Plan Review Details - Permit 17071273
Plan Review Stops For Permit 17071273
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-10 Cont ID  
Sent By jwitmer Date 2017-08-10 Time 14:18 Rev Time 0.00
Received By jwitmer Date 2017-08-09 Time 09:28 Sent To  
Notes
2017-08-10 14:18:382014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17071273
 ADD: 5829 CORPORATE WAY / PUBLIC CHARTER SCHOOL
 CONT: SOUTHSHORE BUILDERS
 TEL: 772-618-0169
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED.- THURS. AUGUST 09 & 10/2017
 ACTION: DENIED
  
 1A) COVERSHEET. THE PLANS LIST THIS AS A BUSINESS
 OCCUPANCY. PLEASE PROVIDE THE CURRENT OCCUPANCY. THE
 LAST BUSINESS LICENSES THAT WERE CLOSED SHOULD THIS TO
 BE A PUBLIC CHARTER SCHOOL. THERE IS STILL A ACTIVE
 LICENSE FOR A CHARTER SCHOOL. YOU HAVE THE OCCUPANCY AS
 A BUSINESS, PLEASE PROVIDE WHAT TYPES OF ACTIVITIES ARE
 GOING TO BE CONDUCTED WITHIN THE CONFINES OF THIS
 BUSINESS? 2014 FBC-B 304.1 VERSES 305.1. EITHER THE
 LEVEL OF ALTERATION MAY CHANGE OR THE OCCUPANCY TYPE
 MAY CHANGE.
 PLEASE NOTE IGENERATION EMPOWER ACADEMY HAD NEVER COME
 IN FOR A CHANGE IN OCCUPNCY!!!!!
 IN 13090021 THERE WAS A EXPIRED PERMIT (NEVER ISSUED)
 TO WIDEN THE CORRIDORS.
 NOTE IF THIS IS A CHARTER SCHOOL THERE WILL BE
 ADDITIONAL COMMENTS ONCE THE OCCUPANCY IS DECLARED.
  
 1B) SHEET A1.1. THE 1ST FLOOR PHASE 1. THE PLANS
 INDICATE A DOOR # 18 AS A 45 MIN. FIRE RATED DOOR WHERE
 THE PLANS DO NOT SHOW THE ELECTRIC ROOM AS FIRE RATED;
 ONLY THE MAIN ELECTRICAL ROOM IS REQUIRED TO BE FIRE
 RATED. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET A1.1. THE 1ST FLOOR HAS A ROOM LABELED WORK
 OUT AREA. THIS AREA WAS A MULTI-PURPOSE ROOM WITH
 ADDITIONAL OFFICES. THIS IS A CHANGE IN USE AND
 OCCUPANCY. ROOM 108 IS CLASSIFIED AS A WORK OUT ROOM OR
 A A-3 OCCUPANCY. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B
 TABLE 508.4. ASSEMBLY OCCUPANCY IN A NON-SPRINKLERED
 BUILDING REQUIRES 2 HOUR FIRE SEPARATION AND 1 ? HOUR
 OPENING PROTECTION. FBC-B TABLE 716.5.
 WILL THE STORAGE ROOMS 109 & 110 BE PART OF THE WORK
 OUT ROOM, WHERE WILL THE OCCUPANCY SEPARATION WALL BE
 PLACED?
  
 3) SHEET A.1.1. PLEASE PROVIDE THE SQUARE FOOTAGE OF
 THIS ROOM. THE SQUARE FOOTAGE IS DEFINITELY OVER THE
 10% OF THE FLOOR AREA. WORK OUT ROOMS WITHOUT EQUIPMENT
 IS FIGURED AT 15 SQ. FT./ OCCUPANT. WHEN EQUIPMENT IS
 SHOWN THE OCCUPANT LOAD IS FIGURED AT 50 SQ. FT./
 OCCUPANT. DOORS SHALL SWING IN THE DIRECTION OF EGRESS
 TRAVEL WHERE SERVING A ROOM OR AREA CONTAINING AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS. 2014 FBC-B
 1008.1.2.
  
 4) SHEET A.1.1. THE LECTURE HALL ROOM 111 PLEASE
 PROVIDE THE SQUARE FOOTAGE OF THIS ROOM. LECTURE HALLS
 ARE ALSO CONSIDERED AN A3 OCCUPANCY. NO OCCUPANCY
 SEPARATION IS REQUIRED BETWEEN THE LECTURE HALL AND THE
 WORK OUT ROOM, BUT THE 2 HOUR FIRE RATING WILL NEED TO
 BE EXTENDED DOWN CORRIDOR 112 AND 1 ? HOUR PROTECTIVES
 ON THE DOOR OPENINGS.
  
 5A) SHEET A.1.1. WITHIN THE LECTURE HALL THERE IS ONLY
 ONE MEANS OF EGRESS, WITH A OCCUPANT LOAD OF 50 OR MORE
 (2) MEANS OF EGRESS WILL BE REQUIRED. SEE 2014 FBC-B
 TABLE 1015.1.
  
 5B) SHEET A1.1. THE 2 REQUIRED MEANS OF EGRESS ANY
 PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR EXIT
 ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART EQUAL
 TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE MAXIMUM
 OVERALL DIAGONAL DIMENSION OF THE BUILDING OR AREA TO
 BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN EXIT
 DOORS OR EXIT ACCESS DOORWAYS. FBC-B 1015.2.1.
  
 6) SHEET A.1.1. THE 1ST FLOOR RESTROOMS AND A.2.1 THE
 2ND FLOOR RESTROOMS ARE BEING RE-CONFIGURED IN THE MENS
 RESTROOMS ON BOTH FLOORS. THE 1ST FLOOR, THE RELOCATING
 THE SHOWER AND THE 2ND FLOOR MENS RESTROOM THE
 ELIMINATION OF THE SHOWER. WHEN SHOWERS ARE PROVIDED
 THEY NEED TO BE PROVIDED FOR EACH SEX. SEE 103
 EQUIVALENT FACILITATION, 2014 FBC-ACCESSIBILITY CODE.
 PLEASE ALSO LOOK AT THE 20% DISPROPORTIONATE COST
 ASPECT IN 202.4.2(III) AND THE POSSIBILITY OF UNISEX
 RESTROOM WITH SHOWER TO BE USED BY BOTH SEXES .
  
 6A) THE 1ST FLOOR MENS BATHROOM (SHOWER) SINCE THE
 SHOWER IS BEING RELOCATED NEEDS TO COMPLY WITH: 2014
 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL
 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 6B) THE RELOCATED SHOWER WILL NEED TO BE ON AN
 ACCESSIBLE ROUTE, PLEASE PROVIDE THE DIMENSIONS FOR THE
 SHOWER, SHOW IF THERE IS TO BE A SEAT OR NOT, IS THIS A
 ROLL IN SHOWER, PROVIDE THE PLACEMENT OF VALVES,
 CONTROL WALL, BACKING FOR GRAB BARS, GRAB BARS SEE ALL
 OF SECTION 608 OF THE ACCESSIBILITY CODE, THERE IS NOT
 INFORMATION TO DO A THOROUGH REVIEW IN THE RESTROOMS.
  
 6C) THE VALUE OF THE WORK WILL BE INCREASING WITH THE
 INCREASED SCOPE OF WORK. ONE CODE ISSUE IS THE 20%
 DISPROPORTIONATE COST. PLEASE PROVIDE A BREAKDOWN OF
 HOW THE FUNDS WILL BE SPENT AND IN THE ORDER AS LISTED
 BELOW. SUBMIT ON THE CONTRACTORS LETTER HEAD A COST
 BREAK DOWN SHOWING COMPLIANCE WITH;
  
 2014 ACCESSIBILITY CODE. 202.4.2 ACCESSIBLE FEATURES IN
 THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 7) SHEET A2.1 IN THE MENS RESTROOM THE RESTROOM IS
 BEING RECONFIGURED, REMOVING THE SHOWER AND ADDING
 ANOTHER LAV. THE PLANS SHOW A DOOR WHERE THE NEW LAV IS
 TO BE INSTALLED, THERE IS NO MANEUVERING CLEARANCES ON
 THE LATCH SIDE OF THE DOOR. SHOW COMPLIANCE WITH 2014
 ACCESS. CODE 404.2.4 AND TABLE 404.2.4.1.
  
 8) PLEASE NOTE THIS IS A 2 STORY NON-SPRINKLERED
 BUILDING. SHEET A2.1 DOES SHOW THERE IS AN EXISTING
 ELEVATOR, BUT THERE IS NO AREA OF REFUGE. THE 2014
 ACCESSIBILITY CODE IN SECTION 207.1 REFERENCES THE 2003
 IBC SECTION 1007 OF THE IBC (INTERNATIONAL BUILDING
 CODE) . IN REVIEWING THE 2003 IBC IN SECTION 1007.6 THE
 AREA OF REFUGE HAS ITS REQUIREMENTS.
  
 2003 IBC-B 1007.6.1. SIZE. EACH AREA OF REFUGE SHALL BE
 SIZED TO ACCOMMODATE ONE WHEEL CHAIR SPACE OF 30 X 48
 INCHES FOR EACH 200 OCCUPANTS.
  
 2003 IBC-B 1007.6.2. SEPARATION. EACH AREA OF REFUGE
 SHALL BE SEPARATED FROM THE REMAINDER OF THE STORY BY A
 SMOKE BARRIER COMPLYING WITH 709. EACH AREA OF REFUGE
 SHALL BE DESIGNED TO MINIMIZE THE INTRUSION OF SMOKE.
 EXCEPTIONS:
 1) AREAS OF REFUGE LOCATED WITHIN A STAIRWAY ENCLOSURE.
 2) AREAS OF REFUGE WHERE THE AREA OF REFUGE AND AREAS
 SERVED BY THE AREA OF REFUGE ARE EQUIPPED THROUGHOUT
 WITH AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH 903.3.1.1 OR 903.3.1.2.
  
 2003 IBC-B 1007.6 .3 TWO-WAY COMMUNICATION. AREAS OF
 REFUGE SHALL BE PROVIDED WITH TWO-WAY COMMUNICATION
 SYSTEM BETWEEN THE AREA OF REFUGE AND A CONTROL POINT.
 IF THE CENTRAL CONTROL POINT IS NOT CONSTANTLY
 ATTENDED, THE AREA OF REFUGE SHALL ALSO HAVE CONTROLLED
 ACCESS TO A PUBLIC TELEPHONE SYSTEM. LOCATION OF THE
 CENTRAL CONTROL POINT SHALL BE APPROVED BY THE FIRE
 DEPARTMENT. TWO-WAY COMMUNICATION SYSTEM SHALL INCLUDE
 BOTH AUDIBLE AND VISIBLE SIGNALS.
  
 1007.6.4 INSTRUCTIONS. IN AREAS OF REFUGE THAT HAVE A
 TWO-WAY EMERGENCY COMMUNICATIONS SYSTEM, INSTRUCTIONS
 ON THE USE OF THE AREA UNDER EMERGENCY CONDITIONS SHALL
 BE POSTED ADJOINING THE COMMUNICATIONS SYSTEM. THE
 INSTRUCTIONS SHALL INCLUDE ALL OF THE FOLLOWING;
 1) DIRECTIONS TO FIND OTHER MEANS OF EGRESS.
 2) PERSONS ABLE TO USE THE EXIT STAIRWAY DO SO AS SOON
 AS POSSIBLE, UNLESS THEY ARE ASSISTING OTHERS.
 3) INFORMATION ON THE PLANNED AVAILABILITY OF
 ASSISTANCE IN THE USE OF STAIRS OR SUPERVISED OPERATION
 OF ELEVATORS AND HOW TO SUMMON SUCH ASSISTANCE. 4)
 DIRECTIONS FOR THE USE OF THE EMERGENCY COMMUNICATIONS
 SYSTEM.
  
 1007.6.5 IDENTIFICATION. EACH DOOR PROVIDING ACCESS TO
 AN AREA OF REFUGE FROM AN ADJACENT FLOOR AREA SHALL BE
 IDENTIFIED BY A SIGN COMPLYING WITH ICC A117., STATING
 AREA OF REFUGE, AND INCLUDING THE INTERNATIONAL SYMBOL
 OF ACCESSIBILITY. WHERE EXIT SIGN ILLUMINATION IS
 REQUIRED BY SECTION 1011.2, THE AREA OF REFUGE SIGN
 SHALL BE ILLUMINATED. ADDITIONALLY, TACTILE SIGNAGE
 COMPLYING WITH ICC A117.1 SHALL BE LOCATED AT EACH DOOR
 TO AN AREA OF REFUGE.
  
 1007.7. SIGNAGE. AT EXITS AND ELEVATORS SERVING A
 REQUIRED ACCESSIBLE SPACE BUT NOT PROVIDING AN APPROVED
 ACCESSIBLE MEANS OF EGRESS, SIGNAGE SHALL BE INSTALLED
 INDICATING THE LOCATION OF ACCESSIBLE MEANS OF EGRESS.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 10) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-24 Cont ID  
Sent By jpearson Date 2017-08-24 Time 14:36 Rev Time 0.00
Received By jpearson Date 2017-08-24 Time 14:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-07 Cont ID  
Sent By scaldero Date 2017-08-07 Time 14:44 Rev Time 0.00
Received By scaldero Date 2017-08-07 Time 14:36 Sent To  
Notes
2017-08-07 14:44:30PERMIT # 17071273
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENT:
  
 1) SHEETS LS.1 AND LS.2 LISTED UNDER INDEX, BUT NOT
 INCLUDED IN SUBMISSION. PROVIDE A LIFE SAFETY PLANS FOR
 EACH FLOOR SHOWING ALL OCCUPANCY TYPES, OCCUPANT LOADS,
 FIRE RATED WALLS, EXIT SIGNS, EMERGENCY LIGHTING,
 TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-30 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-31 Time 10:34 Sent To  
Notes
2017-08-02 10:34:24C10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-08-10 Cont ID  
Sent By jwitmer Date 2017-08-10 Time 14:19 Rev Time 0.00
Received By jwitmer Date 2017-08-09 Time 09:28 Sent To  
Notes
2017-08-10 14:19:19IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By ccole Date 2017-08-30 Time 08:49 Rev Time 0.00
Received By ccole Date 2017-08-29 Time 15:30 Sent To  
Notes
2017-08-30 08:55:161ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #17071273
 8/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) BASED ON THE BUILDING PLAN REVIEW COMMENT #1
 INDICATING THE PROPOSED PROJECT MAY BE A CHANGE OF
 OCCUPANCY, PLEASE REVIEW SECTION C101.4.6 FBC-14 ENERGY
 CONSERVATION AND PROVIDE A COMPLIANCE SUBMITTAL- SEE
 SECTION C401.2 FOR COMPLIANCE PATH INFORMATION.
  
 3) SHEETS M1.1 & M1.2: PLEASE PROVIDE AC EQUIPMENT
 SCHEDULES LISTING THE MAKES AND MODELS OF THE EXISTING
 SYSTEMS, AND THE SYSTEM CAPACITIES- COOLING AND HEATING
 BTUHS AND TOTAL SUPPLY CFMS.
  
 4) M1.1 & M1.2: SHOW THE RETURN AIR SYSTEMS. PLEASE
 NOTE THAT SMOKE DETECTORS MAY BE REQUIRED WHERE SYTEMS
 EXCEED 2000 CFMS IN CAPACITY- SECTION 606.2.1.
  
 5) M1.1: PLAN NOTE #3 INDICATES FIRE DAMPERS AT DUCT
 PENETRATIONS HOWEVER NO DUCTS ARE SHOWN AT THESE
 LOCATIONS. IT APPEARS THAT THE THESE ARE TRANSFER
 GRILLS. PLEASE REVIEW SECTION 601.2 WHICH PROHIBITS AIR
 TO BE TRANSFERRED TO A CORRIDOR AS A MEANS OF RETURNING
 AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2017-08-09 Cont ID  
Sent By jwitmer Date 2017-08-09 Time 13:34 Rev Time 0.00
Received By jwitmer Date 2017-08-09 Time 09:30 Sent To  
Notes
2017-08-09 13:34:262014 FBC- NFIP/ NATIONAL FLOOD INSURANCE PROGRAM PLAN
 REVIEW
 W. P. B. PERMIT: 17071273
 ADD: 5829 CORPORATE WAY
 CONT: SOUTHSHORE BUILDERS
 TEL: 772-618-0169
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 09/2017
 ACTION: PASSED
  
 FLOOD ZONE A-8
 FIRM MARCH 01/ 1979
 COMMUNITY-PANEL NUMBER:
 120229 0015 B
 EFECTIVEE DATE:
 MARCH 01/ 1979
  
 YEAR BUILT: 1985
  
 FLOOD ZONE A-8
 BASE FLOOD: ELE. 14.00 FT. NGVD
  
 BUILDING VALUE (IMPROVEMENT 2016) $1,047,250.00
 LATEST 5 YEAR VALUE OF IMPROVEMENTS $ 104,000.00
 PER CENT OF IMPROVEMENT VALUE 00.0999 %
 < 50% OF THE APPRAISED BUILDING VALUE
 __________________________________________
 NOT A SUBSTANIAL IMPROVEMENT / SEE ATTACHMENTS A-C.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-28 Cont ID  
Sent By thunt Date 2017-08-28 Time 14:29 Rev Time 0.00
Received By thunt Date 2017-08-25 Time 15:08 Sent To  
Notes
2017-08-28 14:36:41CITY RECORDS SHOWS THE EXISTING OCCUPANCY AS A SCHOOL.
 BEING THAT THIS IS A CHANGE OF OCCUPANCY ( BUSINESS) IT
 WOULD NEED TO COMPLY WITH 1012.1.1-10.12.1.1.12 AS WELL
 AS ALL OF CHAPTER 7,8, AND 9 OF THE FBC EXISTING
 BUILDING CODE. ALL COMMON AREA RESTROOMS MUST THEN
 FULLY COMPLY WITH FBC- ACCESSIBILITY 2014.
  
 AT THIS TIME A COMPLETE REVIEW OF THESE PLANS IS NOT
 ABLE TO BE DONE UNTILL THE OCCUPANCY OF THIS BUILDING
 IS ADDRESSED
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  