| 2017-10-04 17:21:55 | W. P. B. REVISION: 17080125 CORRECTED NOTES! |
| | W. P. B. PERMIT: 15111020 NOT: 15050292/ FOUNDATION |
| | PERMIT |
| | ADD: 1100 S. FLAGLER DR. SUITE: UNIT 9B |
| | CONT: SUFFOLK |
| | TEL: 561-407-496-3168 ED HANRATTY |
| | E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS |
| | E-MAIL ADDRESS REQUIREMENTS, |
| | WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN |
| | RECORD. |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | SUBJECT TO FAIR HOUSING! |
| | |
| | 1ST REVIEW |
| | DATE: MON. OCT. 02/2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U04B & |
| | U05B) LEADING INTO THE MASTER BATH HIS & HERS. THE |
| | DOORS AS SHOWN IN THE OPEN POSITION MEASURE 2.50 FT. |
| | FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014 |
| | FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2). |
| | |
| | 1B) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U04B & |
| | U05B) LEADING INTO THE MASTER BATHROOMS HIS & HER |
| | BATHROOMS. PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE |
| | INSTALLED ON THE POCKET DOORS CANNOT BE FULLY RECESSED |
| | HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE |
| | LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205(C)(2)(2).FIGURE 1( C ). |
| | |
| | 1C) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U05W & |
| | U05V) LEADING INTO BOTH HIS AND HER MASTER CLOSETS. THE |
| | DOORS AS SHOWN IN THE OPEN POSITION MEASURE 2.50 FT. |
| | FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014 |
| | FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2). |
| | |
| | 1D) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U05W & |
| | U05V) LEADING INTO BOTH HIS AND HER MASTER CLOSETS. . |
| | PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE INSTALLED |
| | ON THE POCKET DOORS CANNOT BE FULLY RECESSED HARDWARE |
| | HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE LIMITED HAND |
| | MOBILITY. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205(C)(2)(2).FIGURE 1( C ). |
| | |
| | 1E) SHEET 126-18-A2-90-9B PLEASE BE AWARE ALL OF THE |
| | EXTERIOR SLIDING GLASS DOORS WILL NEED TO MEET THE 32 |
| | INCHES CLEAR AND THE HARDWARE HAS TO BE ACCESSIBLE FOR |
| | PEOPLE THAT HAVE LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 2) SHEET 208-18-A6-25-9B FLOOR FINISHES WOOD FLOORS AND |
| | TILE FLOORS. BLDG TYPE: TYPE I/ TYPE II FLOOR |
| | INSULATION (FBC-B 2014) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | 2D) THE PLAN DOES NOT SAY IF THE WOOD FLOORS ARE GOING |
| | TO HAVE AN UNDERLAYMENT ONLY. IF THE FLOORS ARE GOING |
| | TO USE WOOD SLEEPERS AND THEN COMPLIANCE WILL BE |
| | REQUIRED UNDER 2010 FBC-B: |
| | 805.1.1 SUBFLOOR CONSTRUCTION. |
| | FLOOR SLEEPERS, BUCKS AND NAILING BLOCKS SHALL NOT BE |
| | CONSTRUCTED OF COMBUSTIBLE MATERIALS, UNLESS THE SPACE |
| | BETWEEN THE FIRE-RESISTANCE-RATED FLOOR ASSEMBLY AND |
| | THE FLOORING IS EITHER SOLIDLY FILLED WITH |
| | NONCOMBUSTIBLE MATERIALS OR FIREBLOCKED IN ACCORDANCE |
| | WITH SECTION 718, AND PROVIDED THAT SUCH OPEN SPACES |
| | SHALL NOT EXTEND UNDER OR THROUGH PERMANENT PARTITIONS |
| | OR WALLS. |
| | |
| | 805.1.2 WOOD FINISH FLOORING. |
| | WOOD FINISH FLOORING IS PERMITTED TO BE ATTACHED |
| | DIRECTLY TO THE EMBEDDED OR FIREBLOCKED WOOD SLEEPERS |
| | AND SHALL BE PERMITTED WHERE CEMENTED DIRECTLY TO THE |
| | TOP SURFACE OF FIRE-RESISTANCE-RATED FLOOR ASSEMBLIES |
| | OR DIRECTLY TO A WOOD SUBFLOOR ATTACHED TO SLEEPERS AS |
| | PROVIDED FOR IN SECTION 805.1.1. |
| | |
| | 3) THE NARRATIVE LIST SHEETS A0.01C, A2.56A, A6.13A & |
| | A7.55A WITH ADDED REFERENCED NOTES BUT THESE SHEETS ARE |
| | NOT IN THE PERMIT PACKAGE. 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. SUBMIT IF THEY ARE PART OF THIS |
| | REVISION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| 2017-08-29 14:31:49 | W. P. B. REVISION: 17080125 |
| | W. P. B. PERMIT: 15111020 NOT: 15050292/ FOUNDATION |
| | PERMIT |
| | ADD: 1100 S. FLAGLER DR. SUITE: UNIT 9B |
| | CONT: SUFFOLK |
| | TEL: 561-407-496-3168 ED HANRATTY |
| | E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS |
| | E-MAIL ADDRESS REQUIREMENTS, |
| | WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN |
| | RECORD. |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | SUBJECT TO FAIR HOUSING! |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY AUGUST 29/2017 |
| | ACTION: DENIED |
| | |
| | |
| | 1) SHEET 242.17B-A6-68-9A ENLARGED PLAN- DETAIL 1 / |
| | BATHROOM # 2 (SPEC. B) INDICATES REINFORCEMENT FOR |
| | OPTIONAL WALL MOUNTED SEAT AT 24 INCHES A.F.F. PLEASE |
| | PROVIDE IS THE 24 INCHES THE TOP OF BACKING, CENTER |
| | LINE OF BACKING AND WHAT IS THE HEIGHT OF THE BACKING. |
| | THE FAIR HOUSING CODE REQUIRES BACKING FOR TUBS AND |
| | SHOWERS, AND FOR 36 X 36 INCH SHOWERS THE SHOWER STALL |
| | SEAT MUST HAVE REINFORCING TO ALLOW FOR THE |
| | INSTALLATION OF AN OPTIONAL WALL HUNG SEAT. FAIR |
| | HOUSING ALSO USES THE ANSI A117.1 AND FOR SEATS IN |
| | SHOWERS SHALL BE 17 INCHES MINIMUM TO 19 INCHES MAXIMUM |
| | ABOVE THE BATHROOM. THE BACKING HAS TO BE IN HEIGHT |
| | PLACED TO MEET THE HEIGHT REQUIREMENTS FOUND UNDER FAIR |
| | HOUSING AND ANSI A117.1. IF THE DESIGNER WISHES TO HAVE |
| | BACKING AT A HIGHER HEIGHT FOR A FUTURE SEAT THEY WILL |
| | ALSO NEED TO MEET THE REQUIRED BACKING RANGE BY THE |
| | CODE. PLEASE ADD THE ADDITIONAL BACKING REQUIRED AND |
| | CLARIFY WHAT THE 24 INCHES ABOVE FINISH FLOOR IS |
| | RELATIVE TOO. |
| | |
| | 2) THE NARRATIVE FOR THE ARCHITECTURAL PLANS AGAIN |
| | REFERENCES 4 SHEETS NOT FOUND IN THE REVISION SET OF |
| | PLANS, A).01C, A2.56A, A6.13A & A7.55A. W. P. B. |
| | ADMINISTRATIVE CODE 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |