Plan Review Details - Permit 17071262
Plan Review Stops For Permit 17071262
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By cthroop Date 2017-08-25 Time 10:05 Rev Time 0.00
Received By cthroop Date 2017-08-25 Time 09:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-07 Cont ID  
Sent By cthroop Date 2017-08-07 Time 11:13 Rev Time 0.00
Received By cthroop Date 2017-08-07 Time 11:06 Sent To  
Notes
2017-08-07 11:17:09BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. FOUNDATION DETAIL ON PLAN PAGE A 14 LACKS DETAIL.
 PROVIDE CONRETE PSI AND SPECIFY RE-INFORCEMENT SIZE AND
 PLACEMENT.
 2. PROVIDE DESIGN WIND LOADS PER FBC CHPT. R301.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-11-28 Cont ID  
Sent By jleahy Date 2017-11-28 Time 11:36 Rev Time 0.00
Received By jleahy Date 2017-11-28 Time 11:36 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-08-25 Cont ID  
Sent By jleahy Date 2017-08-25 Time 07:21 Rev Time 0.00
Received By jleahy Date 2017-08-25 Time 07:21 Sent To B
Notes
2017-08-25 07:31:11SEE ORIGINAL PLAN REVIEW FOR DEFICEINCIES

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-08 Cont ID  
Sent By jleahy Date 2017-08-08 Time 11:39 Rev Time 0.00
Received By jleahy Date 2017-08-08 Time 11:39 Sent To  
Notes
2017-08-08 11:43:25FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED A CLEAR PLAN OF THE ELECTRICAL WORK BEING
 PERFORMED.
  
 SCETCH SHOWS WIRES RUNNING THRU METAL FRAMING MEMBERS
 THIS WOULD NOT BE ACCEPTABLE, NO GROUND WIRE SHOWN AND
 OPEN CONDUCTORS.
  
 SOME TYPE OF CABLE WOULD BE RQUIRED IN ORDER TO WIRE
 THIS ROOM.
  
 SHOW WHERE POWER COMES FROM AND HOW DC MOTORS GET THEIR
 POWER
  
 FAN TO BE LISTED FOR WET LOCATION NAD LIGHT FIXTURES IF
 USED....

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-28 Cont ID  
Sent By jleahy Date 2017-11-28 Time 11:36 Rev Time 0.00
Received By jleahy Date 2017-11-22 Time 13:18 Sent To  
Notes
2017-11-27 13:18:17RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-25 Cont ID  
Sent By cthroop Date 2017-08-25 Time 10:05 Rev Time 0.00
Received By cthroop Date 2017-08-18 Time 13:39 Sent To  
Notes
2017-08-21 13:39:46RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-08 Cont ID  
Sent By cthroop Date 2017-08-08 Time 11:43 Rev Time 0.00
Received By jleahy Date 2017-07-31 Time 15:38 Sent To  
Notes
2017-08-01 15:38:34ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-23 Cont ID  
Sent By njwira Date 2017-08-23 Time 15:01 Rev Time 0.00
Received By njwira Date 2017-08-21 Time 17:35 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-04 Cont ID  
Sent By njwira Date 2017-08-04 Time 14:21 Rev Time 0.00
Received By njwira Date 2017-08-02 Time 08:57 Sent To B
Notes
***NONE***