Plan Review Details - Permit 17071260
Plan Review Stops For Permit 17071260
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By shill Date 2017-08-16 Time 10:24 Rev Time 0.00
Received By shill Date 2017-08-15 Time 17:09 Sent To  
Notes
2017-08-16 10:25:37****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 ISSUED AT APPLICANT'S RISK
  
 PER ARCHITECT AND CONTRACTOR, THE ELEVATOR LOBBY AND
 ATTACHED CORRIDOR WILL NOT BE DEMOLISHED UNDER THIS
 PERMIT. THIS WORK WILL BE A PART OF THE TENANT BUILDOUT
 PERMIT NOT YET SUBMITTED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-02 Cont ID  
Sent By shill Date 2017-08-02 Time 12:45 Rev Time 0.00
Received By shill Date 2017-08-02 Time 12:45 Sent To  
Notes
2017-08-02 12:50:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. INDIVIDUAL AND COMPANY RESPONSIBLE FOR DESIGN IS NOT
 CLEAR. PER WEBSITE B-DOC.NET, PRINCIPLE IS AN
 ARCHITECT. REVISE PLAN TO INCLUDE ARCHITECT NAME,
 LICENSE NUMBER, SEAL, ETC. (FS481).
  
 2. SCOPE NOT CLEAR, A FLOOR PLAN IS SHOWN BUT NO WORK
 INDICATED, REVISE TO CLARIFY, FBC 107.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By jpearson Date 2017-08-16 Time 11:19 Rev Time 0.00
Received By jpearson Date 2017-08-16 Time 11:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-02 Cont ID  
Sent By jpearson Date 2017-08-02 Time 07:45 Rev Time 0.00
Received By jpearson Date 2017-08-02 Time 07:44 Sent To P
Notes
2017-08-02 07:44:54CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC
 107.2.1, FS 471, 481
 2. PLAN SUBMITTED DOES NOT PROVIDE ANY DETAILS OF THE
 DEMO WORK PROPOSED. PROVIDE SCOPE OF WORK AND SHOW
 DETAILS ON PLAN. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-21 Cont ID  
Sent By thunt Date 2017-08-21 Time 15:25 Rev Time 0.00
Received By thunt Date 2017-08-14 Time 09:45 Sent To  
Notes
2017-08-16 09:27:368/16 REMOVED MECHANICAL STOP PER SAK
  
  
2017-08-15 09:45:46C13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-15 Cont ID  
Sent By cpuell Date 2017-08-15 Time 09:40 Rev Time 0.00
Received By cpuell Date 2017-07-31 Time 15:43 Sent To  
Notes
2017-08-01 15:43:19B15

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-21 Cont ID  
Sent By thunt Date 2017-08-21 Time 15:24 Rev Time 0.00
Received By thunt Date 2017-08-21 Time 15:14 Sent To  
Notes
2017-08-21 15:25:32PLUMBING SUB PERMIT REQUIRED
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-11 Cont ID  
Sent By thunt Date 2017-08-11 Time 15:52 Rev Time 0.00
Received By thunt Date 2017-08-11 Time 15:49 Sent To  
Notes
2017-08-11 15:51:131) PLANS NOT SIGNED AND SEAL BY DESIGN PROFESSIONAL FBC
 107.2.1
 2) THE PLANS SHOULD CLEALY DETAIL THE ENTIRE SCOPE OF
 WORK BEING COMPLETED FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6696
 [email protected]
  