| Plan Review Stops For Permit 17080055 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-09-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-29 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-28 |
Time |
07:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-08-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-30 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-30 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2017-08-30 09:06:51 | ****PROVISO**** | | | ****REVISION REQUIRED**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | ISSUED AT APPLICANT'S RISK | | | | | | REVISION REQUIRED - SEE SHEET LS1. "CODE TABULATION" | | | STATES THAT THE BUILDING IS TYPE VB 1 STORY MAX, "EXIST | | | BASE BUILDING ANALYSIS" STATES IT IS IIIB 2 STORIES. | | | REVISE PLAN TO SHOW COMPLIANCE WITH FBC BUILDING TABLE | | | 503 (FBC EXISTING BUILDING TABLE 1012.5). | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-08-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-04 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-04 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2017-08-04 13:09:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY (FROM | | | BUSINESS TO MERCANTILE); REVISE PLAN TO INCLUDE THIS | | | INFORMATION. SEE FBC EB CHAPTER 10 AND REVISE PLAN TO | | | SHOW COMPLIANCE WITH ALL REQUIREMENTS. IF THIS SPACE | | | WAS BUSINESS, MERCANTILE IS A HIGHER HAZARD. | | | | | | 2. CONFERENCE ROOMS SHOULD HAVE AN OCCUPANT LOAD | | | UTILIZING 15 SF PER PERSON, FBC B 1004, REVISE. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-09-11 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-09-11 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-09-11 |
Time |
15:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-08-09 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-08-09 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2017-08-09 07:34:59 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING | | | COMPLIANCE WITH THE FBC ENERGY CODE. FBC C405.5 | | | 2. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED | | | IN THE FBC ENERGY CODE. SOME AREAS DO NOT SHOW EITHER A | | | TIMER CONTROLLOED CIRCUIT OR OCCUPANCY SENSORS | | | REQUIRED. FBC C405.2.2, 405.2.2.2 | | | 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. FBC C405.7.1 | | | 4. WILL THERE BE ANY SHOW WINDOWS IN THIS BUSINESS? | | | PROVIDE SHOW WINDOW LIGHTING OUTLETS IF NECESSARY. NEC | | | 210.62 | | | 5. PROVIDE AUTOMATIC CONTROL FOR SIGN LIGHTING. | | | "LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS'. FBC | | | C405.2.4 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-08-30 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2017-08-30 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2017-08-30 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-08-07 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2017-08-07 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2017-08-07 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2017-08-07 14:27:02 | PERMIT # 17080055 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) INCLUDE A CODE LIST TO REFERENCE THE 5TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | 2) REVIEW AND RESPOND TO BUILDING DEPT. COMMENT | | | REGARDING CHANGE OF USE FROM BUSINESS TO MERCANTILE. A | | | CHANGE OF USE PERMIT MAY ALSO BE REQUIRED. | | | 3) THE PLANS INDICATE A MIXED-USE OCCUPANCY AND AS SUCH | | | THE CODES REGARDING THE MOST STRINGEST USE (MERCANTILE) | | | SHALL APPLY. PLEASE VERIFY AND CONFIRM THAT | | | THAT THE PLANS SUBMITTED COMPLY WITH THE REQUIREMENTS | | | FOR NEW MERCANTILE OF THE FLORIDA FIRE PREVENTION CODE, | | | 5TH EDITION. | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-09-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-29 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-25 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2017-09-26 16:42:01 | RESUB ROUTED TO THUNT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-09-18 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-09-18 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-08-25 |
Time |
12:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-08-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-08-21 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-08-01 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-10-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-03 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-03 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2017-10-03 12:10:56 | $0 FEE DUE | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-08-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-11 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-11 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2017-08-11 08:13:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | AFTER ALL REVIEWS HAVE PASSED, AN IMPACT FEE ASSESSMENT | | | IS REQUIRED. 561-233-5025 FOR MORE INFORMATION | | | | | | THE PLANS WILL BE REQUIRED TO BE STAMPED AND THE | | | RECEIPT SHOWING FEES DUE, IF APPLICABLE, WILL BE | | | REQUIRED | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-09-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-09-13 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-09-13 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-08-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-08-15 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-08-15 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2017-08-15 07:46:16 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080055 | | | 8/15/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M-1: THE CITY OF WEST PALM BEACH BUILIDNG DIVISION | | | REQUIRES A DUCT SMOKE DETECTOR IN THE RETURN AIR SYSTEM | | | OF THE 5-TON SYSTEM UNLESS MANUFACTURER'S | | | SPECIFICATIONS INDICATE THE SYSTEM CANNOT PRODUCE | | | SUPPLY AIR IN EXCESS OF 2000 CFMS- SECTION 606.2.1. | | | | | | 2) M-1: LABEL THE O/A DUCT. | | | | | | 3) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA USED IN | | | DESIGNING THE ACCU TIE-DOWN DETAIL- SECTION 301.15. | | | | | | 4) THE BUILDING PLANS EXAMINER IS INDICATING THAT THE | | | PROPOSED PROJECT IS A CHANGE OF OCCUPANCY. PLEASE SEE | | | SECTION C101.4.4 FBC-14 ENERGY CONSERVATION. PLEASE | | | NOTE THAT SUBMUITTED ENERGY FORM C402-2014 CAN NOT BE | | | USED FOR A CHANGE OFPOCCUPANCY COMPLIANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-09-27 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2017-09-27 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2017-09-27 |
Time |
15:18 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-09-18 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2017-09-18 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2017-09-15 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2017-09-18 13:33:33 | 9/18/2017 2ND REVIEW DENIED | | | EXISTING | | | COMMENT #1 FROM 1ST REVIEW: SHOW CLEAR FLOOR SPACE FOR | | | TOILET | | | SECTION 604 APPLIES TO ALL TOILET WHILE 603 APPLIES TO | | | THE ROOM ITSELF. ALSO 213.3.2 STATES THAT WHERE WATER | | | CLOSETS ARE PROVIDED AT LEAST ONE SHALL COMPLY WITH | | | 604. | | | | | | NEW COMMENT: | | | PAGE A-4 TOILET ACCESSORY LEGEND D SHOULD READ: ADA | | | ACCESSIBLE WATER CLOSET WITH SEAT HEIGHT BETWEEN | | | 17?-19? | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-08-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-08-21 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-08-21 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2017-08-21 10:45:05 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE SHOW CLEAR FLOOR SPACE TO COMPLY WITH FBC ACC | | | 604.3.1 SIZE. | | | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED | | | PERPENDICULAR FROM THE REAR WALL. | | | | | | 2. KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 CLEAR | | | FLOOR SPACE. | | | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR | | | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | 606.3 HEIGHT. | | | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT | | | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES | | | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 3. A BACKFLOW IS REQUIRED ON REFRIGERATOR ICE MACHINE. | | | PER FBC PL 608.3 | | | | | | 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|