Plan Review Details - Permit 17071263
Plan Review Stops For Permit 17071263
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By rmcdouga Date 2017-08-15 Time 19:09 Rev Time 0.00
Received By rmcdouga Date 2017-08-15 Time 17:18 Sent To  
Notes
2017-08-15 19:09:18APPROVED WITH EXCEPTIONS
 1) THE SCOPE OF WORK FOR THIS PERMIT DOES NOT INCLUDE
 REMOVING THE KITCHEN FLOORING OR INSTALLING THE KITCHEN
 CABINETS.
 2) A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED TO INSTALL FLOORING IN THE KITCHEN.
  
 "BUILDING PROVISO"
 SUBMIT TWO SETS OF TEST REPORTS FOR SOUND TRANSMISSION,
 FLAME SPREAD AND SMOKE DEVELOPED FOR THE SOUND
 INSULATION THAT WILL BE USED UNDER THE BATHROOM FLOOR
 TILES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-07 Cont ID  
Sent By rmcdouga Date 2017-08-07 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2017-08-07 Time 07:40 Sent To  
Notes
2017-08-07 09:06:39ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF DRAWINGS THAT CLEARLY SHOW THE
 BATHROOM DIMENSIONS AND THE SIZES OF THE NEW SHOWERS
 AND SHOWS COMPLIANCE WITH FBC-R307.1
  
 2) PLANS ARE REQUIRED TO BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE AND SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1.4
  
 3) THE DRAWINGS THAT WERE SUBMITTED INDICATE THAT THE
 EXISTING KITCHEN CABINETS ARE TO BE REMOVED. PLEASE
 CLARIFY IF THEY WILL BE REPLACED IN THE SAME
 CONFIGURATION OR NOT. FBC 107.2.1
  
 4) PROVIDE A DETAILED SCOPE OF THE PROPOSED WORK ON THE
 PLANS. FBC 107.2.1
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-15 Cont ID  
Sent By rmcdouga Date 2017-08-15 Time 19:09 Rev Time 0.00
Received By rmcdouga Date 2017-08-10 Time 11:10 Sent To  
Notes
2017-08-11 11:10:34RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-07 Cont ID  
Sent By rmcdouga Date 2017-08-07 Time 09:10 Rev Time 0.00
Received By rmcdouga Date 2017-07-31 Time 15:41 Sent To  
Notes
2017-08-01 15:42:09ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By rmcdouga Date 2017-08-15 Time 18:13 Rev Time 0.00
Received By rmcdouga Date 2017-08-15 Time 17:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-07 Cont ID  
Sent By rmcdouga Date 2017-08-07 Time 09:10 Rev Time 0.00
Received By rmcdouga Date 2017-08-07 Time 07:40 Sent To  
Notes
2017-08-07 08:43:40PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY PLUMBING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF DRAWINGS THAT CLEARLY SHOW THE
 BATHROOM DIMENSIONS AND THE SIZES OF THE NEW SHOWERS
 AND SHOWS COMPLIANCE WITH FBC-R307.1
  
 2) PLANS ARE REQUIRED TO BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE AND SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1.4
  
 3) SUBMIT TWO SETS OF SHOWER PAN DETAILS. FBC 107.2.1
  
 4) INDICATE IF THE DOUBLE LAVATORY IN BATH NUMBER 1 IS
 EXISTING OR AN ADDITIONAL LAVATORY IS BEING ADDED. FBC
 107.2.1
  