| Plan Review Stops For Permit 17080120 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2018-07-10 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2018-07-10 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2018-07-10 11:07:58 | PROVISO FOR SOUND TRANSMISSION TEST VERIFICATION WAS | | | SUBMITTED/APPROVED UNDER 17110020 (REG) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-10-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-10-20 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-10-20 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-10-20 16:31:16 | W. P. B. REVISION: 17080120 | | | W. P. B. PERMIT: 15111020 | | | ADD: 1100 S. FLAGLER DR. SUITE: UNIT 9A | | | CONT: SUFFOLK | | | TEL: 561-691-4552 # 103 | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | SUBJECT TO FAIR HOUSING! | | | | | | 2ND REVIEW | | | DATE: FRI. OCT. 20/2017 | | | | | | ACTION: BUILDING PROVISO | | | | | | 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR | | | COMPLIANCE WITH THE 2010 FBC-B SECTIONS : | | | FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. | | | FBC-B 2010 1207.2 AIR-BORNE SOUND. | | | FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. | | | THESE TEST WILL BE CONDUCTED ON A 8 INCH CONCRETE SLAB | | | UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS SOON | | | AS RESULTS ARE PRINTED AND REVIEWED BY THE DESIGNER OF | | | RECORD. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-08-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-08-29 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-08-29 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2017-08-29 13:52:47 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. REVISION: 17080120 | | | W. P. B. PERMIT: 15111020 NOT: 15050292/ FOUNDATION | | | PERMIT | | | ADD: 1100 S. FLAGLER DR. SUITE: UNIT 9A | | | CONT: SUFFOLK | | | TEL: 561-407-496-3168 ED HANRATTY | | | E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS | | | E-MAIL ADDRESS REQUIREMENTS, | | | WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN | | | RECORD. | | | | | | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | SUBJECT TO FAIR HOUSING! | | | | | | 1ST REVIEW | | | DATE: TUESDAY AUGUST 29/2017 | | | ACTION: DENIED | | | | | | | | | 1) SHEET 242.17B-A6-68-9A ENLARGED PLAN- DETAIL 1 / | | | BATHROOM # 2 (SPEC. B) INDICATES REINFORCEMENT FOR | | | OPTIONAL WALL MOUNTED SEAT AT 24 INCHES A.F.F. PLEASE | | | PROVIDE IS THE 24 INCHES THE TOP OF BACKING, CENTER | | | LINE OF BACKING AND WHAT IS THE HEIGHT OF THE BACKING. | | | THE FAIR HOUSING CODE REQUIRES BACKING FOR TUBS AND | | | SHOWERS, AND FOR 36 X 36 INCH SHOWERS THE SHOWER STALL | | | SEAT MUST HAVE REINFORCING TO ALLOW FOR THE | | | INSTALLATION OF AN OPTIONAL WALL HUNG SEAT. FAIR | | | HOUSING ALSO USES THE ANSI A117.1 AND FOR SEATS IN | | | SHOWERS SHALL BE 17 INCHES MINIMUM TO 19 INCHES MAXIMUM | | | ABOVE THE BATHROOM. THE BACKING HAS TO BE IN HEIGHT | | | PLACED TO MEET THE HEIGHT REQUIREMENTS FOUND UNDER FAIR | | | HOUSING AND ANSI A117.1. IF THE DESIGNER WISHES TO HAVE | | | BACKING AT A HIGHER HEIGHT FOR A FUTURE SEAT THEY WILL | | | ALSO NEED TO MEET THE REQUIRED BACKING RANGE BY THE | | | CODE. PLEASE ADD THE ADDITIONAL BACKING REQUIRED AND | | | CLARIFY WHAT THE 24 INCHES ABOVE FINISH FLOOR IS | | | RELATIVE TOO. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-08-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-08-29 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-08-29 |
Time |
17:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-08-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-08-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-08-29 |
Time |
10:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-10-26 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-10-26 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-10-06 |
Time |
12:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-09-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-08-23 |
Time |
09:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-10-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-26 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-26 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2017-10-26 12:40:39 | MECHANICAL PROVISO: | | | PRIOR TO ISSUANCE OF CO, THE DESIGN PROFESSIONAL OF | | | RECORD SHALL CERTIFY THE APPLICATION OF THE INTUMESCENT | | | PAINT ON THE AC CLOSET DOORS. | | | CCOLE- 10/26/17 | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-09-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-09-15 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-09-15 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2017-09-15 17:01:38 | 1ST REVIEW FBC-2010 MECHANICAL, WPB AMENDMENTS TO THE | | | FBC. | | | REVISION #17080118 | | | MASTER PERMIT #15111020 | | | THE BRISTOL | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE AC CLOSET DOORS UO5G & UO5K MUST BE | | | NON-COMBUSTIBLE- SECTION 602.2.1. THE DOOR SCHEDULE ON | | | THE MASTER SHEET A8.12 INDICATES WOOD DOORS. | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE | | | COOKING APPLIANCE IN THE KITCHEN AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND | | | SIGNATURE BY THE EOR- SECTION 623.1- 623.5 FBC-10 FUEL | | | GAS. | | | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE | | | EXHAUST VENTILATION HOOD AND EXHAUST DUCT, AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND | | | SIGNATURE BY THE EOR- SECTIONS 505.1 AND 505.2. | | | | | | 4) SHOW THE LOCATIONS OF THE RETURN OPENINGS AT THE | | | PERIMETER COVES AND PROVIDE A DETAIL. PLEASE NOTE THAT | | | ALL AIR SUPPLIED TO A MASTER SUITE MUST BE RETURNED- | | | SECTION 601.5 (3). | | | | | | 5) THE ELIMINATION OF BEDROOM #2 AND THE SUPPLY DUCT TO | | | IT HAS REDUCED THE REQUIRED AIRFLOW FOR HP-F DOWN TO | | | APPROXIMATELY 1250 CFMS, THEREFORE HP-F WHICH IS A 4.0 | | | TON UNIT PRODUCING 1700 CFMS APPEARS TO BE OVERSIZED | | | FOR THE AREA IT IS SEVING. | | | | | | 6) SHEETS M.54A & M54.B THAT ARE LISTED IN THE | | | NARRATIVE WERE NOT UPLOADED FOR REVIEW. | | | | | | 7) PROVIDE SUBDUCT INSTALLATION DETAILS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-10-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-17 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-17 |
Time |
17:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-09-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-09-15 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-15 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2017-09-15 13:52:50 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE REVISION FORM IS LISTING PERMIT #15050292 WHICH | | | IS FOUNDATION ONLY, THE REVISION SHALL BE UNDER PERMIT | | | #15111020 MAIN BUILDING PERMIT PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 2. PLEASE SHOW ELEVATION DETAIL FOR THE BACKING FOR | | | OPTIONAL WALL MOUNTED SHOWER SEAT. PER FHA DESIGN | | | MANUAL PG. 6.13 | | | | | | 3. PLEASE PROVIDE ISOMETRICS DETAIL FOR RECONFIGURED | | | BATHROOMS. WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2017-10-26 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-10-26 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-10-26 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2017-09-15 17:02:14 | MECH DIG/SIG OK- CCOLE- 9/15/17 |
|
|