Plan Review Details - Permit 17080045
Plan Review Stops For Permit 17080045
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By shill Date 2017-10-17 Time 17:54 Rev Time 0.00
Received By shill Date 2017-10-17 Time 17:54 Sent To  
Notes
2017-10-17 17:55:00***PROVISOS***
  
 1. THRESHOLD BUILDING - THREE SETS OF PLANS REQUIRED.
 AFTER ISSUANCE, HAVE A FULL SIZE COPY OF THE PLANS MADE
 FOR THE SPECIAL INSPECTOR.
  
 2. 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 3. W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT OR ENGINEER IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC.
  
 4. COORDINATE WITH BUILDING INSPECTOR: WITH THE
 EXTERIOR STAIRS, RAMP (WEST SIDE OF THE BUILDING) AND
 THE ENTRY DOORS ON BOTH THE WEST AND EAST SIDES BEING
 REPLACED, PLEASE PROVIDE AN EGRESS PLAN OF HOW EGRESS
 WILL BE MAINTAINED DURING CONSTRUCTION.
  
 2014 FBC-B 3310.2 MAINTENANCE OF MEANS OF EGRESS.
 REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR
 ALTERATIONS TO ANY BUILDING.
 EXCEPTION: EXISTING MEANS OF EGRESS NEED NOT BE
 MAINTAINED WHERE APPROVED TEMPORARY MEANS OF EGRESS
 SYSTEMS AND FACILITIES ARE PROVIDED.
  
 5. SEPARATE PERMITS REQUIRED FOR IRRIGATION, FIRE
 ALARM, FIRE SPRINKLER, LOW VOLTAGE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-24 Cont ID  
Sent By jwitmer Date 2017-08-24 Time 08:17 Rev Time  
Received By jwitmer Date 2017-08-23 Time 16:56 Sent To  
Notes
2017-08-24 08:17:112014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080045
 ADD: 515 N. FLAGLER DR.
 CONT: GLENEWINKEL CONSTRUCTION CO.
 TEL: 561-251-2459
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 23/ 2014
 ACTION: DENIED
  
 1)THRESHOLD BUILDING. THIS BUILDINGS STRUCTURAL
 ALTERATIONS BEING A HIGHRISE BUILDING MEETS THE
 QUALIFICATIONS FOR A SPECIAL INSPECTOR. FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2) SHEET A-021AT GRID LINE B1-B2/ 5.1-6.5 ALSO HAS A
 NOTE NUMBER D-4 REFERS TO THE REMOVAL OF STAIRS, REFERS
 AGAIN TO THE STRUCTURAL NARRATIVE FOR THE EXTENT OF
 REMOVAL. SHEET A-201 THE SAME PLAZA LEVEL MAKES NO
 REFERENCE TO A FLOOR INFILL. SHEET S-202 SHOWS A DETAIL
 AT THE REMOVED STAIR 09/ S-401. NO SUCH DETAIL ON SHEET
 S-401. WERE THE STAIRS THAT WERE REMOVED JUST
 CONVENIENCE STAIRS IT APPEARS THAT THERE WAS NO SHAFT?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3A) SHEET A-021 THE PLAZA DEMO HAS NOTE # 5 TO REMOVE
 THE EXISTING VESTIBULE, AND ENTRANCE DOORS AND
 SIDELIGHTS. SHEET A-201 SHOWS THE ENTRY DOORS IN A NEW
 LOCATION. SHEET A-600 HAS THE DOOR SCHEDULE AND THESE
 DOORS LISTED AS DOORS L002 A & B. THERE IS NO REFERENCE
 IF THESE DOORS ARE NEW ARE OR TRYING TO BE REUSED. SEE
 THE W. P. B. ADMINISTRATIVE CODE REFERENCE TO USED
 MATERIALS.
  
 104.9.1 USED MATERIALS AND EQUIPMENT. THE USE OF USED
 RECYCLED OR RECLAIMED MATERIALS WHICH MEET THE
 REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS
 PERMITTED. USED EQUIPMENT AND DEVICES SHALL NOT BE
 REUSED UNLESS APPROVED BY THE BUILDING OFFICIAL.
  
 NEW EXTERIOR DOORS WILL NEED TO COMPLY WITH COMPONENTS
 & CLADDING. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS
  
 3B) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) SHEET A-201 INDICATES DETAIL G.1/ A-411 THIS DETAIL
 REFERS TO DETAIL A,15 OF THE SAME SHEET A-411. THIS
 DETAIL IS OF THE NEW VESTIBULE WALL PLAN.
  
 4A) WITHIN THIS DETAIL THE WALL PANELS SHOW THE USE OF
 STEEL STUDS, THE TYPE OF STEEL STUD, STRUCTURAL OR
 ARCHITECTURAL, GAUGE OF STUD, SPACING IS NOT PROVIDED.
 2014 FBC-B 2211.1 AND OR 2211.4 WALL STUD DESIGN.
  
 4B) SHEET A-411 DETAIL A,15 INDICATES THE USE AND
 INSTALLATION OF MCM PANELS (METAL COMPOSITE MATERIALS)
 PLEASE PROVIDE THE MANUFACTURERS REPORT PROVING
 COMPLIANCE WITH SECTIONS 1407.1- 1407.9.
  
 4C) NEW MCM PANELS WILL NEED TO COMPLY WITH COMPONENTS
 & CLADDING. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31) (C) PANEL WALLS: MCM PANELS AND PRODUCTS
 INTRODUCED AS A RESULT OF NEW TECHNOLOGY.
  
 5) WITH THE EXTERIOR STAIRS, RAMP (WEST SIDE OF THE
 BUILDING) AND THE ENTRY DOORS ON BOTH THE WEST AND EAST
 SIDES BEING REPLACED, PLEASE PROVIDE AN EGRESS PLAN OF
 HOW EGRESS WILL BE MAINTAINED DURING CONSTRUCTION.
  
 2014 FBC-B 3310.2 MAINTENANCE OF MEANS OF EGRESS.
 REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR
 ALTERATIONS TO ANY BUILDING.
 EXCEPTION: EXISTING MEANS OF EGRESS NEED NOT BE
 MAINTAINED WHERE APPROVED TEMPORARY MEANS OF EGRESS
 SYSTEMS AND FACILITIES ARE PROVIDED.
  
 6) PLEASE REVIEW SHEET A-201 SEE STAIR SHAFT IN GRID
 LINES B3-B4 & 5.1-6. IN THE PAST THERE WAS CREATED A
 NONCONFORMITY IN THE STAIRWELL (SHAFT). IT APPEARS
 THERE WAS A DOOR REMOVED FROM THE PARKING LEVEL THAT
 LET DIRECT ACCESS INTO THE ATRIUM AREA. THE PLANS HAVE
 THIS BLOCKED OFF BUT THE PLANS DO NOT RATE THE WALL AS
 A 2 HOUR WALL. THE HIGHRISE STAIR ENCLOSURE IS A 2 HOUR
 FIRE RATED SHAFT. THIS PORTION OF THE WALL IS A INFILL,
 PLEASE REQUIRE A 2 HOUR FIRE RATED WALL IN THIS INFILL.
 2014 FBC-B 713.4.
  
 7) SHEET A-301 SHOWS NEW EXTERIOR GLASS GUARDRAIL
 SYSTEMS WITH LAMINATED STRUCTURAL GLASS WITH # 4
 STAINLESS CAP. PLEASE PROVIDE SHOP DRAWING TO BE
 REVIEWED BY THE DESIGNER OF RECORD BEFORE BEING
 SUBMITTED TO THE BUILDING DEPARTMENT. SHOW COMPLIANCE
 WITH 2014 FBC-B 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED
 TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.8. A
 SAFETY FACTOR OF (4) FOUR SHALL BE USED.
  
 8) SHEET A540 DETAIL A,1 THE SOUTH ELEVATION. THIS
 ELEVATION SHOWS AN ALTERNATE GLAZING DETAIL FOR ? INCH
 CLEAR TEMPERED BUTT JOINT GLAZING. TWO ISSUES:
 8A) IS THIS GLAZING TO THE EXTERIOR? IF SO DOES THE
 BUTT JOINT TEMPERED GLAZING HAVE PRODUCT APPROVAL FOR
 LARGE MISSILE IMPACT TESTING? COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 8B) THE PLANS INDICATE THE BUTT JOINT GLAZING AS AN
 ALTERNATIVE, 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3: SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION."
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By jpearson Date 2017-10-17 Time 08:17 Rev Time 0.00
Received By jpearson Date 2017-10-17 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-31 Cont ID  
Sent By jpearson Date 2017-08-31 Time 14:15 Rev Time 0.00
Received By jpearson Date 2017-08-31 Time 14:15 Sent To  
Notes
2017-08-31 14:15:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE A BLOCK NOTE WHERE APPLICABLE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR LOW VOLTAGE SYSTEMS, FIRE ALARM, CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, WALK-IN COOLERS,
 HOODS, ETC. FBC 105.1
 2. PANELS HPCH, HPCL, HPCL1 SHOW A DEMAND FACTOR OF
 84.99% FOR RECEPTACLES. PROVIDE CODE SECTION THAT
 PERMITS THIS OR PROVIDE CORRECTION. FBC 107.2.1, NEC
 220
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-02 Cont ID  
Sent By pleduc Date 2017-10-02 Time   Rev Time 0.00
Received By pleduc Date 2017-10-02 Time 13:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-15 Cont ID  
Sent By pleduc Date 2017-08-15 Time   Rev Time 0.00
Received By pleduc Date 2017-08-14 Time 14:12 Sent To  
Notes
2017-08-15 10:46:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 022 - THUIS SHEET INDICATES THE REMOVAL OF
 TWO SETS OF DOUBLE DOOR AT EACH END OF THE BRIDGE.
 SHEET A 202, INDICATES THE REINSTALLATION OF ONLY ONE
 SET.
  
 THE CONCERN LIES WITH WHAT WAS THE ORIGINAL LIFE SAFETY
 INTENT OF THESE DOORS AND WOULD REMOVING ONE SET
 COMPROMISE THE LIFE SAFETY FEATURES ORIGNALLY DESIGNED.
  
 PLEASE REVIEW THE EOR AND ENSURE THAT THESE DOORS DO
 NOT NEGATIVELY AFFECT THE LIFE SAFETY FEATURES OF THE
 BUILDING.
  
 PER NFPA 101
  
 8.6.7* ATRIUMS. UNLESS PROHIBITED BY CHAPTERS 11
 THROUGH 43, AN ATRIUM SHALL BE PERMITTED, PROVIDED THAT
 THE FOLLOWING CONDITIONS ARE MET:
 (1) THE ATRIUM IS SEPARATED FROM THE ADJACENT SPACES BY
 FIRE BARRIERS WITH NOT LESS THAN A 1-HOUR FIRE
 RESISTANCE RATING, WITH OPENING PROTECTIVES FOR
 CORRIDOR WALLS, UNLESS ONE OF THE FOLLOWING IS MET:
 (A) THE REQUIREMENT OF 8.6.7(1) SHALL NOT APPLY TO
 EXISTING, PREVIOUSLY APPROVED ATRIUMS.
 (B) ANY NUMBER OF LEVELS OF THE BUILDING SHALL BE
 PERMITTED TO OPEN DIRECTLY TO THE ATRIUM WITHOUT
 ENCLOSURE, BASED ON THE RESULTS OF THE ENGINEERING
 ANALYSIS REQUIRED IN 8.6.7(5).
 (C)* GLASS WALLS AND INOPERABLE WINDOWS SHALL BE
 PERMITTED IN LIEU OF THE FIRE BARRIERS WHERE ALL THE
 FOLLOWING ARE MET:
 I. AUTOMATIC SPRINKLERS ARE SPACED ALONG BOTH SIDES OF
 THE GLASS WALL AND THE INOPERABLE WINDOWS AT INTERVALS
 NOT TO EXCEED 6 FT (1830 MM).
 II. THE AUTOMATIC SPRINKLERS SPECIFIED IN
 8.6.7(1)(C)(I) ARE LOCATED AT A DISTANCE FROM THE GLASS
 WALL NOT TO EXCEED 12 IN. (305 MM) AND ARRANGED SO THAT
 THE ENTIRE SURFACE OF THE GLASS IS WET UPON OPERATION
 OF THE SPRINKLERS.
 III. THE GLASS WALL IS OF TEMPERED, WIRED, OR LAMINATED
 GLASS HELD IN PLACE BY A GASKET SYSTEM THAT ALLOWS THE
 GLASS FRAMING SYSTEM TO DEFLECT WITHOUT BREAKING
 (LOADING) THE GLASS BEFORE THE SPRINKLERS OPERATE.
 IV. THE AUTOMATIC SPRINKLERS REQUIRED BY 8.6.7(1)(C)(I)
 ARE NOT REQUIRED ON THE ATRIUM SIDE OF THE GLASS WALL
 AND THE INOPERABLE WINDOW WHERE THERE IS NO WALKWAY OR
 OTHER FLOOR AREA ON THE ATRIUM SIDE ABOVE THE MAIN
 FLOOR LEVEL.
 V. DOORS IN THE GLASS WALLS ARE OF GLASS OR OTHER
 MATERIAL THAT RESISTS THE PASSAGE OF SMOKE.
 VI. DOORS IN THE GLASS WALLS ARE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON DETECTION OF SMOKE.
 VII. THE GLASS IS CONTINUOUS VERTICALLY, WITHOUT
 HORIZONTAL MULLIONS, WINDOW TREATMENTS, OR OTHER
 OBSTRUCTIONS THAT WOULD INTERFERE WITH THE WETTING OF
 THE ENTIRE GLASS SURFACE.
 (2) ACCESS TO EXITS IS PERMITTED TO BE WITHIN THE
 ATRIUM, AND EXIT DISCHARGE IN ACCORDANCE WITH 7.7.2 IS
 PERMITTED TO BE WITHIN THE ATRIUM.
 (3) THE OCCUPANCY WITHIN THE ATRIUM MEETS THE
 SPECIFICATIONS FOR CLASSIFICATION AS LOW OR ORDINARY
 HAZARD CONTENTS. (SEE 6.2.2.)
 (4) THE ENTIRE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7.
 (5)* FOR OTHER THAN EXISTING, PREVIOUSLY APPROVED
 ATRIUMS, AN ENGINEERING ANALYSIS IS PERFORMED THAT
 DEMONSTRATES THAT THE BUILDING IS DESIGNED TO KEEP THE
 SMOKE LAYER INTERFACE ABOVE THE HIGHEST UNPROTECTED
 OPENING TO ADJOINING SPACES, OR 6 FT (1830 MM) ABOVE
 THE HIGHEST FLOOR LEVEL OF EXIT ACCESS OPEN TO THE
 ATRIUM, FOR A PERIOD EQUAL TO 1.5 TIMES THE CALCULATED
 EGRESS TIME OR 20 MINUTES, WHICHEVER IS GREATER.
 (6)* IN OTHER THAN EXISTING, PREVIOUSLY APPROVED
 ATRIUMS, WHERE AN ENGINEERED SMOKE CONTROL SYSTEM IS
 INSTALLED TO MEET THE REQUIREMENTS OF 8.6.7(5), THE
 SYSTEM IS INDEPENDENTLY ACTIVATED BY EACH OF THE
 FOLLOWING:
 (A) REQUIRED AUTOMATIC SPRINKLER SYSTEM
 (B) MANUAL CONTROLS THAT ARE READILY ACCESSIBLE TO THE
 FIRE DEPARTMENT
  
 PROVIDE APPLICABLE DETAILS/PLAN SHEETS/EOR DOCUMENTS,
 ETC
  
  
  
 2) SHEET A 500 - THE DOOR SCHEDULE INDICATES NO RATING
 FOR DOOR B002.
  
 PLEASE REVIEW WITH # 1 ABOVE TO ENSURE THAT THIS DOOR
 IS NOT REQUIRED TO CARRY ANY RATING.
  
 PROVIDE APPLICABLE DETAILS/PLAN SHEETS/EOR DOCUMENTS,
 ETC
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-18 Cont ID  
Sent By cpuell Date 2017-10-18 Time 12:53 Rev Time 0.00
Received By cpuell Date 2017-09-26 Time 16:07 Sent To  
Notes
2017-09-27 16:17:05C37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-09-05 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-01 Time 13:36 Sent To  
Notes
2017-08-02 13:36:23C33

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-08-18 Cont ID  
Sent By jwitmer Date 2017-08-18 Time   Rev Time  
Received By jwitmer Date 2017-08-18 Time 16:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-16 Cont ID  
Sent By ccole Date 2017-10-16 Time 16:33 Rev Time 0.00
Received By ccole Date 2017-10-16 Time 15:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-05 Cont ID  
Sent By ccole Date 2017-09-05 Time 17:27 Rev Time 0.00
Received By ccole Date 2017-09-05 Time 16:44 Sent To  
Notes
2017-09-05 17:40:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080045
 9/5/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE KEY NOTES TO CLARIFY THE SCOPE OF WORK FOR
 THE FSD'S WHERE SHOWN IN THE CORRIDORS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-12 Cont ID  
Sent By gjohnson Date 2017-10-12 Time 14:26 Rev Time 0.00
Received By gjohnson Date 2017-10-12 Time 14:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By gjohnson Date 2017-08-29 Time 11:46 Sent To M
Notes
2017-08-29 11:47:251ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-510 THE VERTICAL GRAB BARS ARE NOT APPROVED
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION.
 PER FBC ACC 609.4
  
 2. GRAB BARS SHALL COMPLY WITH FBC ACC 609.4 POSITION
 OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, EXCEPT THAT AT WATER CLOSETS FOR CHILDREN?S
 USE COMPLYING WITH 604.9, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION 18 INCHES MINIMUM AND 27
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP OF THE GRIPPING SURFACE. THE HEIGHT OF THE LOWER
 GRAB BAR ON THE BACK WALL OF A BATHTUB SHALL COMPLY
 WITH 607.4.1.1 OR 607.4.2.1.
  
 3. SIDE GRAB BAR SHALL COMPLY WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 4. PLEASE PROVIDE SIZING CALCULATIONS FOR GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 5. BACKFLOWS ARE REQUIRED ON THE COFFEE MACHINE AND ICE
 MACHINE. PER FBC PL 608.3 , 608.16.10
  
 6. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR SUMP
 PUMP, PIT AND TANKLESS WATER HEATERS AND GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2017-10-27 Cont ID  
Sent By shill Date 2017-10-27 Time 15:04 Rev Time 0.00
Received By shill Date 2017-10-27 Time 15:04 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-10-17 Cont ID  
Sent By shill Date 2017-10-17 Time 17:55 Rev Time 0.00
Received By shill Date 2017-10-17 Time 17:55 Sent To  
Notes
2017-10-17 17:55:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1)THRESHOLD BUILDING. THIS BUILDINGS STRUCTURAL
 ALTERATIONS BEING A HIGHRISE BUILDING MEETS THE
 QUALIFICATIONS FOR A SPECIAL INSPECTOR. FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2ND REVIEW, THE THRESHOLD INSPECTION PLAN WAS PROVIDED
 BUT IS NOT SIGNED AND SEALED, ALSO LACKS A TITLE BLOCK.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 1C) OK
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-10-18 Cont ID  
Sent By   Date 2017-10-18 Time   Rev Time 0.00
Received By kmartin Date 2017-10-18 Time 09:28 Sent To I
Notes
2017-10-18 09:29:31PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED. THIS PROCESS
 WILL REQUIRE A PLANNED DEVELOPMENT MINOR AMENDMENT. FOR
 MORE INFORMATION, PLEASE CONTACT KEVIN MARTIN -URBAN
 DESIGN PLANNER AT [email protected].

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-31 Cont ID  
Sent By   Date 2017-08-31 Time   Rev Time 0.00
Received By kmartin Date 2017-08-31 Time 15:36 Sent To I
Notes
2017-08-31 15:38:291. PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT FOR ALL
 LANDSCAPE CHANGES.
 2. PLEASE PROVIDE LEASE AGREEMENT CONFIRMING THAT WORK
 ON THE CITY PROPERTY CAN BE ALTERED.
  
 FOR MORE INFORMATION, PLEASE CONTACT KEVIN MARTIN
 -URBAN DESIGN PLANNER AT [email protected].
  