Plan Review Details - Permit 17080021
Plan Review Stops For Permit 17080021
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-14 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-09 Time 11:46 Sent To  
Notes
2017-08-10 11:46:18RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-08 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-01 Time 12:35 Sent To  
Notes
2017-08-02 12:35:18REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-14 Cont ID  
Sent By ccole Date 2017-08-14 Time 11:38 Rev Time 0.00
Received By ccole Date 2017-08-14 Time 11:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-08 Cont ID  
Sent By ccole Date 2017-08-08 Time 10:21 Rev Time 0.00
Received By ccole Date 2017-08-08 Time 10:20 Sent To  
Notes
2017-08-08 10:32:401ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080021
 8/8/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WPB CONSTRUCTION SERVICES RECORDS FOR THE MASTER AND
 SUB-PERMITS ON THE PROJECT DO NOT SHOW A VALUE FOR THE
 MECHANICAL SCIOPE OF WORK. PLEASE PROVIDE ON THE
 REVISION FORM THE INCREASED VALUE FOR THE AC CHANGE OUT
 AND DUCTWORK ASSOCIATED WITH THE PROJECT- SECTION 109.3
 WPB AMENDMENTS TO THE FBC.
  
 2) PLEASE CLARIFY THE SCOPE OF WORK FOR THE DUCTWORK-
 IS THIS A COMPLETE OR PARTIAL REPLACEMENT?
  
 3) SHOW THE SUPPLY CFMS AT EACH DIFFUSER, AND PROVIDE
 RETURN AIR FROM THE BEDROOMS- SECTION 601.5
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved