time 11:54 Rev Time 0.00
Received By jroach Date 2017-08-02 Time 12:39 Sent To  
Notes
2017-08-04 12:39:41C30

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-08-21 Cont ID  
Sent By ccole Date 2017-08-21 Time 13:27 Rev Time 0.00
Received By ccole Date 2017-08-21 Time 13:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-08-21 Cont ID  
Sent By gjohnson Date 2017-08-21 Time 16:14 Rev Time 0.00
Received By gjohnson Date 2017-08-21 Time 16:14 Sent To  
Notes
***NONE***

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2018-03-01 Cont ID  
Sent By rbrown Date 2018-03-01 Time 14:48 Rev Time 0.00
Received By rbrown Date 2018-03-01 Time 14:48 Sent To  
Notes
2018-03-01 14:48:36REVIEWED AND ACCEPTED 2/12/18 LETTER FROM LUIS PEREZ
 REQUESTING A 90 DAY EXTENSION OF THE PERMIT APPLICATION
 BECAUSE THE ORDER OF PRIORITY OF CAPITAL IMPROVEMENT
 PROJECTS WAS CHANGED. EXTENSION GRANTED.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-11-19 Cont ID  
Sent By jroach Date 2018-11-19 Time 13:43 Rev Time 0.00
Received By jroach Date 2018-11-19 Time 11:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-31 Cont ID  
Sent By jroach Date 2017-08-31 Time 11:54 Rev Time 0.00
Received By jroach Date 2017-08-31 Time 11:54 Sent To  
Notes
***NONE***