Plan Review Details - Permit 17080120
Plan Review Stops For Permit 17080120
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-10 Cont ID  
Sent By rgathrig Date 2018-07-10 Time 11:08 Rev Time 0.00
Received By rgathrig Date 2018-07-10 Time 11:07 Sent To  
Notes
2018-07-10 11:07:58PROVISO FOR SOUND TRANSMISSION TEST VERIFICATION WAS
 SUBMITTED/APPROVED UNDER 17110020 (REG)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-20 Cont ID  
Sent By jwitmer Date 2017-10-20 Time 16:31 Rev Time 0.00
Received By jwitmer Date 2017-10-20 Time   Sent To  
Notes
2017-10-20 16:31:16W. P. B. REVISION: 17080120
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 9A
 CONT: SUFFOLK
 TEL: 561-691-4552 # 103
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 2ND REVIEW
 DATE: FRI. OCT. 20/2017
  
 ACTION: BUILDING PROVISO
  
 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS :
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 THESE TEST WILL BE CONDUCTED ON A 8 INCH CONCRETE SLAB
 UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS SOON
 AS RESULTS ARE PRINTED AND REVIEWED BY THE DESIGNER OF
 RECORD.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By jwitmer Date 2017-08-29 Time 13:52 Rev Time 0.00
Received By jwitmer Date 2017-08-29 Time 09:41 Sent To  
Notes
2017-08-29 13:52:472014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080120
 W. P. B. PERMIT: 15111020 NOT: 15050292/ FOUNDATION
 PERMIT
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 9A
 CONT: SUFFOLK
 TEL: 561-407-496-3168 ED HANRATTY
 E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS
 E-MAIL ADDRESS REQUIREMENTS,
 WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN
 RECORD.
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: TUESDAY AUGUST 29/2017
 ACTION: DENIED
  
  
 1) SHEET 242.17B-A6-68-9A ENLARGED PLAN- DETAIL 1 /
 BATHROOM # 2 (SPEC. B) INDICATES REINFORCEMENT FOR
 OPTIONAL WALL MOUNTED SEAT AT 24 INCHES A.F.F. PLEASE
 PROVIDE IS THE 24 INCHES THE TOP OF BACKING, CENTER
 LINE OF BACKING AND WHAT IS THE HEIGHT OF THE BACKING.
 THE FAIR HOUSING CODE REQUIRES BACKING FOR TUBS AND
 SHOWERS, AND FOR 36 X 36 INCH SHOWERS THE SHOWER STALL
 SEAT MUST HAVE REINFORCING TO ALLOW FOR THE
 INSTALLATION OF AN OPTIONAL WALL HUNG SEAT. FAIR
 HOUSING ALSO USES THE ANSI A117.1 AND FOR SEATS IN
 SHOWERS SHALL BE 17 INCHES MINIMUM TO 19 INCHES MAXIMUM
 ABOVE THE BATHROOM. THE BACKING HAS TO BE IN HEIGHT
 PLACED TO MEET THE HEIGHT REQUIREMENTS FOUND UNDER FAIR
 HOUSING AND ANSI A117.1. IF THE DESIGNER WISHES TO HAVE
 BACKING AT A HIGHER HEIGHT FOR A FUTURE SEAT THEY WILL
 ALSO NEED TO MEET THE REQUIRED BACKING RANGE BY THE
 CODE. PLEASE ADD THE ADDITIONAL BACKING REQUIRED AND
 CLARIFY WHAT THE 24 INCHES ABOVE FINISH FLOOR IS
 RELATIVE TOO.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-29 Cont ID  
Sent By jleahy Date 2017-08-29 Time 17:45 Rev Time 0.00
Received By jleahy Date 2017-08-29 Time 17:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-29 Cont ID  
Sent By pleduc Date 2017-08-29 Time   Rev Time 0.00
Received By pleduc Date 2017-08-29 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-26 Cont ID  
Sent By cpuell Date 2017-10-26 Time 13:49 Rev Time 0.00
Received By cpuell Date 2017-10-06 Time 12:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-09-15 Time   Rev Time 0.00
Received By cpuell Date 2017-08-23 Time 09:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-26 Cont ID  
Sent By ccole Date 2017-10-26 Time 12:40 Rev Time 0.00
Received By ccole Date 2017-10-26 Time 12:37 Sent To  
Notes
2017-10-26 12:40:39MECHANICAL PROVISO:
 PRIOR TO ISSUANCE OF CO, THE DESIGN PROFESSIONAL OF
 RECORD SHALL CERTIFY THE APPLICATION OF THE INTUMESCENT
 PAINT ON THE AC CLOSET DOORS.
 CCOLE- 10/26/17
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-18 Cont ID  
Sent By ccole Date 2017-09-15 Time 16:57 Rev Time 0.00
Received By ccole Date 2017-09-15 Time 16:40 Sent To  
Notes
2017-09-15 17:01:381ST REVIEW FBC-2010 MECHANICAL, WPB AMENDMENTS TO THE
 FBC.
 REVISION #17080118
 MASTER PERMIT #15111020
 THE BRISTOL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CLOSET DOORS UO5G & UO5K MUST BE
 NON-COMBUSTIBLE- SECTION 602.2.1. THE DOOR SCHEDULE ON
 THE MASTER SHEET A8.12 INDICATES WOOD DOORS.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 COOKING APPLIANCE IN THE KITCHEN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND
 SIGNATURE BY THE EOR- SECTION 623.1- 623.5 FBC-10 FUEL
 GAS.
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 EXHAUST VENTILATION HOOD AND EXHAUST DUCT, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND
 SIGNATURE BY THE EOR- SECTIONS 505.1 AND 505.2.
  
 4) SHOW THE LOCATIONS OF THE RETURN OPENINGS AT THE
 PERIMETER COVES AND PROVIDE A DETAIL. PLEASE NOTE THAT
 ALL AIR SUPPLIED TO A MASTER SUITE MUST BE RETURNED-
 SECTION 601.5 (3).
  
 5) THE ELIMINATION OF BEDROOM #2 AND THE SUPPLY DUCT TO
 IT HAS REDUCED THE REQUIRED AIRFLOW FOR HP-F DOWN TO
 APPROXIMATELY 1250 CFMS, THEREFORE HP-F WHICH IS A 4.0
 TON UNIT PRODUCING 1700 CFMS APPEARS TO BE OVERSIZED
 FOR THE AREA IT IS SEVING.
  
 6) SHEETS M.54A & M54.B THAT ARE LISTED IN THE
 NARRATIVE WERE NOT UPLOADED FOR REVIEW.
  
 7) PROVIDE SUBDUCT INSTALLATION DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By gjohnson Date 2017-10-17 Time 17:03 Rev Time 0.00
Received By gjohnson Date 2017-10-17 Time 17:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By gjohnson Date 2017-09-15 Time 12:15 Rev Time 0.00
Received By gjohnson Date 2017-09-15 Time 12:15 Sent To  
Notes
2017-09-15 13:52:501ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE REVISION FORM IS LISTING PERMIT #15050292 WHICH
 IS FOUNDATION ONLY, THE REVISION SHALL BE UNDER PERMIT
 #15111020 MAIN BUILDING PERMIT PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PLEASE SHOW ELEVATION DETAIL FOR THE BACKING FOR
 OPTIONAL WALL MOUNTED SHOWER SEAT. PER FHA DESIGN
 MANUAL PG. 6.13
  
 3. PLEASE PROVIDE ISOMETRICS DETAIL FOR RECONFIGURED
 BATHROOMS. WPB AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-10-26 Cont ID  
Sent By cpuell Date 2017-10-26 Time 13:49 Rev Time 0.00
Received By cpuell Date 2017-10-26 Time 13:49 Sent To  
Notes
2017-09-15 17:02:14MECH DIG/SIG OK- CCOLE- 9/15/17


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved