Plan Review Details - Permit 17080108
Plan Review Stops For Permit 17080108
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-10 Cont ID  
Sent By rgathrig Date 2018-07-10 Time 12:24 Rev Time 0.00
Received By rgathrig Date   Time   Sent To  
Notes
2018-07-10 12:24:22PROVISO FOR SOUND TRANSMISSION TEST VERIFICATION WAS
 SUBMITTED/APPROVED UNDER 17110020 (REG)

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-13 Cont ID  
Sent By shill Date 2017-10-13 Time 16:52 Rev Time 0.00
Received By shill Date 2017-10-13 Time 16:52 Sent To  
Notes
2018-07-09 16:47:23SOUND PROVISO SUBMITTED AND REVIEWED FOR COMPLIANCE
 UNDER 17110020 (REG)
2017-10-13 16:56:57PROVISO
  
 FLOORING UNDERLAYMENT TESTS TO BE PROVIDED PRIOR TO
 INSTALLATION
 STC, FBC B 1207.3
 IIC, FBC B 1207.3
 FBC B 603.1, ASTME84 OR UL723
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-10 Cont ID  
Sent By shill Date 2017-10-10 Time 16:07 Rev Time 0.00
Received By shill Date 2017-10-10 Time 11:33 Sent To  
Notes
2017-10-10 16:07:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2010
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 2ND REVIEW
 DATE: 10/10/2017
 ACTION: DENIED
  
 IF ANY OF THESE ISSUES HAVE ALREADY BEEN RESOLVED WITH
 ANOTHER INDIVIDUAL IN THIS DEPARTMENT, PLEASE CONTACT
 ME TO DISCUSS.
  
 PLEASE SEE FBC A FAIR HOUSING ACCESSIBILITY GUIDELINES,
 PURPOSE: "BUILDERS AND DEVELOPERS MAY CHOOSE TO DEPART
 FROM THESE GUIDELINES AND SEEK ALTERNATE WAYS TO
 DEMONSTRATE THAT THEY HAVE MET THE REQUIREMENTS OF THE
 FAIR HOUSING ACT."
  
 2ND SUBMITTAL, THE UNIT DESIGN DOES NOT COMPLY WITH THE
 FHA GUIDELINES AND THE FAIR HOUSING ACT DESIGN MANUAL.
  
 AS IT APPEARS THAT ARCHITECT ELECTS TO DEPART FROM THE
 GUIDELINES, PRIOR TO RESUBMITTING, PLEASE SEND
 RATIONALE FOR EACH ITEM VIA EMAIL FOR CONSIDERATION BY
 THE BUILDING OFFICIAL. IN THIS REVIEW, REFERENCES WILL
 BE MADE TO THE "FAIR HOUSING ACT DESIGN MANUAL". THIS
 IS ONLY FOR THE PURPOSE OF PROVIDING FURTHER
 CLARIFICATION FOR THE RATIONALE BEHIND THE FHA
 GUIDELINES. IF ARCHITECT WISHES TO PROPOSE AN ALTERNATE
 DESIGN, PLEASE PROVIDE ADDITIONAL INFORMATION TO
 DEMONSTRATE HOW THE ALTERNATE DESIGN COMPLIES WITH THE
 REQUIREMENTS OF THE FBC A FHA.
  
 PLEASE FEEL FREE TO CONTACT ME DISCUSS.
  
 COMMENTS FROM PREVIOUS LIST:
  
 1) SHEET 242.07C-A6-69-6C THE DOOR SCHEDULE U05T
 INDICATES A 2 FT. WIDE DOOR ON A LINEN CLOSET LOCATED
 IN THE HALLWAY. THE DEPTH OF THE LINEN CLOSET IS NOT
 GIVEN BUT WHEN THE PLANS ARE CALIBRATED BETWEEN THE
 BACK AND FRONT WALL THE PLANS SCALE 2 FT. 9 INCHES IN
 DEPTH. THE FAIR HOUSING ACT GUIDELINE CLOSET DOORS A
 NOMINAL 32 INCH CLEAR OPENING FOR CLOSETS LESS THAN 24
 INCHES IN DEPTH. ALSO SEE THE 2010 FBC-ACCESSIBILITY
 CODE/ FAIR HOUSING REQUIREMENT 3 SECTION 100.205( C )
 (2) (2).
  
 2ND REVIEW, 2' DEPTH SHOWN FOR THE LINEN CLOSET, 16"
 DOOR. SEE FAIR HOUSING ACT DESIGN MANUAL, SMALL SHALLOW
 STORAGE CLOSET, A MAXIMUM OF 18" RECOMMENDED WITH A
 PARALLEL APPROACH. PARALLEL APPROACH APPEARS TO BE
 BLOCKED SLIGHTLY BY A 4" WALL PROTRUSION.
  
 2) SHEET 126.07-A2-90-6C WITHIN HIS MASTER BATH NEITHER
 THE REVISION 12 LINEN CLOSET NOR THE HALL LINEN CLOSET
 IS DIMENSIONED FOR DEPTH. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 2ND REVIEW, 2' DEPTH SHOWN FOR THE LINEN CLOSET, 16"
 DOOR. SEE FAIR HOUSING ACT DESIGN MANUAL PAGE 3.14,
 SMALL SHALLOW STORAGE CLOSET, A MAXIMUM OF 18"
 RECOMMENDED WITH A PARALLEL APPROACH. TOWEL BAR APPEARS
 TO POSSIBLY OBSTRUCT PARALLEL APPROACH.
  
 3) SHEET 126.07-A2-90-6C WITHIN HIS MASTER BATH THE
 LINEN CLOSET DOOR IS NOT IDENTIFIED, NOR IS IT
 IDENTIFIED IN THE DOOR SCHEDULE AS AN REVISION. THE
 SAME ISSUE WITH THE DEPTH OF THE CLOSET VERSES THE
 WIDTH OF THE DOOR OPENING. 2010 FBC-ACCESSIBILITY CODE/
 FAIR HOUSING REQUIREMENT 3 SECTION
 100.205( C ) (2) (2).
  
 I WAS UNABLE TO LOCATE A DOOR SCHEDULE, PLEASE DIRECT.
  
 4) (NEW COMMENT) INFORMATIONAL ONLY - A NEW NOTE HAS
 BEEN ADDED TO THE PLAN THAT "ALL POCKET DOORS TO HAVE A
 CLEAR OPENING WIDTH OF 32" MINIMUM WHEN FULLY OPEN."
 PLEASE SEE FBC A FHA GUIDELINES REQUIREMENT 3 FIGURE C.
 ALSO SEE FAIR HOUSING ACT DESIGN MANUAL PAGE 3.7. IT IS
 NOT CLEAR HOW A 32" CLEAR POCKET DOOR CAN BE ADAPTED TO
 BE USABLE AS (TYPICAL) USABLE DOOR HARDWARE PREVENTS
 THE DOOR FROM COMPLETELY CLOSING AND WOULD THEREFORE
 NOT HAVE A 32" CLEAR OPENING.
  
 THE TWO NEW POCKET DOORS APPEAR TO BE 36" (COMPLY).
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-26 Cont ID  
Sent By jwitmer Date 2017-08-26 Time 08:58 Rev Time 0.00
Received By jwitmer Date 2017-08-26 Time 07:15 Sent To  
Notes
2017-08-26 08:58:312014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080108
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 6C
 CONT: SUFFOLK
 TEL: 561-407-496-3168 ED HANRATTY
 E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS
 E-MAIL ADDRESS REQUIREMENTS,
 WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN
 RECORD.
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: SATURDAY AUGUST 26/2016
 ACTION: DENIED
  
 1) SHEET 242.07C-A6-69-6C THE DOOR SCHEDULE U05T
 INDICATES A 2 FT. WIDE DOOR ON A LINEN CLOSET LOCATED
 IN THE HALLWAY. THE DEPTH OF THE LINEN CLOSET IS NOT
 GIVEN BUT WHEN THE PLANS ARE CALIBRATED BETWEEN THE
 BACK AND FRONT WALL THE PLANS SCALE 2 FT. 9 INCHES IN
 DEPTH. THE FAIR HOUSING ACT GUIDELINE CLOSET DOORS A
 NOMINAL 32 INCH CLEAR OPENING FOR CLOSETS LESS THAN 24
 INCHES IN DEPTH. ALSO SEE THE 2010 FBC-ACCESSIBILITY
 CODE/ FAIR HOUSING REQUIREMENT 3 SECTION 100.205( C )
 (2) (2).
  
 2) SHEET 126.07-A2-90-6C WITHIN HIS MASTER BATH NEITHER
 THE REVISION 12 LINEN CLOSET NOR THE HALL LINEN CLOSET
 IS DIMENSIONED FOR DEPTH. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 3) SHEET 126.07-A2-90-6C WITHIN HIS MASTER BATH THE
 LINEN CLOSET DOOR IS NOT IDENTIFIED, NOR IS IT
 IDENTIFIED IN THE DOOR SCHEDULE AS AN REVISION. THE
 SAME ISSUE WITH THE DEPTH OF THE CLOSET VERSES THE
 WIDTH OF THE DOOR OPENING. 2010 FBC-ACCESSIBILITY CODE/
 FAIR HOUSING REQUIREMENT 3 SECTION
 100.205( C ) (2) (2).
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-29 Cont ID  
Sent By jleahy Date 2017-08-29 Time 17:41 Rev Time 0.00
Received By jleahy Date 2017-08-29 Time 17:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-29 Cont ID  
Sent By pleduc Date 2017-08-29 Time   Rev Time 0.00
Received By pleduc Date 2017-08-29 Time 10:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-26 Cont ID  
Sent By cpuell Date 2017-10-26 Time 13:44 Rev Time 0.00
Received By cpuell Date 2017-10-06 Time 11:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-09-15 Time   Rev Time 0.00
Received By cpuell Date 2017-08-23 Time 09:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-26 Cont ID  
Sent By ccole Date 2017-10-26 Time 12:29 Rev Time 0.00
Received By ccole Date 2017-10-23 Time 12:11 Sent To  
Notes
2017-10-26 12:30:21MECHANICAL PROVISO:
 PRIOR TO ISSUANCE OF CO, THE DESIGN PROFESSIONAL OF
 RECORD SHALL CERTIFY THE APPLICATION OF THE INTUMESCENT
 PAINT ON THE AC CLOSET DOORS.
 CCOLE- 10/26/17
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By ccole Date 2017-09-15 Time 16:27 Rev Time 0.00
Received By ccole Date 2017-09-15 Time 16:12 Sent To  
Notes
2017-09-15 16:30:231ST REVIEW FBC-2010 MECHANICAL, WPB AMENDMENTS TO THE
 FBC.
 REVISION #17080108
 MASTER PERMIT #15111020
 THE BRISTOL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CLOSET DOORS UO5K, UO5Q, MUST BE
 NON-COMBUSTIBLE- SECTION 602.2.1. THE DOOR SCHEDULE ON
 THE MASTER SHEET A8.12 INDICATES WOOD DOORS.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 COOKING APPLIANCE IN THE KITCHEN, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND
 SIGNATURE BY THE EOR- SECTION 623.1- 623.5 FBC-10 FUEL
 GAS.
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 EXHAUST VENTILATION HOOD AND EXHAUST DUCT, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND
 SIGNATURE BY THE EOR- SECTIONS 505.1 AND 505.2.
  
 4) SHOW THE LOCATIONS OF THE RETURN OPENINGS AT THE
 PERIMETER COVES AND PROVIDE A DETAIL. PLEASE NOTE THAT
 ALL AIR SUPPLIED TO A MASTER SUITE MUST BE RETURNED-
 SECTION 601.5 (3).
  
 5) SHEETS M.54A & M54.B THAT ARE LISTED IN THE
 NARRATIVE WERE NOT UPLOADED FOR REVIEW.
  
 6) PROVIDE SUBDUCT INSTALLATION DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-09-15 Cont ID  
Sent By gjohnson Date 2017-09-15 Time 15:32 Rev Time 0.00
Received By gjohnson Date 2017-09-15 Time 15:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-10-26 Cont ID  
Sent By cpuell Date 2017-10-26 Time 13:44 Rev Time 0.00
Received By cpuell Date 2017-08-26 Time   Sent To  
Notes
2017-09-15 16:19:29MECH DIG/SIGS OK- CCOLE- 9/15/17
2017-09-15 15:33:249/15/17 DIG SIG ON PLUMB SHT OK/GPJ
2017-08-26 09:00:39SAT. 08/26/2017 VERIFIED SIGNATURES ON THE
 ARCHITECTURAL SHEETS. JW