Plan Review Details - Permit 17080055
Plan Review Stops For Permit 17080055
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-09-29 Cont ID  
Sent By shill Date 2017-09-29 Time 14:57 Rev Time 0.00
Received By shill Date 2017-09-28 Time 07:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-30 Cont ID  
Sent By shill Date 2017-08-30 Time 09:01 Rev Time 0.00
Received By shill Date 2017-08-30 Time 08:37 Sent To  
Notes
2017-08-30 09:06:51****PROVISO****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 ISSUED AT APPLICANT'S RISK
  
 REVISION REQUIRED - SEE SHEET LS1. "CODE TABULATION"
 STATES THAT THE BUILDING IS TYPE VB 1 STORY MAX, "EXIST
 BASE BUILDING ANALYSIS" STATES IT IS IIIB 2 STORIES.
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC BUILDING TABLE
 503 (FBC EXISTING BUILDING TABLE 1012.5).
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-04 Cont ID  
Sent By shill Date 2017-08-04 Time 13:09 Rev Time 0.00
Received By shill Date 2017-08-04 Time 13:09 Sent To  
Notes
2017-08-04 13:09:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY (FROM
 BUSINESS TO MERCANTILE); REVISE PLAN TO INCLUDE THIS
 INFORMATION. SEE FBC EB CHAPTER 10 AND REVISE PLAN TO
 SHOW COMPLIANCE WITH ALL REQUIREMENTS. IF THIS SPACE
 WAS BUSINESS, MERCANTILE IS A HIGHER HAZARD.
  
 2. CONFERENCE ROOMS SHOULD HAVE AN OCCUPANT LOAD
 UTILIZING 15 SF PER PERSON, FBC B 1004, REVISE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-11 Cont ID  
Sent By jpearson Date 2017-09-11 Time 15:43 Rev Time 0.00
Received By jpearson Date 2017-09-11 Time 15:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By jpearson Date 2017-08-09 Time 07:35 Rev Time 0.00
Received By jpearson Date 2017-08-09 Time 07:35 Sent To  
Notes
2017-08-09 07:34:59CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE. FBC C405.5
 2. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. SOME AREAS DO NOT SHOW EITHER A
 TIMER CONTROLLOED CIRCUIT OR OCCUPANCY SENSORS
 REQUIRED. FBC C405.2.2, 405.2.2.2
 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC C405.7.1
 4. WILL THERE BE ANY SHOW WINDOWS IN THIS BUSINESS?
 PROVIDE SHOW WINDOW LIGHTING OUTLETS IF NECESSARY. NEC
 210.62
 5. PROVIDE AUTOMATIC CONTROL FOR SIGN LIGHTING.
 "LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS'. FBC
 C405.2.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-30 Cont ID  
Sent By scaldero Date 2017-08-30 Time 14:43 Rev Time 0.00
Received By scaldero Date 2017-08-30 Time 14:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-07 Cont ID  
Sent By scaldero Date 2017-08-07 Time 14:27 Rev Time 0.00
Received By scaldero Date 2017-08-07 Time 14:10 Sent To  
Notes
2017-08-07 14:27:02PERMIT # 17080055
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) INCLUDE A CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
 2) REVIEW AND RESPOND TO BUILDING DEPT. COMMENT
 REGARDING CHANGE OF USE FROM BUSINESS TO MERCANTILE. A
 CHANGE OF USE PERMIT MAY ALSO BE REQUIRED.
 3) THE PLANS INDICATE A MIXED-USE OCCUPANCY AND AS SUCH
 THE CODES REGARDING THE MOST STRINGEST USE (MERCANTILE)
 SHALL APPLY. PLEASE VERIFY AND CONFIRM THAT
 THAT THE PLANS SUBMITTED COMPLY WITH THE REQUIREMENTS
 FOR NEW MERCANTILE OF THE FLORIDA FIRE PREVENTION CODE,
 5TH EDITION.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-09-29 Cont ID  
Sent By shill Date 2017-09-29 Time 14:57 Rev Time 0.00
Received By shill Date 2017-09-25 Time 16:41 Sent To  
Notes
2017-09-26 16:42:01RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-18 Cont ID  
Sent By cpuell Date 2017-09-18 Time 13:43 Rev Time 0.00
Received By cpuell Date 2017-08-25 Time 12:48 Sent To  
Notes
2017-08-28 12:48:30B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-21 Cont ID  
Sent By gjohnson Date 2017-08-21 Time 10:45 Rev Time 0.00
Received By gjohnson Date 2017-08-01 Time 15:16 Sent To  
Notes
2017-08-02 15:16:13B22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-10-03 Cont ID  
Sent By shill Date 2017-10-03 Time 12:10 Rev Time 0.00
Received By shill Date 2017-10-03 Time 12:10 Sent To  
Notes
2017-10-03 12:10:56$0 FEE DUE
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-08-11 Cont ID  
Sent By shill Date 2017-08-11 Time 08:12 Rev Time 0.00
Received By shill Date 2017-08-11 Time 08:12 Sent To  
Notes
2017-08-11 08:13:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 AFTER ALL REVIEWS HAVE PASSED, AN IMPACT FEE ASSESSMENT
 IS REQUIRED. 561-233-5025 FOR MORE INFORMATION
  
 THE PLANS WILL BE REQUIRED TO BE STAMPED AND THE
 RECEIPT SHOWING FEES DUE, IF APPLICABLE, WILL BE
 REQUIRED
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-09-13 Cont ID  
Sent By ccole Date 2017-09-13 Time 15:22 Rev Time 0.00
Received By ccole Date 2017-09-13 Time 15:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-15 Cont ID  
Sent By ccole Date 2017-08-15 Time 07:32 Rev Time 0.00
Received By ccole Date 2017-08-15 Time 07:20 Sent To  
Notes
2017-08-15 07:46:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080055
 8/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: THE CITY OF WEST PALM BEACH BUILIDNG DIVISION
 REQUIRES A DUCT SMOKE DETECTOR IN THE RETURN AIR SYSTEM
 OF THE 5-TON SYSTEM UNLESS MANUFACTURER'S
 SPECIFICATIONS INDICATE THE SYSTEM CANNOT PRODUCE
 SUPPLY AIR IN EXCESS OF 2000 CFMS- SECTION 606.2.1.
  
 2) M-1: LABEL THE O/A DUCT.
  
 3) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA USED IN
 DESIGNING THE ACCU TIE-DOWN DETAIL- SECTION 301.15.
  
 4) THE BUILDING PLANS EXAMINER IS INDICATING THAT THE
 PROPOSED PROJECT IS A CHANGE OF OCCUPANCY. PLEASE SEE
 SECTION C101.4.4 FBC-14 ENERGY CONSERVATION. PLEASE
 NOTE THAT SUBMUITTED ENERGY FORM C402-2014 CAN NOT BE
 USED FOR A CHANGE OFPOCCUPANCY COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-09-27 Cont ID  
Sent By thunt Date 2017-09-27 Time 15:18 Rev Time 0.00
Received By thunt Date 2017-09-27 Time 15:18 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-09-18 Cont ID  
Sent By thunt Date 2017-09-18 Time 13:32 Rev Time 0.00
Received By thunt Date 2017-09-15 Time 15:14 Sent To  
Notes
2017-09-18 13:33:339/18/2017 2ND REVIEW DENIED
 EXISTING
 COMMENT #1 FROM 1ST REVIEW: SHOW CLEAR FLOOR SPACE FOR
 TOILET
 SECTION 604 APPLIES TO ALL TOILET WHILE 603 APPLIES TO
 THE ROOM ITSELF. ALSO 213.3.2 STATES THAT WHERE WATER
 CLOSETS ARE PROVIDED AT LEAST ONE SHALL COMPLY WITH
 604.
  
 NEW COMMENT:
 PAGE A-4 TOILET ACCESSORY LEGEND D SHOULD READ: ADA
 ACCESSIBLE WATER CLOSET WITH SEAT HEIGHT BETWEEN
 17?-19?
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-21 Cont ID  
Sent By gjohnson Date 2017-08-21 Time 09:50 Rev Time 0.00
Received By gjohnson Date 2017-08-21 Time 09:50 Sent To  
Notes
2017-08-21 10:45:051ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW CLEAR FLOOR SPACE TO COMPLY WITH FBC ACC
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 2. KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 CLEAR
 FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3. A BACKFLOW IS REQUIRED ON REFRIGERATOR ICE MACHINE.
 PER FBC PL 608.3
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  